Archived Content
In an effort to keep CISA.gov current, the archive contains outdated information that may not reflect current policy or programs.Emerson DeltaV Multiple Vulnerabilities
Overview
ICS-CERT originally released Advisory ICSA-12-138-01P to the US-CERT secure portal on May 17, 2012, and released Update A on May 21, 2012. This web page release (including Update A) was delayed to allow users time to download and install the update.
Researcher Kuang-Chun Hung of the Security Research and Service InstituteInformation and Communication Security Technology Center (ICST) has identified multiple vulnerabilities in the Emerson DeltaV application.
These vulnerabilities can be exploited by a remote attacker; however, no publicly available exploits are currently known to exist. Emerson has produced a hotfix that mitigates these vulnerabilities. ICST has tested this hotfix and confirms that it fully resolves the vulnerabilities.
Affected Products
The following Emerson products are affected:
- DeltaV and DeltaV Workstations,
- V9.3.1, V10.3.1, V11.3, and V11.3.1,
- DeltaV ProEssentials Scientific Graph, and
- V5.0.0.6
Impact
These vulnerabilities, if exploited, could allow denial of service, information disclosure, or remote code execution.
Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
Background
Emerson is a global manufacturing and technology company offering multiple products and services in the industrial, commercial, and consumer markets through its network power, process management, industrial automation, climate technologies, and tools and storage businesses.
Vulnerability Characterization
Vulnerability Overview
Cross Site Scriptinghttp://cwe.mitre.org/data/definitions/79.html, Web site last accessed May 30, 2012.
This vulnerability enables an attacker to inject client side script into web pages viewed by other users or bypass client side security mechanisms imposed by modern web browsers. If successfully exploited, this vulnerability could allow arbitrary code execution and may require social engineering to exploit.
CVE-2012-1814http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-1814, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS V2 base score of 7.5 has also been assigned.
SQL Injectionhttp://cwe.mitre.org/data/definitions/89.html, Web site last accessed May 30, 2012.
This vulnerability can be used by an attacker to perform database operations that were unintended by the web application designer and, in some instances, can lead to total compromise of the database server. This vulnerability, if successfully exploited, could allow arbitrary code execution.
CVE-2012-1815http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-1815, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS V2 base score of 7.5 has also been assigned.
Denial of Servicehttp://cwe.mitre.org/data/definitions/400.html, Web site last accessed May 30, 2012.
A denial of service can be created by sending a specially crafted packet to PORTSERV.exe on both TCP/111 and UDP/111. This attack will cause the software to crash, denying service to legitimate users.
CVE-2012-1816http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-1816, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS V2 base score of 5 has also been assigned.
Buffer Overflowhttp://cwe.mitre.org/data/definitions/119.html, Web site last accessed May 30, 2012.
In the affected version, DeltaV does not properly sanitize the inputs from project files. Invalid information in certain fields can cause the program to crash and could be used to execute arbitrary code.
CVE-2012-1817http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-1817, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS V2 base score of 4.6 has also been assigned.
File Manipulationhttp://cwe.mitre.org/data/definitions/618.html, Web site last accessed May 30, 2012.
If successfully exploited, an attacker can overwrite arbitrary files on the victim’s computer in the context of the vulnerable application using the ActiveX control.
CVE-2012-1818http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-1818, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS V2 base score of 7.5 has also been assigned.
Vulnerability Details
Exploitability
These vulnerabilities are remotely exploitable.
Existence of Exploit
No known exploits specifically target this vulnerability.
Difficulty
An attacker with a medium skill level would be able to exploit these vulnerabilities.
Mitigation
Emerson has created a hotfix that resolves these vulnerabilities.
Emerson has distributed a notification in KBA NK-1200-0091 ICS-CERT ADVISORY—ICSA-12-137-01 Emerson Multiple Vulnerabilities: Impact and Recommended Actions to customers who own a DeltaV Control System; the notification provides details of the vulnerabilities, recommended mitigations, and instructions on obtaining and installing the hotfix.
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices. Critical devices should not directly face the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPN is only as secure as the connected devices.
The Control Systems Security Program (CSSP) also provides a section for control systems security recommended practices on the CSSP web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to taking defensive measures.
In addition, ICS-CERT recommends that users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open unsolicited attachments in email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Emerson