Schneider Electric InduSoft Web Studio and InTouch Machine Edition 2014 Vulnerabilities
OVERVIEW
Gleb Gritsai, Ilya Karpov, and Kirill Nesterov of Positive Technologies Security Lab and independent researcher Alisa Esage Shevchenko have identified vulnerabilities in the Schneider Electric InduSoft Web Studio and InTouch Machine Edition 2014. Schneider Electric has released new patches that mitigate these vulnerabilities.
Public exploits that target these vulnerabilities may exist.
AFFECTED PRODUCTS
The following Schneider Electric products are affected:
- InduSoft Web Studio, Version 7.1.3.2 and all previous versions and
- InTouch Machine Edition 2014, version 7.1.3.2 and all previous versions.
IMPACT
An attacker who exploits these vulnerabilities may be able to execute arbitrary code.
Impact to individual organizations depends on many factors that are unique to each organization. NCCIC/ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
BACKGROUND
Schneider Electric’s corporate headquarters is located in Paris, France, and maintains offices in more than 100 countries worldwide.
The affected products, Schneider Electric Wonderware InTouch Machine Edition and Schneider Electric InduSoft Web Studio, are embedded HMI software packages. According to Schneider Electric, these products are used in energy management operations in the Commercial Facilities, Energy, Food and Agriculture, and Information Technology sectors globally.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
USE OF HARD-CODED CREDENTIALSCWE-798: Use of Hard-coded Credentials, http://cwe.mitre.org/data/definitions/798.html, web site last accessed March 26, 2015.
Sensitive information is stored in Project Files and Project Configuration Files. This information is protected using a hard-coded, clear text password.
CVE-2015-0996NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-0996, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. Schneider Electric has assigned a CVSS v2 base score of 4.7; the CVSS vector string is (AV:L/AC:M/Au:N/C:C/I:N/A:N).CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:L/AC:M/Au:N/C:C/I:N/A:N, web site last accessed March 26, 2015.
AUTHENTICATIONCWE-287: Improper Authentication, http://cwe.mitre.org/data/definitions/287.html, web site last accessed March 26, 2015.
When connecting to server from HMI, available user names are presented to the screen allowing for potential brute force attacks.
CVE-2015-0997NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-0997, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. Schneider Electric has assigned a CVSS v2 base score of 3.3; the CVSS vector string is (AV:A/AC:L/Au:N/C:P/I:N/A:N).CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:A/AC:L/Au:N/C:P/I:N/A:N, web site last accessed March 26, 2015.
CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATIONCWE-319: Cleartext Transmission of Sensitive Information, http://cwe.mitre.org/data/definitions/319.html, web site last accessed March 26, 2015.
User credentials are sent in clear text allowing for malicious actors to access the control system.
CVE-2015-0998NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-0999, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. Schneider Electric has assigned a CVSS v2 base score of 3.3; the CVSS vector string is (AV:A/AC:L/Au:N/C:P/I:N/A:N).CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:A/AC:L/Au:N/C:P/I:N/A:N, web site last accessed March 26, 2015.
CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATIONCWE-319: Cleartext Transmission of Sensitive Information, http://cwe.mitre.org/data/definitions/319.html, web site last accessed March 26, 2015.
OPC User Credentials are stored in a configuration file in cleartext.
CVE-2015-0999NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-0999, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. Schneider Electric has assigned a CVSS v2 base score of 5.2; the CVSS vector string is (AV:L/AC:L/Au:S/C:C/I:P/A:N).CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:L/AC:L/Au:S/C:C/I:P/A:N, web site last accessed March 26, 2015.
VULNERABILITY DETAILS
EXPLOITABILITY
These vulnerabilities could be exploited from an adjacent network.
EXISTENCE OF EXPLOIT
Public exploits that target these vulnerabilities may exist.
DIFFICULTY
An attacker with a low skill would be able to exploit these vulnerabilities.
MITIGATION
Schneider Electric has two divisions supporting this product under separate organizations. Patch availability and technical information is available at these separate divisional support units. Schneider Electric has issued separate security notices for each specific division/product support center.
SEVD-2015-054-01 – InduSoft Web Studio
Schneider Electric has released patches, available for download, to remediate the noted vulnerabilities.
The patch for InduSoft Web Studio, Version 7.1.3.4, Service Pack 3, Patch 4, is available for download using this URL:
http://www.indusoft.com/dev/INDUSOFT/Release/IWS71.3.4/IWS71.3.4.zip
SEVD-2015-054-02 - InTouch Machine Edition 2014
This document is intended to help provide an overview of the identified vulnerability and actions required to mitigate it. To obtain full details on the issues and assistance on how to protect your installation, please contact your local Schneider Electric representative. These organizations will be fully aware of the situation and can support you through the process.
For further information on vulnerabilities in Schneider Electric’s products, please visit Schneider Electric’s cybersecurity web page at:
http://www2.schneider-electric.com/sites/corporate/en/support/cybersecurity/cybersecurity.page
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Schneider Electric
