Archived Content

In an effort to keep CISA.gov current, the archive contains outdated information that may not reflect current policy or programs.
ICS Advisory

Siemens SCALANCE X Switches (Update C)

Last Revised
Alert Code
ICSA-21-012-02

1. EXECUTIVE SUMMARY

  • CVSS v3 9.1
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SCALANCE X200, X200IRT, X300
  • Vulnerabilities: Use of Hard-coded Cryptographic Key

2. UPDATE INFORMATION

This updated advisory is a follow-up to the advisory update titled ICSA-21-012-02 Siemens SCALANCE X Switches (Update B) that was published February 14, 2021, to the ICS webpage on us-cert.cisa.gov.

3. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to execute a man-in-the-middle attack and decrypt previously captured traffic.

4. TECHNICAL DETAILS

4.1 AFFECTED PRODUCTS

The following Siemens products are affected:

  • SCALANCE X-200 switch family (incl. SIPLUS NET variants): All versions prior to v5.2.5

--------- Begin Update C Part 1 of 2 ---------

  • SCALANCE X-200RNA switch family: All versions prior to v3.2.7

--------- End Update C Part 1 of 2 ---------

  • SCALANCE X-200IRT switch family (incl. SIPLUS NET variants): All versions prior to v5.5.0
  • SCALANCE X-300 switch family (incl. X408 and SIPLUS NET variants): All versions prior to v4.1.0

4.2 VULNERABILITY OVERVIEW

4.2.1    USE OF HARD-CODED CRYPTOGRAPHIC KEY CWE-321

Devices create a new unique key upon factory reset, except when used with C-PLUG. When used with C-PLUG the devices use the hardcoded private RSA-key shipped with the firmware-image. An attacker could exploit this vulnerability to create a man-in-the-middle situation and decrypt previously captured traffic.

CVE-2020-28391 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).

4.2.2    USE OF HARD-CODED CRYPTOGRAPHIC KEY CWE-321

Devices do not create a new unique private key after factory reset. An attacker could exploit this vulnerability to create a man-in-the-middle situation and decrypt previously captured traffic.

CVE-2020-28395 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).

4.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Multiple Sectors
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

4.4 RESEARCHER

Siemens ProductCERT reported these vulnerabilities to CISA.

5. MITIGATIONS

Siemens recommends applying updates where available:

--------- Begin Update C Part 2 of 2 ---------

--------- End Update C Part 2 of 2 ---------

Siemens has identified the following specific workarounds and mitigations users can apply to reduce the risk:

  • Update the default self-signed device X.509 certificates with own trusted certificate.
  • Update the default hardcoded X.509 certificates from the firmware image (fingerprints SHA-1: F2:C8:3B:8F:86:27:74:AA:60:EC:D4:A0:CF:0D:BE:A6:D1:FE:22:12 and SHA-256: 25:60:DB:B3: F9:07:9D:69:0E:DD:A9:EB:4E:1C:D5:8E:AF:79:16:C3:C8:13:A6:F6:59:AD:05:E4:6F:77:F7:72)

As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to the Siemens operational guidelines for Industrial Security and following the recommendations in the product manuals.

For additional information, please refer to Siemens Security Advisory SSA-274900

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.



CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.



Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.

This product is provided subject to this Notification and this Privacy & Use policy.

Vendor

  • Siemens