Archived Content
In an effort to keep CISA.gov current, the archive contains outdated information that may not reflect current policy or programs.Advantech WebAccess Vulnerabilities
OVERVIEW
NCCIC/ICS-CERT received a report from the Zero Day Initiative (ZDI) concerning vulnerabilities affecting the Advantech WebAccess application. These vulnerabilities were reported to ZDI by security researchers Dave Weinstein, Tom Gallagher, John Leitch, and others. Advantech has produced an updated software version that mitigates these vulnerabilities.
These vulnerabilities could be exploited remotely. Exploits that target these vulnerabilities are known to be publicly available.
AFFECTED PRODUCTS
The following Advantech WebAcess versions are affected:
- Advantech WebAcess v7.1 and earlier.
IMPACT
An attacker exploiting these vulnerabilities in WebAccess may be able to bypass authentication or cause a denial of service.
Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
BACKGROUND
Advantech is based in Taiwan and has distribution offices in 21 countries worldwide.
Advantech WebAccess, formerly known as BroadWin WebAccess, is a web-based SCADA and human-machine interface product used in energy, critical manufacturing, commercial facilities, and government facilities. These systems are deployed globally.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
STACK-BASED BUFFER OVERFLOWSCWE-121: Stack-Based Buffer Overflow, http://cwe.mitre.org/data/definitions/121.html, web site last accessed July 17, 2014.
There are multiple ways to overflow the static stack buffer by providing overly long strings to specific parameters (namely ProjectName, SetParameter, NodeName, CCDParameter, SetColor, AlarmImage, GetParameter, GetColor, ServerResponse, SetBaud, and IPAddress) within the webvact.ocx, dvs.ocx, and webdact.ocx ActiveX files.
CVE-2014-2364NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-2364 , NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. has been assigned to these vulnerabilities. A CVSS v2 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:N/C:P/I:P/A:P).CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:P/I:P/A:P, web site last accessed July 17, 2014.
UNSAFE ACTIVEX CONTROL MARKED SAFE FOR SCRIPTINGCWE-623: Unsafe ActiveX Control Marked Safe For Scripting, http://cwe.mitre.org/data/definitions/623.html, web site last accessed July 17, 2014.
The bwocxrun ActiveX control (installed by default as part of setup) allows navigation from the Internet to a local file. This is accomplished through the BrowseFolder method.
CVE-2014-2368NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-2368, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS v2 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:N/C:P/I:P/A:P).CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:P/I:P/A:P, web site last accessed July 17, 2014.
REMOTE AUTHENTICATION BYPASSCWE-592: Authentication Bypass Issues, http://cwe.mitre.org/data/definitions/592.html, web site last accessed July 17, 2014.
The ChkCookie subroutine within broadweb\include\gChkCook.asp ActiveX control (installed by default as part of setup) allows navigation from the Internet to a local file. If user, proj, and scada are set, and bwuser is set to true, this will grant access to several previously restricted pages.
CVE-2014-2367NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-2367, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS v2 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:N/C:P/I:P/A:P).CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:P/I:P/A:P, web site last accessed July 17, 2014.
PASSWORD DISCLOSURECWE-316: Cleartext Storage of Sensitive Information in Memory, http://cwe.mitre.org/data/definitions/316.html, web site last accessed July 17, 2014.
The upAdminPg.asp component includes the password of the specified account in the underlying HTML when serving the page.
CVE-2014-2366NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-2366, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS v2 base score of 9.0 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:S/C:C/I:C/A:C). CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:S/C:C/I:C/A:C, web site last accessed July 17, 2014.
REMOTE CODE EXECUTIONCWE-284: Improper Access Control, http://cwe.mitre.org/data/definitions/284.html, web site last accessed July 17, 2014.
Advantech WebAccess contains a flaw that enables a malicious user to arbitrarily create and delete files.
CVE-2014-2365NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-2365, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS v2 base score of 6.5 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:S/C:P/I:P/A:P).CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:S/C:P/I:P/A:P, web site last accessed July 17, 2014.
VULNERABILITY DETAILS
EXPLOITABILITY
These vulnerabilities could be exploited remotely.
EXISTENCE OF EXPLOIT
Exploits that target these vulnerabilities are publicly available.
DIFFICULTY
An attacker with a moderate skill would be able to exploit these vulnerabilities.
MITIGATION
Advantech released a new WebAccess Installation Package v7.2 on June 6, 2014, that removes some vulnerable ActiveX components and resolves the vulnerabilities within others. The download link for v7.2 is available at:
http://webaccess.advantech.com/
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Advantech