ICS Advisory

Rockwell Automation 1794-AENT Flex I/O Series B

Last Revised
Alert Code
ICSA-20-294-01

1. EXECUTIVE SUMMARY

  • CVSS v3 7.5
  • ATTENTION: Exploitable remotely/low skill level to exploit
  • Vendor: Rockwell Automation
  • Equipment: 1794-AENT Flex I/O Series B
  • Vulnerabilities: Classic Buffer Overflow

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could crash the device being accessed, resulting in a buffer overflow condition that may allow remote code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of 1794-AENT Flex I/O Series B, an Ethernet/IP adapter, are affected:

  • 1794-AENT Flex I/O, Series B, Versions 4.003 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1    BUFFER COPY WITHOUT CHECKING SIZE OF INPUT ('CLASSIC BUFFER OVERFLOW') CWE-120

A buffer overflow vulnerability exists in the Ethernet/IP Request Path Port Segment. This vulnerability could allow a remote, unauthenticated attacker to send a malicious packet resulting in a denial-of-service condition on the device. 

CVE-2020-6083 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.2    BUFFER COPY WITHOUT CHECKING SIZE OF INPUT ('CLASSIC BUFFER OVERFLOW') CWE-120

A buffer overflow vulnerability exists in the Ethernet/IP Request Path Logical Segment. This vulnerability could allow a remote, unauthenticated attacker to send a malicious packet resulting in the device entering a fault state, causing a denial-of-service condition. 

CVE-2020-6084 and CVE-2020-6085 have been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.3    BUFFER COPY WITHOUT CHECKING SIZE OF INPUT ('CLASSIC BUFFER OVERFLOW') CWE-120

A buffer overflow vulnerability exists in the Ethernet/IP Request Path Data Segment. This vulnerability could allow a remote, unauthenticated attacker to send a malicious packet resulting in the device entering a fault state, causing a denial-of-service condition. 

CVE-2020-6086 and CVE-2020-6087 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Jared Rittle of Cisco Talos reported these vulnerabilities to Rockwell Automation.

4. MITIGATIONS

Rockwell Automation recommends affected users ensure they are employing proper network segmentation and security controls when implementing the affected product.

For more information please see the Rockwell Automation Security Advisory (login required).

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.



CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.



Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks: 

No known public exploits specifically target these vulnerabilities.