ICS Advisory

Advantech iView

Last Revised
Alert Code
ICSA-22-179-03

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Advantech
  • Equipment: iView
  • Vulnerabilities: SQL Injection, Missing Authentication for Critical Function, Relative Path Traversal, Command Injection

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to read or modify sensitive data, disclose information, or execute arbitrary code.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Advantech iView management software are affected:

  • Advantech iView: All versions prior to 5_7_04_6469

3.2 VULNERABILITY OVERVIEW

3.2.1    IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89

The affected product is vulnerable to multiple SQL injections, which may allow an unauthorized attacker to disclose information.

CVE-2022-2135 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.2    IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89

The affected product is vulnerable to multiple SQL injections that require low privileges for exploitation and may allow an unauthorized attacker to disclose information.

CVE-2022-2136 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.3    IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89

The affected product is vulnerable to two SQL injections that require high privileges for exploitation and may allow an unauthorized attacker to disclose information.

CVE-2022-2137 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N).

3.2.4    IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89

The affected product is vulnerable to a SQL injection with high attack complexity, which may allow an unauthorized attacker to disclose information.

CVE-2022-2142 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.5    MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306

The affected product is vulnerable due to missing authentication, which may allow an attacker to read or modify sensitive data and execute arbitrary code, resulting in a denial-of-service condition.

CVE-2022-2138 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H).

3.2.6    RELATIVE PATH TRAVERSAL CWE-23

The affected product is vulnerable to directory traversal, which may allow an attacker to access unauthorized files and execute arbitrary code.

CVE-2022-2139 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N).

3.2.7    IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN A COMMAND ('COMMAND INJECTION') CWE-77

The affected product is vulnerable to two instances of command injection, which may allow an attacker to remotely execute arbitrary code.

CVE-2022-2143 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Multiple Sectors
  • COUNTRIES/AREAS DEPLOYED: East Asia, Europe, United States
  • COMPANY HEADQUARTERS LOCATION: Taiwan

3.4 RESEARCHER

rgod, working with Trend Micro’s Zero Day Initiative, reported these vulnerabilities to CISA.

4. MITIGATIONS

Advantech recommends updating firmware to Version 5_7_4_6469 to address these vulnerabilities.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.

Vendor