ICS Advisory

Siemens SIMATIC S7-1500 CPU 1518(F)-4 PN/DP MFP V3.1

Release Date
Alert Code
ICSA-23-348-10

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).



View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SIMATIC S7-1500 CPU 1518(F)-4 PN/DP MFP V3.1
  • Vulnerabilities: Improper Restriction of XML External Entity Reference, Time-of-check Time-of-use (TOCTOU) Race Condition, Command Injection, Missing Encryption of Sensitive Data, Cross-site Scripting, Improper Restriction of Operations within the Bounds of a Memory Buffer, Use After Free, Improper Input Validation, Out-of-bounds Write, Out-of-bounds Read, Infinite Loop, Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection'), Allocation of Resources Without Limits or Throttling, Observable Discrepancy, Generation of Error Message Containing Sensitive Information, NULL Pointer Dereference, Integer Overflow or Wraparound, Uncontrolled Search Path Element, Double Free, Improper Encoding or Escaping of Output, Inappropriate Encoding for Output Context, Path Traversal, Improper Resource Shutdown or Release, Uncontrolled Resource Consumption, CRLF Injection, Encoding Error, Exposure of Resource to Wrong Sphere, Insufficient Entropy, Divide By Zero, Improper Check for Dropped Privileges, Improper Initialization, Incorrect Conversion between Numeric Types, Uncontrolled Recursion, Improper Check for Unusual or Exceptional Conditions, Improper Handling of Exceptional Conditions, Unrestricted Upload of File with Dangerous Type, Missing Release of Resource after Effective Lifetime, Missing Release of Memory after Effective Lifetime, Exposure of Sensitive Information to an Unauthorized Actor, Use of Insufficiently Random Values, Signed to Unsigned Conversion Error, Improper Certificate Validation, Incorrect Type Conversion or Cast, Classic Buffer Overflow, Authentication Bypass by Spoofing, Improper Privilege Management, Use of a Broken or Risky Cryptographic Algorithm, Incorrect Calculation, OS Command Injection, Untrusted Search Path, Reachable Assertion, Wrap or Wraparound, Release of Invalid Pointer or Reference, Type Confusion, XML Entity Expansion, Off-by-one Error, Insufficient Verification of Data Authenticity, Unchecked Return Value, Missing Initialization of Resource, Improper Validation of Integrity Check Value, Insufficiently Protected Credentials, Use of Incorrectly-Resolved Name or Reference, Use of Uninitialized Resource, Cleartext Transmission of Sensitive Information, Improper Link Resolution Before File Access ('Link Following'), Open Redirect, Inadequate Encryption Strength, Improper Authentication, SQL Injection, Server-Side Request Forgery (SSRF), Incorrect Default Permissions, Expected Behavior Violation, Improper Validation of Syntactic Correctness of Input, Stack-based Buffer Overflow, Improper Validation of Array Index, Inefficient Algorithmic Complexity, Inefficient Regular Expression Complexity, Excessive Iteration, Heap-based Buffer Overflow, Protection Mechanism Failure, Deserialization of Untrusted Data

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could result in sensitive information disclosure, tampering and deletion, or a denial-of-service condition.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following products of Siemens, are affected:

  • SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0): All versions prior to V3.1.0
  • SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0): All versions prior to V3.1.0
  • SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0): All versions prior to V3.1.0
  • SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0): All versions prior to V3.1.0
  • SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0): All versions prior to V3.1.0

3.2 Vulnerability Overview

3.2.1 IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE CWE-611

expat 2.1.0 and earlier does not properly handle entities expansion unless an application developer uses the XML_SetEntityDeclHandler function, which allows remote attackers to cause a denial-of-service (resource consumption), send HTTP requests to intranet servers, or read arbitrary files via a crafted XML document, aka an XML External Entity (XXE) issue. NOTE: it could be argued that because expat already provides the ability to disable external entity expansion, the responsibility for resolving this issue lies with application developers; according to this argument, this entry should be REJECTed, and each affected application would need its own CVE.

CVE-2013-0340 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.2.2 TIME-OF-CHECK TIME-OF-USE (TOCTOU) RACE CONDITION CWE-367

shadow: TOCTOU (time-of-check time-of-use) race condition when copying and removing directory trees

CVE-2013-4235 has been assigned to this vulnerability. A CVSS v3 base score of 4.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:N/I:H/A:N).

3.2.3 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN A COMMAND ('COMMAND INJECTION') CWE-77

run-mailcap in the Debian mime-support package before 3.52-1+deb7u1 allows context-dependent attackers to execute arbitrary commands via shell metacharacters in a filename.

CVE-2014-7209 has been assigned to this vulnerability. A CVSS v3 base score of 9.0 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:H).

3.2.4 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN A COMMAND ('COMMAND INJECTION') CWE-77

In Python (aka CPython) up to 3.10.8, the mailcap module does not add escape characters into commands discovered in the system mailcap file. This may allow attackers to inject shell commands into applications that call mailcap.findmatch with untrusted input (if they lack validation of user-provided filenames or arguments). The fix is also back-ported to 3.7, 3.8, 3.9.

CVE-2015-20107 has been assigned to this vulnerability. A CVSS v3 base score of 7.6 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:H/A:L).

3.2.5 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Use-after-free vulnerability in bzip2recover in bzip2 1.0.6 allows remote attackers to cause a denial-of-service (crash) via a crafted bzip2 file, related to block ends set to before the start of the block.

CVE-2016-3189 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.6 IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION ('CROSS-SITE SCRIPTING') CWE-79

A possible cross-site scripting vulnerability exists in libxml after commit 960f0e2.

CVE-2016-3709 has been assigned to this vulnerability. A CVSS v3 base score of 6.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N).

3.2.7 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

xpointer.c in libxml2 before 2.9.5 (as used in Apple iOS before 10, OS X before 10.12, tvOS before 10, and watchOS before 3, and other products) does not forbid namespace nodes in XPointer ranges, which allows remote attackers to execute arbitrary code or cause a denial-of-service (use-after-free and memory corruption) via a crafted XML document.

CVE-2016-4658 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.8 USE AFTER FREE CWE-416

Use-after-free vulnerability in libxml2 through 2.9.4, as used in Google Chrome before 52.0.2743.82, allows remote attackers to cause a denial-of-service or possibly have unspecified other impact via vectors related to the XPointer range-to function.

CVE-2016-5131 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.9 IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE CWE-611

libxml2 2.9.4 and earlier, as used in XMLSec 1.2.23 and earlier and other products, does not offer a flag directly indicating that the current document may be read but other files may not be opened, which makes it easier for remote attackers to conduct XML External Entity (XXE) attacks via a crafted document.

CVE-2016-9318 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N).

3.2.10 IMPROPER INPUT VALIDATION CWE-20

The iconv program in the GNU C Library (aka glibc or libc6) 2.31 and earlier, when invoked with multiple suffixes in the destination encoding (TRANSLATE or IGNORE) along with the -c option, enters an infinite loop when processing invalid multi-byte input sequences, leading to a denial of service.

CVE-2016-10228 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.11 IMPROPER INPUT VALIDATION CWE-20

In the GNU C Library (aka glibc or libc6) through 2.28, the getaddrinfo function would successfully parse a string that contained an IPv4 address followed by whitespace and arbitrary characters, which could lead applications to incorrectly assume that it had parsed a valid string, without the possibility of embedded HTTP headers or other potentially dangerous substrings.

CVE-2016-10739 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L).

3.2.12 OUT-OF-BOUNDS WRITE CWE-787

A remote code execution vulnerability in libxml2 could enable an attacker using a specially crafted file to execute arbitrary code within the context of an unprivileged process. This issue is rated as High due to the possibility of remote code execution in an application that uses this library.

CVE-2017-0663 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.13 IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE CWE-611

A flaw in libxml2 allows remote XML entity inclusion with default parser flags (i.e., when the caller did not request entity substitution, DTD validation, external DTD subset loading, or default DTD attributes). Depending on the context, this may expose a higher-risk attack surface in libxml2 not usually reachable with default parser flags, and expose content from local files, HTTP, or FTP servers (which might be otherwise unreachable).

CVE-2017-7375 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.14 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

Buffer overflow in libxml2 allows remote attackers to execute arbitrary code by leveraging an incorrect limit for port values when handling redirects.

CVE-2017-7376 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.15 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

A buffer overflow vulnerability was discovered in libxml2 20904-GITv2.9.4-16-g0741801. This could allow an attacker to write about "size" many bytes beyond the allocated memory. This vulnerability causes programs that use libxml2, such as PHP, to crash.

CVE-2017-9047 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.16 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

libxml2 20904-GITv2.9.4-16-g0741801 is vulnerable to a stack-based buffer overflow. This vulnerability causes programs that use libxml2, such as PHP, to crash.

CVE-2017-9048 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.17 OUT-OF-BOUNDS READ CWE-125

libxml2 20904-GITv2.9.4-16-g0741801 is vulnerable to a heap-based buffer over-read in the xmlDictComputeFastKey function in dict.c. This vulnerability causes programs that use libxml2, such as PHP, to crash. This vulnerability exists because of an incomplete fix for libxml2 Bug 759398.

CVE-2017-9049 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.18 OUT-OF-BOUNDS READ CWE-125

libxml2 20904-GITv2.9.4-16-g0741801 is vulnerable to a heap-based buffer over-read in the xmlDictAddString function in dict.c. This vulnerability causes programs that use libxml2, such as PHP, to crash. This vulnerability exists because of an incomplete fix for CVE-2016-1839.

CVE-2017-9050 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.19 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

parser.c in libxml2 before 2.9.5 mishandles parameter-entity references because the NEXTL macro calls the xmlParserHandlePEReference function in the case of a '%' character in a DTD name.

CVE-2017-16931 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.20 LOOP WITH UNREACHABLE EXIT CONDITION ('INFINITE LOOP') CWE-835

parser.c in libxml2 before 2.9.5 does not prevent infinite recursion in parameter entities.

CVE-2017-16932 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.21 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS IN OUTPUT USED BY A DOWNSTREAM COMPONENT ('INJECTION') CWE-74

sensible-browser in sensible-utils before 0.0.11 does not validate strings before launching the program specified by the BROWSER environment variable, which allows remote attackers to conduct argument-injection attacks via a crafted URL, as demonstrated by a --proxy-pac-file argument.

CVE-2017-17512 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.22 ALLOCATION OF RESOURCES WITHOUT LIMITS OR THROTTLING CWE-770

The xz_head function in xzlib.c in libxml2 before 2.9.6 allows remote attackers to cause a denial of service (memory consumption) via a crafted LZMA file, because the decoder functionality does not restrict memory usage to what is required for a legitimate file.

CVE-2017-18258 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.23 OBSERVABLE DISCREPANCY CWE-203

Libgcrypt before 1.7.10 and 1.8.x before 1.8.3 allows a memory-cache side-channel attack on ECDSA signatures that can be mitigated through the use of blinding during the signing process in the _gcry_ecc_ecdsa_sign function in cipher/ecc-ecdsa.c, aka the Return Of the Hidden Number Problem or ROHNP.

CVE-2018-0495 has been assigned to this vulnerability. A CVSS v3 base score of 4.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:N/A:N).

3.2.24 GENERATION OF ERROR MESSAGE CONTAINING SENSITIVE INFORMATION CWE-209

stack_protect_prologue in cfgexpand.c and stack_protect_epilogue in function.c in GNU Compiler Collection (GCC) 4.1 through 8 (under certain circumstances) generate instruction sequences when targeting ARM targets that spill the address of the stack protector guard, which allows an attacker to bypass the protection of -fstack-protector, -fstack-protector-all, -fstack-protector-strong, and -fstack-protector-explicit against stack overflow by controlling what the stack canary is compared against.

CVE-2018-12886 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.25 NULL POINTER DEREFERENCE CWE-476

A NULL pointer dereference vulnerability exists in the xpath.c:xmlXPathCompOpEval() function of libxml2 through 2.9.8 when parsing an invalid XPath expression in the XPATH_OP_AND or XPATH_OP_OR case. Applications processing untrusted XSL format inputs with the use of the libxml2 library may be vulnerable to a denial of service attack due to a crash of the application.

CVE-2018-14404 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.26 LOOP WITH UNREACHABLE EXIT CONDITION ('INFINITE LOOP') CWE-835

libxml2 2.9.8, if --with-lzma allows remote attackers to cause a denial-of-service (infinite loop) via a crafted XML file that triggers LZMA_MEMLIMIT_ERROR, as demonstrated by xmllint, a different vulnerability than CVE-2015-8035 and CVE-2018-9251.

CVE-2018-14567 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.27 INTEGER OVERFLOW OR WRAPAROUND CWE-190

International Components for Unicode (ICU) for C/C++ 63.1 has an integer overflow in number::impl::DecimalQuantity::toScientificString() in i18n/number_decimalquantity.cpp.

CVE-2018-18928 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.28 IMPROPER INPUT VALIDATION CWE-20

In the GNU C Library (aka glibc or libc6) through 2.28, attempting to resolve a crafted hostname via getaddrinfo() leads to the allocation of a socket descriptor that is not closed. This is related to the if_nametoindex() function.

CVE-2018-19591 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.29 LOOP WITH UNREACHABLE EXIT CONDITION ('INFINITE LOOP') CWE-835

GNU Tar through 1.30, when --sparse is used, mishandles file shrinkage during read access, which allows local users to cause a denial of service (infinite read loop in sparse_dump_region in sparse.c) by modifying a file that is supposed to be archived by a different user's process (e.g., a system backup running as root).

CVE-2018-20482 has been assigned to this vulnerability. A CVSS v3 base score of 4.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.30 IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE CWE-611

In libexpat in Expat before 2.2.7, XML input including XML names that contain a large number of colons could make the XML parser consume a high amount of RAM and CPU resources while processing (enough to be usable for denial-of-service attacks).

CVE-2018-20843 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.31 OUT-OF-BOUNDS WRITE CWE-787

zlib before 1.2.12 allows memory corruption when deflating (i.e., when compressing) if the input has many distant matches.

CVE-2018-25032 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.32 OUT-OF-BOUNDS WRITE CWE-787

An integer overflow flaw which could lead to an out of bounds write was discovered in libssh2 before 1.8.1 in the way packets are read from the server. A remote attacker who compromises a SSH server may be able to execute code on the client system when a user connects to the server.

CVE-2019-3855 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.33 OUT-OF-BOUNDS WRITE CWE-787

An integer overflow flaw, which could lead to an out of bounds write, was discovered in libssh2 before 1.8.1 in the way keyboard prompt requests are parsed. A remote attacker who compromises a SSH server may be able to execute code on the client system when a user connects to the server.

CVE-2019-3856 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.34 OUT-OF-BOUNDS WRITE CWE-787

An integer overflow flaw which could lead to an out of bounds write was discovered in libssh2 before 1.8.1 in the way SSH_MSG_CHANNEL_REQUEST packets with an exit signal are parsed. A remote attacker who compromises a SSH server may be able to execute code on the client system when a user connects to the server.

CVE-2019-3857 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.35 OUT-OF-BOUNDS READ CWE-125

An out of bounds read flaw was discovered in libssh2 before 1.8.1 when a specially crafted SFTP packet is received from the server. A remote attacker who compromises a SSH server may be able to cause a denial-of-service or read data in the client memory.

CVE-2019-3858 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.2.36 OUT-OF-BOUNDS READ CWE-125

An out of bounds read flaw was discovered in libssh2 before 1.8.1 in the _libssh2_packet_require and _libssh2_packet_requirev functions. A remote attacker who compromises a SSH server may be able to cause a denial-of-service or read data in the client memory.

CVE-2019-3859 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.2.37 OUT-OF-BOUNDS READ CWE-125

An out of bounds read flaw was discovered in libssh2 before 1.8.1 in the way SFTP packets with empty payloads are parsed. A remote attacker who compromises a SSH server may be able to cause a denial-of-service or read data in the client memory.

CVE-2019-3860 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.2.38 OUT-OF-BOUNDS READ CWE-125

An out of bounds read flaw was discovered in libssh2 before 1.8.1 in the way SSH packets with a padding length value greater than the packet length are parsed. A remote attacker who compromises a SSH server may be able to cause a denial-of-service or read data in the client memory.

CVE-2019-3861 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.2.39 OUT-OF-BOUNDS READ CWE-125

An out of bounds read flaw was discovered in libssh2 before 1.8.1 in the way SSH_MSG_CHANNEL_REQUEST packets with an exit status message and no payload are parsed. A remote attacker who compromises a SSH server may be able to cause a denial-of-service or read data in the client memory.

CVE-2019-3862 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.2.40 OUT-OF-BOUNDS WRITE CWE-787

A flaw was found in libssh2 before 1.8.1. A server could send a multiple keyboard interactive response messages whose total length are greater than unsigned char max characters. This value is used as an index to copy memory causing in an out of bounds memory write error.

CVE-2019-3863 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.41 USE AFTER FREE CWE-416

An exploitable use after free vulnerability exists in the window function functionality of Sqlite3 3.26.0. A specially crafted SQL command can cause a use after free vulnerability, potentially resulting in remote code execution. An attacker can send a malicious SQL command to trigger this vulnerability.

CVE-2019-5018 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.42 OUT-OF-BOUNDS WRITE CWE-787

An exploitable code execution vulnerability exists in the quota file functionality of E2fsprogs 1.45.3. A specially crafted ext4 partition can cause an out-of-bounds write on the heap, resulting in code execution. An attacker can corrupt a partition to trigger this vulnerability.

CVE-2019-5094 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:H/UI:N/S:C/C:H/I:H/A:H).

3.2.43 OUT-OF-BOUNDS WRITE CWE-787

A code execution vulnerability exists in the directory rehashing functionality of E2fsprogs e2fsck 1.45.4. A specially crafted ext4 directory can cause an out-of-bounds write on the stack, resulting in code execution. An attacker can corrupt a partition to trigger this vulnerability.

CVE-2019-5188 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:H/UI:N/S:C/C:H/I:H/A:H).

3.2.44 INTEGER OVERFLOW OR WRAPAROUND CWE-190

An integer overflow in curl's URL API results in a buffer overflow in libcurl 7.62.0 to and including 7.64.1.

CVE-2019-5435 has been assigned to this vulnerability. A CVSS v3 base score of 3.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:L).

3.2.45 OUT-OF-BOUNDS WRITE CWE-787

A heap buffer overflow in the TFTP receiving code allows for DoS or arbitrary code execution in libcurl versions 7.19.4 through 7.64.1.

CVE-2019-5436 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.46 UNCONTROLLED SEARCH PATH ELEMENT CWE-427

A non-privileged user or program can put code and a config file in a known non-privileged path (under C:/usr/local/) that will make curl <= 7.65.1 automatically run the code (as an openssl "engine") on invocation. If that curl is invoked by a privileged user it can do anything it wants.

CVE-2019-5443 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.47 DOUBLE FREE CWE-415

Double-free vulnerability in the FTP-kerberos code in cURL 7.52.0 to 7.65.3.

CVE-2019-5481 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.48 OUT-OF-BOUNDS WRITE CWE-787

Heap buffer overflow in the TFTP protocol handler in cURL 7.19.4 to 7.65.3.

CVE-2019-5482 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.49 IMPROPER ENCODING OR ESCAPING OF OUTPUT CWE-116

An issue was discovered in OpenSSH 7.9. Due to missing character encoding in the progress display, a malicious server (or Man-in-The-Middle attacker) can employ crafted object names to manipulate the client output, e.g., by using ANSI control codes to hide additional files being transferred. This affects refresh_progress_meter() in progressmeter.c.

CVE-2019-6109 has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:N).

3.2.50 INAPPROPRIATE ENCODING FOR OUTPUT CONTEXT CWE-838

In OpenSSH 7.9, due to accepting and displaying arbitrary stderr output from the server, a malicious server (or Man-in-The-Middle attacker) can manipulate the client output, for example to use ANSI control codes to hide additional files being transferred.

CVE-2019-6110 has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:N).

3.2.51 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY ('PATH TRAVERSAL') CWE-22

An issue was discovered in OpenSSH 7.9. Due to the scp implementation being derived from 1983 rcp, the server chooses which files/directories are sent to the client. However, the scp client only performs cursory validation of the object name returned (only directory traversal attacks are prevented). A malicious scp server (or Man-in-The-Middle attacker) can overwrite arbitrary files in the scp client target directory. If recursive operation (-r) is performed, the server can manipulate subdirectories as well (for example, to overwrite the .ssh/authorized_keys file).

CVE-2019-6111 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.52 IMPROPER RESOURCE SHUTDOWN OR RELEASE CWE-404

The string component in the GNU C Library (aka glibc or libc6) through 2.28, when running on the x32 architecture, incorrectly attempts to use a 64-bit register for size_t in assembly codes, which can lead to a segmentation fault or possibly unspecified other impact, as demonstrated by a crash in __memmove_avx_unaligned_erms in sysdeps/x86_64/multiarch/memmove-vec-unaligned-erms.S during a memcpy.

CVE-2019-6488 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.53 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

In the GNU C Library (aka glibc or libc6) through 2.29, the memcmp function for the x32 architecture can incorrectly return zero (indicating that the inputs are equal) because the RDX most significant bit is mishandled.

CVE-2019-7309 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.54 OUT-OF-BOUNDS READ CWE-125

SQLite3 from 3.6.0 to and including 3.27.2 is vulnerable to heap out-of-bound read in the rtreenode() function when handling invalid rtree tables.

CVE-2019-8457 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.55 OUT-OF-BOUNDS READ CWE-125

In the GNU C Library (aka glibc or libc6) through 2.29, proceed_next_node in posix/regexec.c has a heap-based buffer over-read via an attempted case-insensitive regular-expression match.

CVE-2019-9169 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.56 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Python 2.7.x through 2.7.16 and 3.x through 3.7.2 is affected by improper handling of unicode encoding (with an incorrect netloc) during NFKC normalization. A specially crafted URL could be incorrectly parsed to locate cookies or authentication data and send that information to a different host than when parsed correctly.

CVE-2019-9636 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.57 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

Lib/zipfile.py in Python through 3.7.2 allows remote attackers to cause a denial-of-service (resource consumption) via a ZIP bomb.

CVE-2019-9674 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.58 IMPROPER NEUTRALIZATION OF CRLF SEQUENCES ('CRLF INJECTION') CWE-93

An issue was discovered in urllib2 in Python 2.x through 2.7.16 and urllib in Python 3.x through 3.7.3. CRLF injection is possible if the attacker controls a url parameter, as demonstrated by the first argument to urllib.request.urlopen with \r\n (specifically in the query string after a ? character) followed by an HTTP header or a Redis command.

CVE-2019-9740 has been assigned to this vulnerability. A CVSS v3 base score of 6.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N).

3.2.59 NULL POINTER DEREFERENCE CWE-476

pax_decode_header in sparse.c in GNU Tar before 1.32 had a NULL pointer dereference when parsing certain archives that have malformed extended headers.

CVE-2019-9923 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.60 OUT-OF-BOUNDS READ CWE-125

In SQLite 3.27.2, running fts5 prefix queries inside a transaction could trigger a heap-based buffer over-read in fts5HashEntrySort in sqlite3.c, which may lead to an information leak. This is related to ext/fts5/fts5_hash.c.

CVE-2019-9936 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.61 NULL POINTER DEREFERENCE CWE-476

In SQLite 3.27.2, interleaving reads and writes in a single transaction with an fts5 virtual table will lead to a NULL Pointer Dereference in fts5ChunkIterate in sqlite3.c. This is related to ext/fts5/fts5_hash.c and ext/fts5/fts5_index.c.

CVE-2019-9937 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.62 IMPROPER NEUTRALIZATION OF CRLF SEQUENCES ('CRLF INJECTION') CWE-93

An issue was discovered in urllib2 in Python 2.x through 2.7.16 and urllib in Python 3.x through 3.7.3. CRLF injection is possible if the attacker controls a url parameter, as demonstrated by the first argument to urllib.request.urlopen with \r\n (specifically in the path component of a URL that lacks a ? character) followed by an HTTP header or a Redis command. This is similar to the CVE-2019-9740 query string issue.

CVE-2019-9947 has been assigned to this vulnerability. A CVSS v3 base score of 6.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N).

3.2.63 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY ('PATH TRAVERSAL') CWE-22

urllib in Python 2.x through 2.7.16 supports the local_file: scheme, which makes it easier for remote attackers to bypass protection mechanisms that blacklist file: URIs, as demonstrated by triggering a urllib.urlopen('local_file:///etc/passwd') call.

CVE-2019-9948 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).

3.2.64 ENCODING ERROR CWE-172

A security regression of CVE-2019-9636 was discovered in python affecting versions 2.7, 3.5, 3.6, 3.7 and from v3.8.0a4 through v3.8.0b1, which still allows an attacker to exploit CVE-2019-9636 by abusing the user and password parts of a URL. When an application parses user-supplied URLs to store cookies, authentication credentials, or other kind of information, it is possible for an attacker to provide specially crafted URLs to make the application locate host-related information (e.g. cookies, authentication data) and send them to a different host than where it should, unlike if the URLs had been correctly parsed. The result of an attack may vary based on the application.

CVE-2019-10160 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.65 OUT-OF-BOUNDS WRITE CWE-787

A buffer overflow in iptables-restore in netfilter iptables 1.8.2 allows an attacker to (at least) crash the program or potentially gain code execution via a specially crafted iptables-save file. This is related to add_param_to_argv in xshared.c.

CVE-2019-11360 has been assigned to this vulnerability. A CVSS v3 base score of 4.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:H/UI:R/S:U/C:N/I:N/A:H).

3.2.66 IMPROPER INPUT VALIDATION CWE-20

GNU libidn2 before 2.2.0 fails to perform the roundtrip checks specified in RFC3490 Section 4.2 when converting A-labels to U-labels. This makes it possible in some circumstances for one domain to impersonate another. By creating a malicious domain that matches a target domain except for the inclusion of certain punycoded Unicode characters (that would be discarded when converted first to a Unicode label and then back to an ASCII label), arbitrary domains can be impersonated.

CVE-2019-12290 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.67 OUT-OF-BOUNDS WRITE CWE-787

BZ2_decompress in decompress.c in bzip2 through 1.0.6 has an out-of-bounds write when there are many selectors.

CVE-2019-12900 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.68 EXPOSURE OF RESOURCE TO WRONG SPHERE CWE-668

In Libgcrypt 1.8.4, the C implementation of AES is vulnerable to a flush-and-reload side-channel attack because physical addresses are available to other processes. (The C implementation is used on platforms where an assembly-language implementation is unavailable.) NOTE: the vendor's position is that the issue report cannot be validated because there is no description of an attack

CVE-2019-12904 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.69 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

An issue was discovered in the server in OpenLDAP before 2.4.48. When the server administrator delegates rootDN (database admin) privileges for certain databases but wants to maintain isolation (e.g., for multi-tenant deployments), slapd does not properly stop a rootDN from requesting authorization as an identity from another database during a SASL bind or with a proxyAuthz (RFC 4370) control. (It is not a common configuration to deploy a system where the server administrator and a DB administrator enjoy different levels of trust.)

CVE-2019-13057 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N).

3.2.70 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

An issue was discovered in OpenLDAP 2.x before 2.4.48. When using SASL authentication and session encryption, and relying on the SASL security layers in slapd access controls, it is possible to obtain access that would otherwise be denied via a simple bind for any identity covered in those ACLs. After the first SASL bind is completed, the sasl_ssf value is retained for all new non-SASL connections. Depending on the ACL configuration, this can affect different types of operations (searches, modifications, etc.). In other words, a successful authorization step completed by one user affects the authorization requirement for a different user.

CVE-2019-13565 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.71 OBSERVABLE DISCREPANCY CWE-203

It was discovered that there was a ECDSA timing attack in the libgcrypt20 cryptographic library. Version affected: 1.8.4-5, 1.7.6-2+deb9u3, and 1.6.3-2+deb8u4. Versions fixed: 1.8.5-2 and 1.6.3-2+deb8u7.

CVE-2019-13627 has been assigned to this vulnerability. A CVSS v3 base score of 6.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:N).

3.2.72 INSUFFICIENT ENTROPY CWE-331

The POWER9 backend in GNU Compiler Collection (GCC) before version 10 could optimize multiple calls of the __builtin_darn intrinsic into a single call, thus reducing the entropy of the random number generator. This occurred because a volatile operation was not specified. For example, within a single execution of a program, the output of every __builtin_darn() call may be the same.

CVE-2019-15847 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.73 OUT-OF-BOUNDS READ CWE-125

In libexpat before 2.2.8, crafted XML input could fool the parser into changing from DTD parsing to document parsing too early; a consecutive call to XML_GetCurrentLineNumber (or XML_GetCurrentColumnNumber) then resulted in a heap-based buffer over-read.

CVE-2019-15903 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.74 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

An issue was discovered in Python through 2.7.16, 3.x through 3.5.7, 3.6.x through 3.6.9, and 3.7.x through 3.7.4. The email module wrongly parses email addresses that contain multiple @ characters. An application that uses the email module and implements some kind of checks on the From/To headers of a message could be tricked into accepting an email address that should be denied. An attack may be the same as in CVE-2019-11340; however, this CVE applies to Python more generally.

CVE-2019-16056 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.75 DIVIDE BY ZERO CWE-369

In SQLite through 3.29.0, whereLoopAddBtreeIndex in sqlite3.c can crash a browser or other application because of missing validation of a sqlite_stat1 sz field, aka a "severe division by zero in the query planner."

CVE-2019-16168 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.76 INTEGER OVERFLOW OR WRAPAROUND CWE-190

OpenSSH 7.7 through 7.9 and 8.x before 8.1, when compiled with an experimental key type, has a pre-authentication integer overflow if a client or server is configured to use a crafted XMSS key. This leads to memory corruption and local code execution because of an error in the XMSS key parsing algorithm. NOTE: the XMSS implementation is considered experimental in all released OpenSSH versions, and there is no supported way to enable it when building portable OpenSSH.

CVE-2019-16905 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.77 INTEGER OVERFLOW OR WRAPAROUND CWE-190

In libssh2 v1.9.0 and earlier versions, the SSH_MSG_DISCONNECT logic in packet.c has an integer overflow in a bounds check, enabling an attacker to specify an arbitrary (out-of-bounds) offset for a subsequent memory read. A crafted SSH server may be able to disclose sensitive information or cause a denial of service condition on the client system when a user connects to the server.

CVE-2019-17498 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:H).

3.2.78 OUT-OF-BOUNDS WRITE CWE-787

LZ4 before 1.9.2 has a heap-based buffer overflow in LZ4_write32 (related to LZ4_compress_destSize), affecting applications that call LZ4_compress_fast with a large input. (This issue can also lead to data corruption.) NOTE: the vendor states "only a few specific / uncommon usages of the API are at risk."

CVE-2019-17543 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.79 OUT-OF-BOUNDS READ CWE-125

There is a heap-based buffer over-read in the _nc_find_entry function in tinfo/comp_hash.c in the terminfo library in ncurses before 6.1-20191012.

CVE-2019-17594 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L).

3.2.80 OUT-OF-BOUNDS READ CWE-125

There is a heap-based buffer over-read in the fmt_entry function in tinfo/comp_hash.c in the terminfo library in ncurses before 6.1-20191012.

CVE-2019-17595 has been assigned to this vulnerability. A CVSS v3 base score of 5.4 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:L).

3.2.81 OUT-OF-BOUNDS WRITE CWE-787

idn2_to_ascii_4i in lib/lookup.c in GNU libidn2 before 2.1.1 has a heap-based buffer overflow via a long domain string.

CVE-2019-18224 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.82 IMPROPER CHECK FOR DROPPED PRIVILEGES CWE-273

An issue was discovered in disable_priv_mode in shell.c in GNU Bash through 5.0 patch 11. By default, if Bash is run with its effective UID not equal to its real UID, it will drop privileges by setting its effective UID to its real UID. However, it does so incorrectly. On Linux and other systems that support "saved UID" functionality, the saved UID is not dropped. An attacker with command execution in the shell can use "enable -f" for runtime loading of a new builtin, which can be a shared object that calls setuid() and therefore regains privileges. However, binaries running with an effective UID of 0 are unaffected.

CVE-2019-18276 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.83 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS IN OUTPUT USED BY A DOWNSTREAM COMPONENT ('INJECTION') CWE-74

An issue was discovered in urllib2 in Python 2.x through 2.7.17 and urllib in Python 3.x through 3.8.0. CRLF injection is possible if the attacker controls a url parameter, as demonstrated by the first argument to urllib.request.urlopen with \r\n (specifically in the host component of a URL) followed by an HTTP header. This is similar to the CVE-2019-9740 query string issue and the CVE-2019-9947 path string issue. (This is not exploitable when glibc has CVE-2016-10739 fixed.).

CVE-2019-18348 has been assigned to this vulnerability. A CVSS v3 base score of 6.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N).

3.2.84 IMPROPER INITIALIZATION CWE-665

On the x86-64 architecture, the GNU C Library (aka glibc) before 2.31 fails to ignore the LD_PREFER_MAP_32BIT_EXEC environment variable during program execution after a security transition, allowing local attackers to restrict the possible mapping addresses for loaded libraries and thus bypass ASLR for a setuid program.

CVE-2019-19126 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N).

3.2.85 NULL POINTER DEREFERENCE CWE-476

SQLite 3.30.1 mishandles pExpr->y.pTab, as demonstrated by the TK_COLUMN case in sqlite3ExprCodeTarget in expr.c.

CVE-2019-19242 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.86 IMPROPER INPUT VALIDATION CWE-20

Select in select.c in SQLite 3.30.1 allows a crash if a sub-select uses both DISTINCT and window functions, and also has certain ORDER BY usage.

CVE-2019-19244 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.87 INCORRECT CONVERSION BETWEEN NUMERIC TYPES CWE-681

lookupName in resolve.c in SQLite 3.30.1 omits bits from the colUsed bitmask in the case of a generated column, which allows attackers to cause a denial-of-service or possibly have unspecified other impact.

CVE-2019-19317 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.88 IMPROPER INPUT VALIDATION CWE-20

SQLite 3.30.1 mishandles certain SELECT statements with a nonexistent VIEW, leading to an application crash.

CVE-2019-19603 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.89 UNCONTROLLED RECURSION CWE-674

alter.c in SQLite through 3.30.1 allows attackers to trigger infinite recursion via certain types of self-referential views in conjunction with ALTER TABLE statements.

CVE-2019-19645 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.90 IMPROPER CHECK FOR UNUSUAL OR EXCEPTIONAL CONDITIONS CWE-754

pragma.c in SQLite through 3.30.1 mishandles NOT NULL in an integrity_check PRAGMA command in certain cases of generated columns.

CVE-2019-19646 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.91 NULL POINTER DEREFERENCE CWE-476

exprListAppendList in window.c in SQLite 3.30.1 allows attackers to trigger an invalid pointer dereference because constant integer values in ORDER BY clauses of window definitions are mishandled.

CVE-2019-19880 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.92 OUT-OF-BOUNDS WRITE CWE-787

cyrus-sasl (aka Cyrus SASL) 2.1.27 has an out-of-bounds write leading to unauthenticated remote denial-of-service in OpenLDAP via a malformed LDAP packet. The OpenLDAP crash is ultimately caused by an off-by-one error in _sasl_add_string in common.c in cyrus-sasl.

CVE-2019-19906 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.93 NULL POINTER DEREFERENCE CWE-476

flattenSubquery in select.c in SQLite 3.30.1 mishandles certain uses of SELECT DISTINCT involving a LEFT JOIN in which the right-hand side is a view. This can cause a NULL pointer dereference (or incorrect results).

CVE-2019-19923 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.94 IMPROPER HANDLING OF EXCEPTIONAL CONDITIONS CWE-755

SQLite 3.30.1 mishandles certain parser-tree rewriting, related to expr.c, vdbeaux.c, and window.c. This is caused by incorrect sqlite3WindowRewrite() error handling.

CVE-2019-19924 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).

3.2.95 UNRESTRICTED UPLOAD OF FILE WITH DANGEROUS TYPE CWE-434

zipfileUpdate in ext/misc/zipfile.c in SQLite 3.30.1 mishandles a NULL pathname during an update of a ZIP archive.

CVE-2019-19925 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.96 NULL POINTER DEREFERENCE CWE-476

multiSelect in select.c in SQLite 3.30.1 mishandles certain errors during parsing, as demonstrated by errors from sqlite3WindowRewrite() calls. NOTE: this vulnerability exists because of an incomplete fix for CVE-2019-19880.

CVE-2019-19926 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.97 MISSING RELEASE OF RESOURCE AFTER EFFECTIVE LIFETIME CWE-772

xmlParseBalancedChunkMemoryRecover in parser.c in libxml2 before 2.9.10 has a memory leak related to newDoc->oldNs.

CVE-2019-19956 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.98 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

ext/misc/zipfile.c in SQLite 3.30.1 mishandles certain uses of INSERT INTO in situations involving embedded '\0' characters in filenames, leading to a memory-management error that can be detected by (for example) valgrind.

CVE-2019-19959 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.99 IMPROPER HANDLING OF EXCEPTIONAL CONDITIONS CWE-755

selectExpander in select.c in SQLite 3.30.1 proceeds with WITH stack unwinding even after a parsing error.

CVE-2019-20218 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.100 OUT-OF-BOUNDS READ CWE-125

nlist.c in libbsd before 0.10.0 has an out-of-bounds read during a comparison for a symbol name from the string table (strtab).

CVE-2019-20367 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.2.101 MISSING RELEASE OF MEMORY AFTER EFFECTIVE LIFETIME CWE-401

xmlSchemaPreRun in xmlschemas.c in libxml2 2.9.10 allows an xmlSchemaValidateStream memory leak.

CVE-2019-20388 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.102 USE AFTER FREE CWE-416

iproute2 before 5.1.0 has a use-after-free in get_netnsid_from_name in ip/ipnetns.c. NOTE: security relevance may be limited to certain uses of setuid that, although not a default, are sometimes a configuration option offered to end users. Even when setuid is used, other factors (such as C library configuration) may block exploitability.

CVE-2019-20795 has been assigned to this vulnerability. A CVSS v3 base score of 4.4 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H).

3.2.103 LOOP WITH UNREACHABLE EXIT CONDITION ('INFINITE LOOP') CWE-835

In Lib/tarfile.py in Python through 3.8.3, an attacker is able to craft a TAR archive leading to an infinite loop when opened by tarfile.open, because _proc_pax lacks header validation.

CVE-2019-20907 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.104 OUT-OF-BOUNDS READ CWE-125

The iconv feature in the GNU C Library (aka glibc or libc6) through 2.32, when processing invalid multi-byte input sequences in the EUC-KR encoding, may have a buffer over-read.

CVE-2019-25013 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.105 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

GNU Libc current is affected by: Mitigation bypass. The impact is: Attacker may bypass stack guard protection. The component is: nptl. The attack vector is: Exploit stack buffer overflow vulnerability and use this bypass vulnerability to bypass stack guard. NOTE: Upstream comments indicate "this is being treated as a non-security bug and no real threat.

CVE-2019-1010022 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.106 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

GNU Libc current is affected by: Re-mapping current loaded library with malicious ELF file. The impact is: In worst case attacker may evaluate privileges. The component is: libld. The attack vector is: Attacker sends 2 ELF files to victim and asks to run ldd on it. ldd execute code. NOTE: Upstream comments indicate "this is being treated as a non-security bug and no real threat."

CVE-2019-1010023 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.107 EXPOSURE OF SENSITIVE INFORMATION TO AN UNAUTHORIZED ACTOR CWE-200

GNU Libc current is affected by: Mitigation bypass. The impact is: Attacker may bypass ASLR using cache of thread stack and heap. The component is: glibc. NOTE: Upstream comments indicate "this is being treated as a non-security bug and no real threat."

CVE-2019-1010024 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.108 USE OF INSUFFICIENTLY RANDOM VALUES CWE-330

GNU Libc current is affected by: Mitigation bypass. The impact is: Attacker may guess the heap addresses of pthread_created thread. The component is: glibc. NOTE: the vendor's position is "ASLR bypass itself is not a vulnerability."

CVE-2019-1010025 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.109 OUT-OF-BOUNDS READ CWE-125

GNU gdb All versions is affected by: Buffer Overflow - Out of bound memory access. The impact is: Deny of Service, Memory Disclosure, and Possible Code Execution. The component is: The main gdb module. The attack vector is: Open an ELF for debugging. The fixed version is: Not fixed yet.

CVE-2019-1010180 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.110 USE AFTER FREE CWE-416

A heap use-after-free vulnerability was found in systemd before version v245-rc1, where asynchronous Polkit queries are performed while handling dbus messages. A local unprivileged attacker can abuse this flaw to crash systemd services or potentially execute code and elevate their privileges, by sending specially crafted dbus messages.

CVE-2020-1712 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.111 OUT-OF-BOUNDS WRITE CWE-787

An out-of-bounds write vulnerability was found in glibc before 2.31 when handling signal trampolines on PowerPC. Specifically, the backtrace function did not properly check the array bounds when storing the frame address, resulting in a denial of service or potential code execution. The highest threat from this vulnerability is to system availability.

CVE-2020-1751 has been assigned to this vulnerability. A CVSS v3 base score of 5.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.112 USE AFTER FREE CWE-416

A use-after-free vulnerability introduced in glibc upstream version 2.14 was found in the way the tilde expansion was carried out. Directory paths containing an initial tilde followed by a valid username were affected by this issue. A local attacker could exploit this flaw by creating a specially crafted path that, when processed by the glob function, would potentially lead to arbitrary code execution. This was fixed in version 2.32.

CVE-2020-1752 has been assigned to this vulnerability. A CVSS v3 base score of 7.0 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.113 SIGNED TO UNSIGNED CONVERSION ERROR CWE-195

An exploitable signed comparison vulnerability exists in the ARMv7 memcpy() implementation of GNU glibc 2.30.9000. Calling memcpy() (on ARMv7 targets that utilize the GNU glibc implementation) with a negative value for the 'num' parameter results in a signed comparison vulnerability. If an attacker underflows the 'num' parameter to memcpy(), this vulnerability could lead to undefined behavior such as writing to out-of-bounds memory and potentially remote code execution. Furthermore, this memcpy() implementation allows for program execution to continue in scenarios where a segmentation fault or crash should have occurred. The dangers occur in that subsequent execution and iterations of this code will be executed with this corrupted data.

CVE-2020-6096 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.114 LOOP WITH UNREACHABLE EXIT CONDITION ('INFINITE LOOP') CWE-835

xmlStringLenDecodeEntities in parser.c in libxml2 2.9.10 has an infinite loop in a certain end-of-file situation.

CVE-2020-7595 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.115 EXPOSURE OF SENSITIVE INFORMATION TO AN UNAUTHORIZED ACTOR CWE-200

The libcurl library versions 7.62.0 to and including 7.70.0 are vulnerable to an information disclosure vulnerability that can lead to a partial password being leaked over the network and to the DNS server(s).

CVE-2020-8169 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.116 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS IN OUTPUT USED BY A DOWNSTREAM COMPONENT ('INJECTION') CWE-74

curl 7.20.0 through 7.70.0 is vulnerable to improper restriction of names for files and other resources that can lead too overwriting a local file when the -J flag is used.

CVE-2020-8177 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H).

3.2.117 USE AFTER FREE CWE-416

Due to use of a dangling pointer, libcurl 7.29.0 through 7.71.1 can use the wrong connection when sending data.

CVE-2020-8231 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.118 EXPOSURE OF SENSITIVE INFORMATION TO AN UNAUTHORIZED ACTOR CWE-200

A malicious server can use the FTP PASV response to trick curl 7.73.0 and earlier into connecting back to a given IP address and port, and this way potentially make curl extract information about services that are otherwise private and not disclosed, for example doing port scanning and service banner extractions.

CVE-2020-8284 has been assigned to this vulnerability. A CVSS v3 base score of 3.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.119 UNCONTROLLED RECURSION CWE-674

curl 7.21.0 to and including 7.73.0 is vulnerable to uncontrolled recursion due to a stack overflow issue in FTP wildcard match parsing.

CVE-2020-8285 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.120 IMPROPER CERTIFICATE VALIDATION CWE-295

The libcurl library versions 7.41.0 to and including 7.73.0 are vulnerable to an improper check for certificate revocation due to insufficient verification of the OCSP response. This vulnerability could allow an attacker to pass a revoked certificate as valid.

CVE-2020-8286 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.121 UNCONTROLLED SEARCH PATH ELEMENT CWE-427

In Python (CPython) 3.6 through 3.6.10, 3.7 through 3.7.6, and 3.8 through 3.8.1, an insecure dependency load upon launch on Windows 7 may result in an attacker's copy of api-ms-win-core-path-l1-1-0.dll being loaded and used instead of the system's copy. Windows 8 and later are unaffected.

CVE-2020-8315 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:H/A:N).

3.2.122 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

Python 2.7 through 2.7.17, 3.5 through 3.5.9, 3.6 through 3.6.10, 3.7 through 3.7.6, and 3.8 through 3.8.1 allows an HTTP server to conduct regular expression denial-of-service (ReDoS) attacks against a client because of urllib.request.AbstractBasicAuthHandler catastrophic backtracking.

CVE-2020-8492 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.123 NULL POINTER DEREFERENCE CWE-476

In SQLite 3.31.1, isAuxiliaryVtabOperator allows attackers to trigger a NULL pointer dereference and segmentation fault because of generated column optimizations.

CVE-2020-9327 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.124 OUT-OF-BOUNDS WRITE CWE-787

The GNU C Library (aka glibc or libc6) before 2.32 could overflow an on-stack buffer during range reduction if an input to an 80-bit long double function contains a non-canonical bit pattern, a seen when passing a 0x5d414141414141410000 value to sinl on x86 targets. This is related to sysdeps/ieee754/ldbl-96/e_rem_pio2l.c.

CVE-2020-10029 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.125 OUT-OF-BOUNDS WRITE CWE-787

An issue was discovered in International Components for Unicode (ICU) for C/C++ through 66.1. An integer overflow, leading to a heap-based buffer overflow, exists in the UnicodeString::doAppend() function in common/unistr.cpp.

CVE-2020-10531 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.126 OUT-OF-BOUNDS WRITE CWE-787

Perl before 5.30.3 on 32-bit platforms allows a heap-based buffer overflow because nested regular expression quantifiers have an integer overflow.

CVE-2020-10543 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H).

3.2.127 INCORRECT TYPE CONVERSION OR CAST CWE-704

A flaw was found in python. In algorithms with quadratic time complexity using non-binary bases, when using int("text"), a system could take 50ms to parse an int string with 100,000 digits and 5s for 1,000,000 digits (float, decimal, int.from_bytes(), and int() for binary bases 2, 4, 8, 16, and 32 are not affected). The highest threat from this vulnerability is to system availability.

CVE-2020-10735 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.128 INTEGER OVERFLOW OR WRAPAROUND CWE-190

Perl before 5.30.3 has an integer overflow related to mishandling of a "PL_regkind[OP(n)] == NOTHING" situation. A crafted regular expression could lead to malformed bytecode with a possibility of instruction injection.

CVE-2020-10878 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H).

3.2.129 USE OF INSUFFICIENTLY RANDOM VALUES CWE-330

GnuTLS 3.6.x before 3.6.13 uses incorrect cryptography for DTLS. The earliest affected version is 3.6.3 (2018-07-16) because of an error in a 2017-10-06 commit. The DTLS client always uses 32 '\0' bytes instead of a random value, and thus contributes no randomness to a DTLS negotiation. This breaks the security guarantees of the DTLS protocol.

CVE-2020-11501 has been assigned to this vulnerability. A CVSS v3 base score of 7.4 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:N).

3.2.130 IMPROPER INITIALIZATION CWE-665

SQLite through 3.31.1 allows attackers to cause a denial-of-service (segmentation fault) via a malformed window-function query because the AggInfo object's initialization is mishandled.

CVE-2020-11655 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.131 USE AFTER FREE CWE-416

In SQLite through 3.31.1, the ALTER TABLE implementation has a use-after-free, as demonstrated by an ORDER BY clause that belongs to a compound SELECT statement.

CVE-2020-11656 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.132 IMPROPER INPUT VALIDATION CWE-20

The scp client in OpenSSH 8.2 incorrectly sends duplicate responses to the server upon a utimes system call failure, which allows a malicious unprivileged user on the remote server to overwrite arbitrary files in the client's download directory by creating a crafted subdirectory anywhere on the remote server. The victim must use the command scp -rp to download a file hierarchy containing, anywhere inside, this crafted subdirectory. NOTE: the vendor points out that "this attack can achieve no more than a hostile peer is already able to achieve within the scp protocol" and "utimes does not fail under normal circumstances.

CVE-2020-12062 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.133 UNCONTROLLED RECURSION CWE-674

In filter.c in slapd in OpenLDAP before 2.4.50, LDAP search filters with nested boolean expressions can result in denial of service (daemon crash).

CVE-2020-12243 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.134 BUFFER COPY WITHOUT CHECKING SIZE OF INPUT ('CLASSIC BUFFER OVERFLOW') CWE-120

regcomp.c in Perl before 5.30.3 allows a buffer overflow via a crafted regular expression because of recursive S_study_chunk calls.

CVE-2020-12723 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.135 INTEGER OVERFLOW OR WRAPAROUND CWE-190

json-c through 0.14 has an integer overflow and out-of-bounds write via a large JSON file, as demonstrated by printbuf_memappend.

CVE-2020-12762 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.136 INTEGER OVERFLOW OR WRAPAROUND CWE-190

SQLite through 3.32.0 has an integer overflow in sqlite3_str_vappendf in printf.c.

CVE-2020-13434 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.137 NULL POINTER DEREFERENCE CWE-476

SQLite through 3.32.0 has a segmentation fault in sqlite3ExprCodeTarget in expr.c.

CVE-2020-13435 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.138 AUTHENTICATION BYPASS BY SPOOFING CWE-290

An exploitable denial-of-service vulnerability exists in Systemd 245. A specially crafted DHCP FORCERENEW packet can cause a server running the DHCP client to be vulnerable to a DHCP ACK spoofing attack. An attacker can forge a pair of FORCERENEW and DCHP ACK packets to reconfigure the server.

CVE-2020-13529 has been assigned to this vulnerability. A CVSS v3 base score of 6.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:A/AC:H/PR:N/UI:N/S:C/C:N/I:N/A:H).

3.2.139 USE AFTER FREE CWE-416

ext/fts3/fts3.c in SQLite before 3.32.0 has a use-after-free in fts3EvalNextRow, related to the snippet feature.

CVE-2020-13630 has been assigned to this vulnerability. A CVSS v3 base score of 7.0 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.140 IMPROPER INPUT VALIDATION CWE-20

SQLite before 3.32.0 allows a virtual table to be renamed to the name of one of its shadow tables, related to alter.c and build.c.

CVE-2020-13631 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N).

3.2.141 NULL POINTER DEREFERENCE CWE-476

ext/fts3/fts3_snippet.c in SQLite before 3.32.0 has a NULL pointer dereference via a crafted matchinfo() query.

CVE-2020-13632 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.142 IMPROPER PRIVILEGE MANAGEMENT CWE-269

systemd through v245 mishandles numerical usernames such as ones composed of decimal digits or 0x followed by hex digits, as demonstrated by use of root privileges when privileges of the 0x0 user account were intended. NOTE: this issue exists because of an incomplete fix for CVE-2017-1000082.

CVE-2020-13776 has been assigned to this vulnerability. A CVSS v3 base score of 6.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:H/I:H/A:H).

3.2.143 USE OF A BROKEN OR RISKY CRYPTOGRAPHIC ALGORITHM CWE-327

GnuTLS 3.6.x before 3.6.14 uses incorrect cryptography for encrypting a session ticket (a loss of confidentiality in TLS 1.2, and an authentication bypass in TLS 1.3). The earliest affected version is 3.6.4 (2018-09-24) because of an error in a 2018-09-18 commit. Until the first key rotation, the TLS server always uses wrong data in place of an encryption key derived from an application.

CVE-2020-13777 has been assigned to this vulnerability. A CVSS v3 base score of 7.4 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:N).

3.2.144 USE AFTER FREE CWE-416

SQLite 3.32.2 has a use-after-free in resetAccumulator in select.c because the parse tree rewrite for window functions is too late.

CVE-2020-13871 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.145 OBSERVABLE DISCREPANCY CWE-203

The client side in OpenSSH 5.7 through 8.4 has an Observable Discrepancy leading to an information leak in the algorithm negotiation. This allows man-in-the-middle attackers to target initial connection attempts (where no host key for the server has been cached by the client). NOTE: some reports state that 8.5 and 8.6 are also affected.

CVE-2020-14145 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.146 INCORRECT CALCULATION CWE-682

Lib/ipaddress.py in Python through 3.8.3 improperly computes hash values in the IPv4Interface and IPv6Interface classes, which might allow a remote attacker to cause a denial of service if an application is affected by the performance of a dictionary containing IPv4Interface or IPv6Interface objects, and this attacker can cause many dictionary entries to be created. This is fixed in: v3.5.10, v3.5.10rc1; v3.6.12; v3.7.9; v3.8.4, v3.8.4rc1, v3.8.5, v3.8.6, v3.8.6rc1; v3.9.0, v3.9.0b4, v3.9.0b5, v3.9.0rc1, v3.9.0rc2.

CVE-2020-14422 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.147 OUT-OF-BOUNDS WRITE CWE-787

In SQLite before 3.32.3, select.c mishandles query-flattener optimization, leading to a multiSelectOrderBy heap overflow because of misuse of transitive properties for constant propagation.

CVE-2020-15358 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.148 UNCONTROLLED SEARCH PATH ELEMENT CWE-427

In Python 3.6 through 3.6.10, 3.7 through 3.7.8, 3.8 through 3.8.4rc1, and 3.9 through 3.9.0b4 on Windows, a Trojan horse python3.dll might be used in cases where CPython is embedded in a native application. This occurs because python3X.dll may use an invalid search path for python3.dll loading (after Py_SetPath has been used). NOTE: this issue CANNOT occur when using python.exe from a standard (non-embedded) Python installation on Windows.

CVE-2020-15523 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.149 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND ('OS COMMAND INJECTION') CWE-78

scp in OpenSSH through 8.3p1 allows command injection in the scp.c toremote function, as demonstrated by backtick characters in the destination argument. NOTE: the vendor reportedly has stated that they intentionally omit validation of "anomalous argument transfers" because that could "stand a great chance of breaking existing workflows."

CVE-2020-15778 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.150 UNTRUSTED SEARCH PATH CWE-426

In Python 3.8.4, sys.path restrictions specified in a python38._pth file are ignored, allowing code to be loaded from arbitrary locations. The 'executable-name'._pth file (e.g., the python._pth file) is not affected.

CVE-2020-15801 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.151 OUT-OF-BOUNDS WRITE CWE-787

Buffer Overflow vulnerability in one_one_mapping function in progs/dump_entry.c:1373 in ncurses 6.1 allows remote attackers to cause a denial-of-service via crafted command.

CVE-2020-19185 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.152 OUT-OF-BOUNDS WRITE CWE-787

Buffer Overflow vulnerability in _nc_find_entry function in tinfo/comp_hash.c:66 in ncurses 6.1 allows remote attackers to cause a denial-of-service via crafted command.

CVE-2020-19186 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.153 OUT-OF-BOUNDS WRITE CWE-787

Buffer Overflow vulnerability in fmt_entry function in progs/dump_entry.c:1100 in ncurses 6.1 allows remote attackers to cause a denial-of-service via crafted command.

CVE-2020-19187 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.154 OUT-OF-BOUNDS WRITE CWE-787

Buffer Overflow vulnerability in fmt_entry function in progs/dump_entry.c:1116 in ncurses 6.1 allows remote attackers to cause a denial-of-service via crafted command.

CVE-2020-19188 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.155 OUT-OF-BOUNDS WRITE CWE-787

Buffer Overflow vulnerability in postprocess_terminfo function in tinfo/parse_entry.c:997 in ncurses 6.1 allows remote attackers to cause a denial-of-service via crafted command.

CVE-2020-19189 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.156 OUT-OF-BOUNDS WRITE CWE-787

Buffer Overflow vulnerability in _nc_find_entry in tinfo/comp_hash.c:70 in ncurses 6.1 allows remote attackers to cause a denial-of-service via crafted command.

CVE-2020-19190 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.157 INTEGER OVERFLOW OR WRAPAROUND CWE-190

Integer overflow vulnerability in tool_operate.c in curl 7.65.2 via a large value as the retry delay. NOTE: many parties report that this has no direct security impact on the curl user; however, it may (in theory) cause a denial of service to associated systems or networks if, for example, --retry-delay is misinterpreted as a value much smaller than what was intended. This is not especially plausible because the overflow only happens if the user was trying to specify that curl should wait weeks (or longer) before trying to recover from a transient error.

CVE-2020-19909 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:L).

3.2.158 OUT-OF-BOUNDS WRITE CWE-787

The libcpu component which is used by libasm of elfutils version 0.177 (git 47780c9e), suffers from denial-of-service vulnerability caused by application crashes due to out-of-bounds write (CWE-787), off-by-one error (CWE-193) and reachable assertion (CWE-617); to exploit the vulnerability, the attackers need to craft certain ELF files which bypass the missing bound checks.

CVE-2020-21047 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.159 USE AFTER FREE CWE-416

International Components for Unicode (ICU-20850) v66.1 was discovered to contain a use after free bug in the pkg_createWithAssemblyCode function in the file tools/pkgdata/pkgdata.cpp.

CVE-2020-21913 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.160 OUT-OF-BOUNDS WRITE CWE-787

An issue was discovered in function _libssh2_packet_add in libssh2 1.10.0 allows attackers to access out of bounds memory.

CVE-2020-22218 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.161 OUT-OF-BOUNDS WRITE CWE-787

An issue was discovered in GnuTLS before 3.6.15. A server can trigger a NULL pointer dereference in a TLS 1.3 client if a no_renegotiation alert is sent with unexpected timing, and then an invalid second handshake occurs. The crash happens in the application's error handling path, where the gnutls_deinit function is called after detecting a handshake failure.

CVE-2020-24659 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.162 OUT-OF-BOUNDS READ CWE-125

GNOME project libxml2 v2.9.10 has a global buffer over-read vulnerability in xmlEncodeEntitiesInternal at libxml2/entities.c. The issue has been fixed in commit 50f06b3e.

CVE-2020-24977 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:L).

3.2.163 NULL POINTER DEREFERENCE CWE-476

A NULL pointer dereference was found in OpenLDAP server and was fixed in openldap 2.4.55, during a request for renaming RDNs. An unauthenticated attacker could remotely crash the slapd process by sending a specially crafted request, causing a denial-of-service.

CVE-2020-25692 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.164 REACHABLE ASSERTION CWE-617

A flaw was found in OpenLDAP. This flaw allows an attacker who can send a malicious packet to be processed by OpenLDAP's slapd server, to trigger an assertion failure. The highest threat from this vulnerability is to system availability.

CVE-2020-25709 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.165 REACHABLE ASSERTION CWE-617

A flaw was found in OpenLDAP in versions before 2.4.56. This flaw allows an attacker who sends a malicious packet processed by OpenLDAP to force a failed assertion in csnNormalize23(). The highest threat from this vulnerability is to system availability.

CVE-2020-25710 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.166 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS IN OUTPUT USED BY A DOWNSTREAM COMPONENT ('INJECTION') CWE-74

http.client in Python 3.x before 3.5.10, 3.6.x before 3.6.12, 3.7.x before 3.7.9, and 3.8.x before 3.8.5 allows CRLF injection if the attacker controls the HTTP request method, as demonstrated by inserting CR and LF control characters in the first argument of HTTPConnection.request.

CVE-2020-26116 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:L/A:N).

3.2.167 LOOP WITH UNREACHABLE EXIT CONDITION ('INFINITE LOOP') CWE-835

The iconv function in the GNU C Library (aka glibc or libc6) 2.32 and earlier, when processing invalid multi-byte input sequences in IBM1364, IBM1371, IBM1388, IBM1390, and IBM1399 encodings, fails to advance the input state, which could lead to an infinite loop in applications, resulting in a denial-of-service, a different vulnerability from CVE-2016-10228.

CVE-2020-27618 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.168 UNCONTROLLED RECURSION CWE-674

MIT Kerberos 5 (aka krb5) before 1.17.2 and 1.18.x before 1.18.3 allows unbounded recursion via an ASN.1-encoded Kerberos message because the lib/krb5/asn.1/asn1_encode.c support for BER indefinite lengths lacks a recursion limit.

CVE-2020-28196 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.169 INTEGER OVERFLOW OR WRAPAROUND CWE-190

An issue was discovered in p11-kit 0.21.1 through 0.23.21. Multiple integer overflows have been discovered in the array allocations in the p11-kit library and the p11-kit list command, where overflow checks are missing before calling realloc or calloc.

CVE-2020-29361 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.170 OUT-OF-BOUNDS READ CWE-125

An issue was discovered in p11-kit 0.21.1 through 0.23.21. A heap-based buffer over-read has been discovered in the RPC protocol used by thep11-kit server/remote commands and the client library. When the remote entity supplies a byte array through a serialized PKCS#11 function call, the receiving entity may allow the reading of up to 4 bytes of memory past the heap allocation.

CVE-2020-29362 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.171 OUT-OF-BOUNDS WRITE CWE-787

An issue was discovered in p11-kit 0.23.6 through 0.23.21. A heap-based buffer overflow has been discovered in the RPC protocol used by p11-kit server/remote commands and the client library. When the remote entity supplies a serialized byte array in a CK_ATTRIBUTE, the receiving entity may not allocate sufficient length for the buffer to store the deserialized value.

CVE-2020-29363 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.172 REACHABLE ASSERTION CWE-617

The iconv function in the GNU C Library (aka glibc or libc6) 2.30 to 2.32, when converting UCS4 text containing an irreversible character, fails an assertion in the code path and aborts the program, potentially resulting in a denial-of-service.

CVE-2020-29562 has been assigned to this vulnerability. A CVSS v3 base score of 4.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:L/UI:R/S:U/C:N/I:N/A:H).

3.2.173 OUT-OF-BOUNDS WRITE CWE-787

sysdeps/i386/ldbl2mpn.c in the GNU C Library (aka glibc or libc6) before 2.23 on x86 targets has a stack-based buffer overflow if the input to any of the printf family of functions is an 80-bit long double with a non-canonical bit pattern, as seen when passing a \x00\x04\x00\x00\x00\x00\x00\x00\x00\x04 value to sprintf. NOTE: the issue does not affect glibc by default in 2016 or later (i.e., 2.23 or later) because of commits made in 2015 for inlining of C99 math functions through use of GCC built-ins. In other words, the reference to 2.23 is intentional despite the mention of "Fixed for glibc 2.33" in the 26649 reference.

CVE-2020-29573 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.174 NULL POINTER DEREFERENCE CWE-476

In SQlite 3.31.1, a potential null pointer derreference was found in the INTERSEC query processing.

CVE-2020-35525 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.175 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

In SQLite 3.31.1, there is an out of bounds access problem through ALTER TABLE for views that have a nested FROM clause.

CVE-2020-35527 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.176 INTEGER UNDERFLOW (WRAP OR WRAPAROUND) CWE-191

An integer underflow was discovered in OpenLDAP before 2.4.57 leading to slapd crashes in the Certificate Exact Assertion processing, resulting in denial-of-service (schema_init.c serialNumberAndIssuerCheck).

CVE-2020-36221 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.177 REACHABLE ASSERTION CWE-617

A flaw was discovered in OpenLDAP before 2.4.57 leading to an assertion failure in slapd in the saslAuthzTo validation, resulting in denial-of-service.

CVE-2020-36222 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.178 OUT-OF-BOUNDS READ CWE-125

A flaw was discovered in OpenLDAP before 2.4.57 leading to a slapd crash in the Values Return Filter control handling, resulting in denial-of-service (double free and out-of-bounds read).

CVE-2020-36223 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.179 RELEASE OF INVALID POINTER OR REFERENCE CWE-763

A flaw was discovered in OpenLDAP before 2.4.57 leading to an invalid pointer free and slapd crash in the saslAuthzTo processing, resulting in denial-of-service.

CVE-2020-36224 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.180 DOUBLE FREE CWE-415

A flaw was discovered in OpenLDAP before 2.4.57 leading to a double free and slapd crash in the saslAuthzTo processing, resulting in denial-of-service.

CVE-2020-36225 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.181 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

A flaw was discovered in OpenLDAP before 2.4.57 leading to a memch->bv_len miscalculation and slapd crash in the saslAuthzTo processing, resulting in denial-of-service.

CVE-2020-36226 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.182 LOOP WITH UNREACHABLE EXIT CONDITION ('INFINITE LOOP') CWE-835

A flaw was discovered in OpenLDAP before 2.4.57 leading to an infinite loop in slapd with the cancel_extop Cancel operation, resulting in denial-of-service.

CVE-2020-36227 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.183 INTEGER UNDERFLOW (WRAP OR WRAPAROUND) CWE-191

An integer underflow was discovered in OpenLDAP before 2.4.57 leading to a slapd crash in the Certificate List Exact Assertion processing, resulting in denial-of-service.

CVE-2020-36228 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.184 ACCESS OF RESOURCE USING INCOMPATIBLE TYPE ('TYPE CONFUSION') CWE-843

A flaw was discovered in ldap_X509dn2bv in OpenLDAP before 2.4.57 leading to a slapd crash in the X.509 DN parsing in ad_keystring, resulting in denial-of-service.

CVE-2020-36229 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.185 REACHABLE ASSERTION CWE-617

A flaw was discovered in OpenLDAP before 2.4.57 leading in an assertion failure in slapd in the X.509 DN parsing in decode.c ber_next_element, resulting in denial-of-service.

CVE-2020-36230 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.186 BUFFER COPY WITHOUT CHECKING SIZE OF INPUT ('CLASSIC BUFFER OVERFLOW') CWE-120

Python 3.x through 3.9.1 has a buffer overflow in PyCArg_repr in _ctypes/callproc.c, which may lead to remote code execution in certain Python applications that accept floating-point numbers as untrusted input, as demonstrated by a 1e300 argument to c_double.from_param. This occurs because sprintf is used unsafely.

CVE-2021-3177 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.187 REACHABLE ASSERTION CWE-617

The iconv function in the GNU C Library (aka glibc or libc6) 2.32 and earlier, when processing invalid input sequences in the ISO-2022-JP-3 encoding, fails an assertion in the code path and aborts the program, potentially resulting in a denial-of-service.

CVE-2021-3326 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.188 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY ('PATH TRAVERSAL') CWE-22

There's a flaw in Python 3's pydoc. A local or adjacent attacker who discovers or is able to convince another local or adjacent user to start a pydoc server could access the server and use it to disclose sensitive information belonging to the other user that they would not normally be able to access. The highest risk of this flaw is to data confidentiality. This flaw affects Python versions before 3.8.9, Python versions before 3.9.3 and Python versions before 3.10.0a7.

CVE-2021-3426 has been assigned to this vulnerability. A CVSS v3 base score of 5.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:A/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N).

3.2.189 USE AFTER FREE CWE-416

There's a flaw in libxml2's xmllint in versions before 2.9.11. An attacker who is able to submit a crafted file to be processed by xmllint could trigger a use-after-free. The greatest impact of this flaw is to confidentiality, integrity, and availability.

CVE-2021-3516 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.190 OUT-OF-BOUNDS WRITE CWE-787

There is a flaw in the xml entity encoding functionality of libxml2 in versions before 2.9.11. An attacker who is able to supply a crafted file to be processed by an application linked with the affected functionality of libxml2 could trigger an out-of-bounds read. The most likely impact of this flaw is to application availability, with some potential impact to confidentiality and integrity if an attacker is able to use memory information to further exploit the application.

CVE-2021-3517 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H).

3.2.191 USE AFTER FREE CWE-416

There's a flaw in libxml2 in versions before 2.9.11. An attacker who is able to submit a crafted file to be processed by an application linked with libxml2 could trigger a use-after-free. The greatest impact from this flaw is to confidentiality, integrity, and availability.

CVE-2021-3518 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.192 INTEGER OVERFLOW OR WRAPAROUND CWE-190

There's a flaw in lz4. An attacker who submits a crafted file to an application linked with lz4 may be able to trigger an integer overflow, leading to calling of memmove() on a negative size argument, causing an out-of-bounds write and/or a crash. The greatest impact of this flaw is to availability, with some potential impact to confidentiality and integrity as well.

CVE-2021-3520 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.193 NULL POINTER DEREFERENCE CWE-476

A vulnerability found in libxml2 in versions before 2.9.11 shows that it did not propagate errors while parsing XML mixed content, causing a NULL dereference. If an untrusted XML document was parsed in recovery mode and post-validated, the flaw could be used to crash the application. The highest threat from this vulnerability is to system availability.

CVE-2021-3537 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.194 IMPROPER RESTRICTION OF RECURSIVE ENTITY REFERENCES IN DTDS ('XML ENTITY EXPANSION') CWE-776

A flaw was found in libxml2. Exponential entity expansion attack its possible bypassing all existing protection mechanisms and leading to denial-of-service.

CVE-2021-3541 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.195 IMPROPER INPUT VALIDATION CWE-20

A flaw was found in the way nettle's RSA decryption functions handled specially crafted ciphertext. An attacker could use this flaw to provide a manipulated ciphertext leading to application crash and denial-of-service.

CVE-2021-3580 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.196 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

There's a flaw in urllib's AbstractBasicAuthHandler class. An attacker who controls a malicious HTTP server that an HTTP client (such as web browser) connects to, could trigger a Regular Expression Denial of Service (ReDOS) during an authentication request with a specially crafted payload that is sent by the server to the client. The greatest threat that this flaw poses is to application availability.

CVE-2021-3733 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.197 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

A flaw was found in python. An improperly handled HTTP response in the HTTP client code of python may allow a remote attacker, who controls the HTTP server, to make the client script enter an infinite loop, consuming CPU time. The highest threat from this vulnerability is to system availability.

CVE-2021-3737 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.198 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

Heap/stack buffer overflow in the dlang_lname function in d-demangle.c in libiberty allows attackers to potentially cause a denial-of-service (segmentation fault and crash) via a crafted mangled symbol.

CVE-2021-3826 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.199 UNCONTROLLED RECURSION CWE-674

A flaw was found in systemd. An uncontrolled recursion in systemd-tmpfiles may lead to a denial-of-service at boot time when too many nested directories are created in /tmp.

CVE-2021-3997 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.200 OUT-OF-BOUNDS READ CWE-125

A flaw was found in glibc. The realpath() function can mistakenly return an unexpected value, potentially leading to information leakage and disclosure of sensitive data.

CVE-2021-3998 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.201 OFF-BY-ONE ERROR CWE-193

A flaw was found in glibc. An off-by-one buffer overflow and underflow in getcwd() may lead to memory corruption when the size of the buffer is exactly 1. A local attacker who can control the input buffer and size passed to getcwd() in a setuid program could use this flaw to potentially execute arbitrary code and escalate their privileges on the system.

CVE-2021-3999 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.202 INSUFFICIENT VERIFICATION OF DATA AUTHENTICITY CWE-345

It was found that a specially crafted LUKS header could trick cryptsetup into disabling encryption during the recovery of the device. An attacker with physical access to the medium, such as a flash disk, could use this flaw to force a user into permanently disabling the encryption layer of that medium.

CVE-2021-4122 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:P/AC:L/PR:N/UI:R/S:U/C:N/I:H/A:N).

3.2.203 UNCHECKED RETURN VALUE CWE-252

A flaw was found in Python, specifically in the FTP (File Transfer Protocol) client library in PASV (passive) mode. The issue is how the FTP client trusts the host from the PASV response by default. This flaw allows an attacker to set up a malicious FTP server that can trick FTP clients into connecting back to a given IP address and port. This vulnerability could lead to FTP client scanning ports, which otherwise would not have been possible.

CVE-2021-4189 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.204 NULL POINTER DEREFERENCE CWE-476

A NULL pointer dereference flaw was found in GnuTLS. As Nettle's hash update functions internally call memcpy, providing zero-length input may cause undefined behavior. This flaw leads to a denial-of-service after authentication in rare circumstances.

CVE-2021-4209 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.205 OUT-OF-BOUNDS READ CWE-125

A flaw was found in the src/list.c of tar 1.33 and earlier. This flaw allows an attacker who can submit a crafted input file to tar to cause uncontrolled consumption of memory. The highest threat from this vulnerability is to system availability.

CVE-2021-20193 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.206 USE AFTER FREE CWE-416

A flaw was found in SQLite's SELECT query functionality (src/select.c). This flaw allows an attacker who is capable of running SQL queries locally on the SQLite database to cause a denial-of-service or possible code execution by triggering a use-after-free. The highest threat from this vulnerability is to system availability.

CVE-2021-20227 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.207 USE AFTER FREE CWE-416

A flaw was found in gnutls. A use after free issue in client sending key_share extension may lead to memory corruption and other consequences.

CVE-2021-20231 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.208 USE AFTER FREE CWE-416

A flaw was found in gnutls. A use after free issue in client_send_params in lib/ext/pre_shared_key.c may lead to memory corruption and other potential consequences.

CVE-2021-20232 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.209 OUT-OF-BOUNDS WRITE CWE-787

A flaw was found in Nettle in versions before 3.7.2, where several Nettle signature verification functions (GOST DSA, EDDSA & ECDSA) result in the Elliptic Curve Cryptography point (ECC) multiply function being called with out-of-range scalers, possibly resulting in incorrect results. This flaw allows an attacker to force an invalid signature, causing an assertion failure or possible validation. The highest threat to this vulnerability is to confidentiality, integrity, as well as system availability.

CVE-2021-20305 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.210 EXPOSURE OF SENSITIVE INFORMATION TO AN UNAUTHORIZED ACTOR CWE-200

curl 7.1.1 to and including 7.75.0 is vulnerable to an "Exposure of Private Personal Information to an Unauthorized Actor" by leaking credentials in the HTTP Referer: header. libcurl does not strip off user credentials from the URL when automatically populating the Referer: HTTP request header field in outgoing HTTP requests, and therefore risks leaking sensitive data to the server that is the target of the second HTTP request.

CVE-2021-22876 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.211 AUTHENTICATION BYPASS BY SPOOFING CWE-290

curl 7.63.0 to and including 7.75.0 includes vulnerability that allows a malicious HTTPS proxy to MITM a connection due to bad handling of TLS 1.3 session tickets. When using a HTTPS proxy and TLS 1.3, libcurl can confuse session tickets arriving from the HTTPS proxy but work as if they arrived from the remote server and then wrongly "short-cut" the host handshake. When confusing the tickets, a HTTPS proxy can trick libcurl to use the wrong session ticket resume for the host and thereby circumvent the server TLS certificate check and make a MITM attack to be possible to perform unnoticed. Note that such a malicious HTTPS proxy needs to provide a certificate that curl will accept for the MITMed server for an attack to work - unless curl has been told to ignore the server certificate check.

CVE-2021-22890 has been assigned to this vulnerability. A CVSS v3 base score of 3.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:L/A:N).

3.2.212 EXPOSURE OF RESOURCE TO WRONG SPHERE CWE-668

curl 7.61.0 through 7.76.1 suffers from exposure of data element to wrong session due to a mistake in the code for CURLOPT_SSL_CIPHER_LIST when libcurl is built to use the Schannel TLS library. The selected cipher set was stored in a single "static" variable in the library, which has the surprising side-effect that if an application sets up multiple concurrent transfers, the last one that sets the ciphers will accidentally control the set used by all transfers. In a worst-case scenario, this weakens transport security significantly.

CVE-2021-22897 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.213 MISSING INITIALIZATION OF RESOURCE CWE-909

curl 7.7 through 7.76.1 suffers from an information disclosure when the -t command line option, known as CURLOPT_TELNETOPTIONS in libcurl, is used to send variable=content pairs to TELNET servers. Due to a flaw in the option parser for sending NEW_ENV variables, libcurl could be made to pass on uninitialized data from a stack based buffer to the server, resulting in potentially revealing sensitive internal information to the server using a clear-text network protocol.

CVE-2021-22898 has been assigned to this vulnerability. A CVSS v3 base score of 3.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:L/I:N/A:N).

3.2.214 USE AFTER FREE CWE-416

curl 7.75.0 through 7.76.1 suffers from a use-after-free vulnerability resulting in already freed memory being used when a TLS 1.3 session ticket arrives over a connection. A malicious server can use this in rare unfortunate circumstances to potentially reach remote code execution in the client. When libcurl at run-time sets up support for TLS 1.3 session tickets on a connection using OpenSSL, it stores pointers to the transfer in-memory object for later retrieval when a session ticket arrives. If the connection is used by multiple transfers (like with a reused HTTP/1.1 connection or multiplexed HTTP/2 connection) that first transfer object might be freed before the new session is established on that connection and then the function will access a memory buffer that might be freed. When using that memory, libcurl might even call a function pointer in the object, making it possible for a remote code execution if the server could somehow manage to get crafted memory content into the correct place in memory.

CVE-2021-22901 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.215 IMPROPER VALIDATION OF INTEGRITY CHECK VALUE CWE-354

When curl is instructed to download content using the metalink feature, the contents is verified against a hash provided in the metalink XML file.The metalink XML file points out to the client how to get the same content from a set of different URLs, potentially hosted by different servers and the client can then download the file from one or several of them. In a serial or parallel manner.If one of the servers hosting the contents has been breached and the contents of the specific file on that server is replaced with a modified payload, curlshould detect this when the hash of the file mismatches after a completed download. It should remove the contents and instead try getting the contents from another URL. This is not done, and instead such a hash mismatch is only mentioned in text and the potentially malicious content is kept in the file on disk.

CVE-2021-22922 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:H/A:N).

3.2.216 INSUFFICIENTLY PROTECTED CREDENTIALS CWE-522

When curl is instructed to get content using the metalink feature, and a user name and password are used to download the metalink XML file, those same credentials are then subsequently passed on to each of the servers from which curl will download or try to download the contents from. Often contrary to the user's expectations and intentions and without telling the user it happened.

CVE-2021-22923 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:N/A:N).

3.2.217 USE OF INCORRECTLY-RESOLVED NAME OR REFERENCE CWE-706

libcurl keeps previously used connections in a connection pool for subsequent transfers to reuse, if one of them matches the setup. Due to errors in the logic, the config matching function did not take 'issuercert' into account and it compared the involved paths case insensitively, which could lead to libcurl reusing wrong connections. File paths are, or can be, case sensitive on many systems but not all, and can even vary depending on used file systems. The comparison also didn't include the 'issuer cert' which a transfer can set to qualify how to verify the server certificate.

CVE-2021-22924 has been assigned to this vulnerability. A CVSS v3 base score of 3.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.218 USE OF UNINITIALIZED RESOURCE CWE-908

curl supports the -t command line option, known as CURLOPT_TELNETOPTIONS in libcurl. This rarely used option is used to send variable=content pairs to TELNET servers. Due to flaw in the option parser for sending NEW_ENV variables, libcurl could be made to pass on uninitialized data from a stack based buffer to the server. Therefore potentially revealing sensitive internal information to the server using a clear-text network protocol. This could happen because curl did not call and use sscanf() correctly when parsing the string provided by the application.

CVE-2021-22925 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.219 IMPROPER CERTIFICATE VALIDATION CWE-295

libcurl-using applications can ask for a specific client certificate to be used in a transfer. This is done with the CURLOPT_SSLCERT option (--cert with the command line tool).When libcurl is built to use the macOS native TLS library Secure Transport, an application can ask for the client certificate by name or with a file name - using the same option. If the name exists as a file, it will be used instead of by name.If the application runs with a current working directory that is writable by other users (like /tmp), a malicious user can create a file name with the same name as the app wants to use by name, and thereby trick the application to use the file based cert instead of the one referred to by name making libcurl send the wrong client certificate in the TLS connection handshake.

CVE-2021-22926 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.220 DOUBLE FREE CWE-415

When sending data to an MQTT server, libcurl <= 7.73.0 and 7.78.0 could in some circumstances erroneously keep a pointer to an already freed memory area and both use that again in a subsequent call to send data and also free it again.

CVE-2021-22945 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.2.221 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319

A user can tell curl >= 7.20.0 and <= 7.78.0 to require a successful upgrade to TLS when speaking to an IMAP, POP3 or FTP server (--ssl-reqd on the command line orCURLOPT_USE_SSL set to CURLUSESSL_CONTROL or CURLUSESSL_ALL withlibcurl). This requirement could be bypassed if the server would return a properly crafted but perfectly legitimate response.This flaw would then make curl silently continue its operations withoutTLS contrary to the instructions and expectations, exposing possibly sensitive data in clear text over the network.

CVE-2021-22946 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.222 INSUFFICIENT VERIFICATION OF DATA AUTHENTICITY CWE-345

When curl >= 7.20.0 and <= 7.78.0 connects to an IMAP or POP3 server to retrieve data using STARTTLS to upgrade to TLS security, the server can respond and send back multiple responses at once that curl caches. curl would then upgrade to TLS but not flush the in-queue of cached responses but instead continue using and trustingthe responses it got before the TLS handshake as if they were authenticated.Using this flaw, it allows a Man-In-The-Middle attacker to first inject the fake responses, then pass-through the TLS traffic from the legitimate server and trick curl into sending data back to the user thinking the attacker's injected data comes from the TLS-protected server.

CVE-2021-22947 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.223 IMPROPER INPUT VALIDATION CWE-20

The package python/cpython from 0 and before 3.6.13, from 3.7.0 and before 3.7.10, from 3.8.0 and before 3.8.8, from 3.9.0 and before 3.9.2 are vulnerable to Web Cache Poisoning via urllib.parse.parse_qsl and urllib.parse.parse_qs by using a vector called parameter cloaking. When the attacker can separate query parameters using a semicolon (;), they can cause a difference in the interpretation of the request between the proxy (running with default configuration) and the server. This can result in malicious requests being cached as completely safe ones, as the proxy would usually not see the semicolon as a separator, and therefore would not include it in a cache key of an unkeyed parameter.

CVE-2021-23336 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:N/I:L/A:H).

3.2.224 REACHABLE ASSERTION CWE-617

In OpenLDAP through 2.4.57 and 2.5.x through 2.5.1alpha, an assertion failure in slapd can occur in the issuerAndThisUpdateCheck function via a crafted packet, resulting in a denial-of-service (daemon exit) via a short timestamp. This is related to schema_init.c and checkTime.

CVE-2021-27212 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.225 INCORRECT CONVERSION BETWEEN NUMERIC TYPES CWE-681

An issue was discovered in GNOME GLib before 2.66.7 and 2.67.x before 2.67.4. If g_byte_array_new_take() was called with a buffer of 4GB or more on a 64-bit platform, the length would be truncated modulo 2**32, causing unintended length truncation.

CVE-2021-27218 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.226 INCORRECT CONVERSION BETWEEN NUMERIC TYPES CWE-681

An issue was discovered in GNOME GLib before 2.66.6 and 2.67.x before 2.67.3. The function g_bytes_new has an integer overflow on 64-bit platforms due to an implicit cast from 64 bits to 32 bits. The overflow could potentially lead to memory corruption.

CVE-2021-27219 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.227 DOUBLE FREE CWE-415

The nameserver caching daemon (nscd) in the GNU C Library (aka glibc or libc6) 2.29 through 2.33, when processing a request for netgroup lookup, may crash due to a double-free, potentially resulting in degraded service or Denial of Service on the local system. This is related to netgroupcache.c.

CVE-2021-27645 has been assigned to this vulnerability. A CVSS v3 base score of 2.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:N/I:N/A:L).

3.2.228 DOUBLE FREE CWE-415

ssh-agent in OpenSSH before 8.5 has a double free that may be relevant in a few less-common scenarios, such as unconstrained agent-socket access on a legacy operating system, or the forwarding of an agent to an attacker-controlled host.

CVE-2021-28041 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:L/UI:R/S:U/C:H/I:H/A:H).

3.2.229 IMPROPER LINK RESOLUTION BEFORE FILE ACCESS ('LINK FOLLOWING') CWE-59

An issue was discovered in GNOME GLib before 2.66.8. When g_file_replace() is used with G_FILE_CREATE_REPLACE_DESTINATION to replace a path that is a dangling symlink, it incorrectly also creates the target of the symlink as an empty file, which could conceivably have security relevance if the symlink is attacker-controlled. (If the path is a symlink to a file that already exists, then the contents of that file correctly remain unchanged.)

CVE-2021-28153 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).

3.2.230 IMPROPER CERTIFICATE VALIDATION CWE-295

The urllib3 library 1.26.x before 1.26.4 for Python omits SSL certificate validation in some cases involving HTTPS to HTTPS proxies. The initial connection to the HTTPS proxy (if an SSLContext isn't given via proxy_config) doesn't verify the hostname of the certificate. This means certificates for different servers that still validate properly with the default urllib3 SSLContext will be silently accepted.

CVE-2021-28363 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N).

3.2.231 URL REDIRECTION TO UNTRUSTED SITE ('OPEN REDIRECT') CWE-601

Python 3.x through 3.10 has an open redirection vulnerability in lib/http/server.py due to no protection against multiple (/) at the beginning of URI path which may leads to information disclosure.

CVE-2021-28861 has been assigned to this vulnerability. A CVSS v3 base score of 7.4 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:H/I:N/A:N).

3.2.232 OUT-OF-BOUNDS READ CWE-125

An issue found in SQLite SQLite3 v.3.35.4 that could allow a remote attacker to cause a denial of service via the appendvfs.c function.

CVE-2021-31239 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.233 OUT-OF-BOUNDS WRITE CWE-787

An issue was discovered in json-c from 20200420 (post 0.14 unreleased code) through 0.15-20200726. A stack-buffer-overflow exists in the auxiliary sample program json_parse which is located in the function parseit.

CVE-2021-32292 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.234 LOOP WITH UNREACHABLE EXIT CONDITION ('INFINITE LOOP') CWE-835

In elfutils 0.183, an infinite loop was found in the function handle_symtab in readelf.c .Which allows attackers to cause a denial-of-service (infinite loop) via crafted file.

CVE-2021-33294 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.235 OBSERVABLE DISCREPANCY CWE-203

Libgcrypt before 1.8.8 and 1.9.x before 1.9.3 mishandles ElGamal encryption because it lacks exponent blinding to address a side-channel attack against mpi_powm, and the window size is not chosen appropriately. This, for example, affects use of ElGamal in OpenPGP.

CVE-2021-33560 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.236 USE AFTER FREE CWE-416

The mq_notify function in the GNU C Library (aka glibc) versions 2.32 and 2.33 has a use-after-free. It may use the notification thread attributes object (passed through its struct sigevent parameter) after it has been freed by the caller, leading to a denial-of-service (application crash) or possibly unspecified other impact.

CVE-2021-33574 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.237 ALLOCATION OF RESOURCES WITHOUT LIMITS OR THROTTLING CWE-770

The use of alloca function with an uncontrolled size in function unit_name_path_escape allows a local attacker, able to mount a filesystem on a very long path, to crash systemd and the whole system by allocating a very large space in the stack.

CVE-2021-33910 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.238 INTEGER OVERFLOW OR WRAPAROUND CWE-190

The wordexp function in the GNU C Library (aka glibc) through 2.33 may crash or read arbitrary memory in parse_param (in posix/wordexp.c) when called with an untrusted, crafted pattern, potentially resulting in a denial-of-service or disclosure of information. This occurs because atoi was used but strtoul should have been used to ensure correct calculations.

CVE-2021-35942 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.2.239 USE AFTER FREE CWE-416

The CIL compiler in SELinux 3.2 has a use-after-free in __cil_verify_classperms (called from __cil_verify_classpermission and __cil_pre_verify_helper).

CVE-2021-36084 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:L).

3.2.240 USE AFTER FREE CWE-416

The CIL compiler in SELinux 3.2 has a use-after-free in __cil_verify_classperms (called from __verify_map_perm_classperms and hashtab_map).

CVE-2021-36085 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:L).

3.2.241 USE AFTER FREE CWE-416

The CIL compiler in SELinux 3.2 has a use-after-free in cil_reset_classpermission (called from cil_reset_classperms_set and cil_reset_classperms_list).

CVE-2021-36086 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:L).

3.2.242 OUT-OF-BOUNDS READ CWE-125

The CIL compiler in SELinux 3.2 has a heap-based buffer over-read in ebitmap_match_any (called indirectly from cil_check_neverallow). This occurs because there is sometimes a lack of checks for invalid statements in an optional block.

CVE-2021-36087 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:L).

3.2.243 NULL POINTER DEREFERENCE CWE-476

ec_verify in kdc/kdc_preauth_ec.c in the Key Distribution Center (KDC) in MIT Kerberos 5 (aka krb5) before 1.18.4 and 1.19.x before 1.19.2 allows remote attackers to cause a NULL pointer dereference and daemon crash. This occurs because a return value is not properly managed in a certain situation.

CVE-2021-36222 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.244 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

A segmentation fault can occur in the sqlite3.exe command-line component of SQLite 3.36.0 via the idxGetTableInfo function when there is a crafted SQL query.

CVE-2021-36690 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.245 INTEGER OVERFLOW OR WRAPAROUND CWE-190

An integer overflow in util-linux through 2.37.1 can potentially cause a buffer overflow if an attacker were able to use system resources in a way that leads to a large number in the /proc/sysvipc/sem file.

CVE-2021-37600 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.246 NULL POINTER DEREFERENCE CWE-476

The Key Distribution Center (KDC) in MIT Kerberos 5 (aka krb5) before 1.18.5 and 1.19.x before 1.19.3 has a NULL pointer dereference in kdc/do_tgs_req.c via a FAST inner body that lacks a server field.

CVE-2021-37750 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.247 NULL POINTER DEREFERENCE CWE-476

In librt in the GNU C Library (aka glibc) through 2.34, sysdeps/unix/sysv/linux/mq_notify.c mishandles certain NOTIFY_REMOVED data, leading to a NULL pointer dereference. NOTE: this vulnerability was introduced as a side effect of the CVE-2021-33574 fix.

CVE-2021-38604 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.248 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

sshd in OpenSSH 6.2 through 8.x before 8.8, when certain non-default configurations are used, allows privilege escalation because supplemental groups are not initialized as expected. Helper programs for AuthorizedKeysCommand and AuthorizedPrincipalsCommand may run with privileges associated with group memberships of the sshd process, if the configuration specifies running the command as a different user.

CVE-2021-41617 has been assigned to this vulnerability. A CVSS v3 base score of 7.0 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.249 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

In iconvdata/iso-2022-jp-3.c in the GNU C Library (aka glibc) 2.34, remote attackers can force iconv() to emit a spurious '\0' character via crafted ISO-2022-JP-3 data that is accompanied by an internal state reset. This may affect data integrity in certain iconv() use cases.

CVE-2021-43396 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.250 INTEGER OVERFLOW OR WRAPAROUND CWE-190

GNU Multiple Precision Arithmetic Library (GMP) through 6.2.1 has an mpz/inp_raw.c integer overflow and resultant buffer overflow via crafted input, leading to a segmentation fault on 32-bit platforms.

CVE-2021-43618 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.251 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

In Expat (aka libexpat) before 2.4.3, a left shift by 29 (or more) places in the storeAtts function in xmlparse.c can lead to realloc misbehavior (e.g., allocating too few bytes, or only freeing memory).

CVE-2021-45960 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.252 INTEGER OVERFLOW OR WRAPAROUND CWE-190

In doProlog in xmlparse.c in Expat (aka libexpat) before 2.4.3, an integer overflow exists for m_groupSize.

CVE-2021-46143 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.253 UNCONTROLLED RECURSION CWE-674

GCC v12.0 was discovered to contain an uncontrolled recursion via the component libiberty/rust-demangle.c. This vulnerability allows attackers to cause a denial-of-service (DoS) by consuming excessive CPU and memory resources.

CVE-2021-46195 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.254 ALLOCATION OF RESOURCES WITHOUT LIMITS OR THROTTLING CWE-770

In libtirpc before 1.3.3rc1, remote attackers could exhaust the file descriptors of a process that uses libtirpc because idle TCP connections are mishandled. This can, in turn, lead to an svc_run infinite loop without accepting new connections.

CVE-2021-46828 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.255 OFF-BY-ONE ERROR CWE-193

GNU Libtasn1 before 4.19.0 has an ETYPE_OK off-by-one array size check that affects asn1_encode_simple_der.

CVE-2021-46848 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.2.256 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS IN OUTPUT USED BY A DOWNSTREAM COMPONENT ('INJECTION') CWE-74

A flaw was found in Python, specifically within the urllib.parse module. This module helps break Uniform Resource Locator (URL) strings into components. The issue involves how the urlparse method does not sanitize input and allows characters like '\r' and '\n' in the URL path. This flaw allows an attacker to input a crafted URL, leading to injection attacks. This flaw affects Python versions prior to 3.10.0b1, 3.9.5, 3.8.11, 3.7.11 and 3.6.14.

CVE-2022-0391 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.257 GENERATION OF ERROR MESSAGE CONTAINING SENSITIVE INFORMATION CWE-209

A flaw was found in the util-linux chfn and chsh utilities when compiled with Readline support. The Readline library uses an "INPUTRC" environment variable to get a path to the library config file. When the library cannot parse the specified file, it prints an error message containing data from the file. This flaw allows an unprivileged user to read root-owned files, potentially leading to privilege escalation. This flaw affects util-linux versions prior to 2.37.4.

CVE-2022-0563 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N).

3.2.258 LOOP WITH UNREACHABLE EXIT CONDITION ('INFINITE LOOP') CWE-835

The BN_mod_sqrt() function in openSSL, which computes a modular square root, contains a bug that can cause it to loop forever for non-prime moduli. Internally this function is used when parsing certificates that contain elliptic curve public keys in compressed form or explicit elliptic curve parameters with a base point encoded in compressed form. It is possible to trigger the infinite loop by crafting a certificate that has invalid explicit curve parameters. Since certificate parsing happens prior to verification of the certificate signature, any process that parses an externally supplied certificate may thus be subject to a denial of service attack. The infinite loop can also be reached when parsing crafted private keys as they can contain explicit elliptic curve parameters.

CVE-2022-0778 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.259 IMPROPER INPUT VALIDATION CWE-20

An arbitrary file write vulnerability was found in GNU gzip's zgrep utility. When zgrep is applied on the attacker's chosen file name (for example, a crafted file name), this can overwrite an attacker's content to an arbitrary attacker-selected file. This flaw occurs due to insufficient validation when processing filenames with two or more newlines where selected content and the target file names are embedded in crafted multi-line file names. This flaw allows a remote, low privileged attacker to force zgrep to write arbitrary files on the system.

CVE-2022-1271 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.260 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND ('OS COMMAND INJECTION') CWE-78

The c_rehash script does not properly sanitise shell metacharacters to prevent command injection.

CVE-2022-1292 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.261 OUT-OF-BOUNDS WRITE CWE-787

An out-of-bounds read/write vulnerability was found in e2fsprogs 1.46.5. This issue leads to a segmentation fault and possibly arbitrary code execution via a specially crafted filesystem.

CVE-2022-1304 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.262 IMPROPER CERTIFICATE VALIDATION CWE-295

Under certain circumstances, the command line OCSP verify function reports successful verification when the verification in fact failed. In this case the incorrect successful response will also be accompanied by error messages showing the failure and contradicting the apparently successful result.

CVE-2022-1343 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).

3.2.263 USE OF A BROKEN OR RISKY CRYPTOGRAPHIC ALGORITHM CWE-327

When using the RC4-MD5 ciphersuite, which is disabled by default, an attacker is able to modify data in transit due to an incorrect use of the AAD data as the MAC key in OpenSSL 3.0. An attacker is not able to decrypt any communication.

CVE-2022-1434 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.264 IMPROPER RESOURCE SHUTDOWN OR RELEASE CWE-404

The used OpenSSL version improperly reuses memory when decoding certificates or keys. This can lead to a process termination and denial-of-service for long lived processes.

CVE-2022-1473 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.265 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND ('OS COMMAND INJECTION') CWE-78

In addition to the c_rehash shell command injection identified in CVE-2022-1292, further circumstances where the c_rehash script does not properly sanitise shell metacharacters to prevent command injection were found by code review. When the CVE-2022-1292 was fixed it was not discovered that there are other places in the script where the file names of certificates being hashed were possibly passed to a command executed through the shell. This script is distributed by some operating systems in a manner where it is automatically executed. On such operating systems, an attacker could execute arbitrary commands with the privileges of the script. Use of the c_rehash script is considered obsolete and should be replaced by the OpenSSL rehash command line tool.

CVE-2022-2068 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.266 INADEQUATE ENCRYPTION STRENGTH CWE-326

AES OCB mode for 32-bit x86 platforms using the AES-NI assembly optimised implementation will not encrypt the entirety of the data under some circumstances. This could reveal sixteen bytes of data that was preexisting in the memory that wasn't written. In the special case of "in place" encryption, sixteen bytes of the plaintext would be revealed. Since OpenSSL does not support OCB based cipher suites for TLS and DTLS, they are both unaffected.

CVE-2022-2097 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.267 OUT-OF-BOUNDS WRITE CWE-787

The OpenSSL 3.0.4 release introduced a serious bug in the RSA implementation for X86_64 CPUs supporting the AVX512IFMA instructions. This issue makes the RSA implementation with 2048 bit private keys incorrect on such machines and memory corruption will happen during the computation. As a consequence of the memory corruption an attacker may be able to trigger a remote code execution on the machine performing the computation. SSL/TLS servers or other servers using 2048 bit RSA private keys running on machines supporting AVX512IFMA instructions of the X86_64 architecture are affected by this issue.

CVE-2022-2274 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.268 DOUBLE FREE CWE-415

A vulnerability found in gnutls. This security flaw happens because of a double free error occurs during verification of pkcs7 signatures in gnutls_pkcs7_verify function.

CVE-2022-2509 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.269 OUT-OF-BOUNDS WRITE CWE-787

A flaw was found in the bash package, where a heap-buffer overflow can occur in valid parameter_transform. This issue may lead to memory problems.

CVE-2022-3715 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.270 OFF-BY-ONE ERROR CWE-193

An off-by-one Error issue was discovered in Systemd in format_timespan() function of time-util.c. An attacker could supply specific values for time and accuracy that leads to buffer overrun in format_timespan(), leading to a denial-of-service.

CVE-2022-3821 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.271 INADEQUATE ENCRYPTION STRENGTH CWE-326

A timing based side channel exists in the OpenSSL RSA Decryption implementation which could be sufficient to recover a plaintext across a network in a Bleichenbacher style attack. To achieve a successful decryption an attacker would have to be able to send a very large number of trial messages for decryption. The vulnerability affects all RSA padding modes: PKCS#1 v1.5, RSA-OEAP and RSASVE. For example, in a TLS connection, RSA is commonly used by a client to send an encrypted pre-master secret to the server. An attacker that had observed a genuine connection between a client and a server could use this flaw to send trial messages to the server and record the time taken to process them. After a sufficiently large number of messages the attacker could recover the pre-master secret used for the original connection and thus be able to decrypt the application data sent over that connection.

CVE-2022-4304 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.272 DOUBLE FREE CWE-415

The function PEM_read_bio_ex() reads a PEM file from a BIO and parses and decodes the "name" (e.g. "CERTIFICATE"), any header data and the payload data. If the function succeeds then the "name_out", "header" and "data" arguments are populated with pointers to buffers containing the relevant decoded data. The caller is responsible for freeing those buffers. It is possible to construct a PEM file that results in 0 bytes of payload data. In this case PEM_read_bio_ex() will return a failure code but will populate the header argument with a pointer to a buffer that has already been freed. If the caller also frees this buffer then a double free will occur. This will most likely lead to a crash. This could be exploited by an attacker who has the ability to supply malicious PEM files for parsing to achieve a denial of service attack. The functions PEM_read_bio() and PEM_read() are simple wrappers around PEM_read_bio_ex() and therefore these functions are also directly affected. These functions are also called indirectly by a number of other OpenSSL functions including PEM_X509_INFO_read_bio_ex() and SSL_CTX_use_serverinfo_file() which are also vulnerable. Some OpenSSL internal uses of these functions are not vulnerable because the caller does not free the header argument if PEM_read_bio_ex() returns a failure code. These locations include the PEM_read_bio_TYPE() functions as well as the decoders introduced in OpenSSL 3.0. The OpenSSL asn1parse command line application is also impacted by this issue.

CVE-2022-4450 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.273 IMPROPER AUTHENTICATION CWE-287

An improper authentication vulnerability exists in curl 7.33.0 to and including 7.82.0 which might allow reuse OAUTH2-authenticated connections without properly making sure that the connection was authenticated with the same credentials as set for this transfer. This affects SASL-enabled protocols: SMPTP(S), IMAP(S), POP3(S) and LDAP(S) (openldap only).

CVE-2022-22576 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N).

3.2.274 INTEGER OVERFLOW OR WRAPAROUND CWE-190

addBinding in xmlparse.c in Expat (aka libexpat) before 2.4.3 has an integer overflow.

CVE-2022-22822 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.275 INTEGER OVERFLOW OR WRAPAROUND CWE-190

build_model in xmlparse.c in Expat (aka libexpat) before 2.4.3 has an integer overflow.

CVE-2022-22823 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.276 INTEGER OVERFLOW OR WRAPAROUND CWE-190

defineAttribute in xmlparse.c in Expat (aka libexpat) before 2.4.3 has an integer overflow.

CVE-2022-22824 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.277 INTEGER OVERFLOW OR WRAPAROUND CWE-190

lookup in xmlparse.c in Expat (aka libexpat) before 2.4.3 has an integer overflow.

CVE-2022-22825 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.278 INTEGER OVERFLOW OR WRAPAROUND CWE-190

nextScaffoldPart in xmlparse.c in Expat (aka libexpat) before 2.4.3 has an integer overflow.

CVE-2022-22826 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.279 INTEGER OVERFLOW OR WRAPAROUND CWE-190

storeAtts in xmlparse.c in Expat (aka libexpat) before 2.4.3 has an integer overflow.

CVE-2022-22827 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.280 BUFFER COPY WITHOUT CHECKING SIZE OF INPUT ('CLASSIC BUFFER OVERFLOW') CWE-120

The deprecated compatibility function svcunix_create in the sunrpc module of the GNU C Library (aka glibc) through 2.34 copies its path argument on the stack without validating its length, which may result in a buffer overflow, potentially resulting in a denial-of-service or (if an application is not built with a stack protector enabled) arbitrary code execution.

CVE-2022-23218 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.281 BUFFER COPY WITHOUT CHECKING SIZE OF INPUT ('CLASSIC BUFFER OVERFLOW') CWE-120

The deprecated compatibility function clnt_create in the sunrpc module of the GNU C Library (aka glibc) through 2.34 copies its hostname argument on the stack without validating its length, which may result in a buffer overflow, potentially resulting in a denial-of-service or (if an application is not built with a stack protector enabled) arbitrary code execution.

CVE-2022-23219 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.282 USE AFTER FREE CWE-416

valid.c in libxml2 before 2.9.13 has a use-after-free of ID and IDREF attributes.

CVE-2022-23308 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.283 INTEGER OVERFLOW OR WRAPAROUND CWE-190

Expat (aka libexpat) before 2.4.4 has a signed integer overflow in XML_GetBuffer, for configurations with a nonzero XML_CONTEXT_BYTES.

CVE-2022-23852 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.284 INTEGER OVERFLOW OR WRAPAROUND CWE-190

Expat (aka libexpat) before 2.4.4 has an integer overflow in the doProlog function.

CVE-2022-23990 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.285 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89

In Cyrus SASL 2.1.17 through 2.1.27 before 2.1.28, plugins/sql.c does not escape the password for a SQL INSERT or UPDATE statement.

CVE-2022-24407 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.286 IMPROPER ENCODING OR ESCAPING OF OUTPUT CWE-116

xmltok_impl.c in Expat (aka libexpat) before 2.4.5 lacks certain validation of encoding, such as checks for whether a UTF-8 character is valid in a certain context.

CVE-2022-25235 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.287 EXPOSURE OF RESOURCE TO WRONG SPHERE CWE-668

xmlparse.c in Expat (aka libexpat) before 2.4.5 allows attackers to insert namespace-separator characters into namespace URIs.

CVE-2022-25236 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.288 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

In Expat (aka libexpat) before 2.4.5, an attacker can trigger stack exhaustion in build_model via a large nesting depth in the DTD element.

CVE-2022-25313 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.289 INTEGER OVERFLOW OR WRAPAROUND CWE-190

In Expat (aka libexpat) before 2.4.5, there is an integer overflow in copyString.

CVE-2022-25314 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.290 INTEGER OVERFLOW OR WRAPAROUND CWE-190

In Expat (aka libexpat) before 2.4.5, there is an integer overflow in storeRawNames.

CVE-2022-25315 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.291 UNTRUSTED SEARCH PATH CWE-426

In Python before 3.10.3 on Windows, local users can gain privileges because the search path is inadequately secured. The installer may allow a local attacker to add user-writable directories to the system search path. To exploit, an administrator must have installed Python for all users and enabled PATH entries. A non-administrative user can trigger a repair that incorrectly adds user-writable paths into PATH, enabling search-path hijacking of other users and system services. This affects Python (CPython) through 3.7.12, 3.8.x through 3.8.12, 3.9.x through 3.9.10, and 3.10.x through 3.10.2.

CVE-2022-26488 has been assigned to this vulnerability. A CVSS v3 base score of 7.0 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.292 INSUFFICIENTLY PROTECTED CREDENTIALS CWE-522

An insufficiently protected credentials vulnerability exists in curl 4.9 to and include curl 7.82.0 are affected that could allow an attacker to extract credentials when follows HTTP(S) redirects is used with authentication could leak credentials to other services that exist on different protocols or port numbers.

CVE-2022-27774 has been assigned to this vulnerability. A CVSS v3 base score of 5.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:U/C:H/I:N/A:N).

3.2.293 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

An information disclosure vulnerability exists in curl 7.65.0 to 7.82.0 are vulnerable that by using an IPv6 address that was in the connection pool but with a different zone id it could reuse a connection instead.

CVE-2022-27775 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.294 INSUFFICIENTLY PROTECTED CREDENTIALS CWE-522

A insufficiently protected credentials vulnerability in fixed in curl 7.83.0 might leak authentication or cookie header data on HTTP redirects to the same host but another port number.

CVE-2022-27776 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N).

3.2.295 USE OF INCORRECTLY-RESOLVED NAME OR REFERENCE CWE-706

A use of incorrectly resolved name vulnerability fixed in 7.83.1 might remove the wrong file when --no-clobber is used together with --remove-on-error.

CVE-2022-27778 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:H/A:H).

3.2.296 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

libcurl wrongly allows cookies to be set for Top Level Domains (TLDs) if the host name is provided with a trailing dot.curl can be told to receive and send cookies. curl's "cookie engine" can bebuilt with or without Public Suffix List awareness. If PSL support not provided, a more rudimentary check exists to at least prevent cookies from being set on TLDs. This check was broken if the host name in the URL uses a trailing dot.This can allow arbitrary sites to set cookies that then would get sent to a different and unrelated site or domain.

CVE-2022-27779 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.297 SERVER-SIDE REQUEST FORGERY (SSRF) CWE-918

The curl URL parser wrongly accepts percent-encoded URL separators like '/' when decoding the host name part of a URL, making it a different URL using the wrong host name when it is later retrieved. This flaw can be used to circumvent filters, checks and more.

CVE-2022-27780 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.298 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

libcurl provides the CURLOPT_CERTINFO option to allow applications to request details to be returned about a server's certificate chain.Due to an erroneous function, a malicious server could make libcurl built with NSS get stuck in a never-ending busy-loop when trying to retrieve that information.

CVE-2022-27781 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.299 IMPROPER CERTIFICATE VALIDATION CWE-295

libcurl would reuse a previously created connection even when a TLS or SSH related option had been changed that should have prohibited reuse.libcurl keeps previously used connections in a connection pool for subsequent transfers to reuse if one of them matches the setup. However, several TLS and SSH settings were left out from the configuration match checks, making them match too easily.

CVE-2022-27782 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.300 UNCONTROLLED RECURSION CWE-674

libiberty/rust-demangle.c in GNU GCC 11.2 allows stack consumption in demangle_const, as demonstrated by nm-new.

CVE-2022-27943 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.301 IMPROPER AUTHENTICATION CWE-287

The Linux-PAM package before 1.5.2-6.1 for openSUSE Tumbleweed allows authentication bypass for SSH logins. The pam_access.so module doesn't correctly restrict login if a user tries to connect from an IP address that is not resolvable via DNS. In such conditions, a user with denied access to a machine can still get access. NOTE: the relevance of this issue is largely limited to openSUSE Tumbleweed and openSUSE Factory; it does not affect Linux-PAM upstream.

CVE-2022-28321 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.302 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89

In OpenLDAP 2.x before 2.5.12 and 2.6.x before 2.6.2, a SQL injection vulnerability exists in the experimental back-sql backend to slapd, via a SQL statement within an LDAP query. This can occur during an LDAP search operation when the search filter is processed, due to a lack of proper escaping.

CVE-2022-29155 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.303 INTEGER OVERFLOW OR WRAPAROUND CWE-190

In libxml2 before 2.9.14, several buffer handling functions in buf.c (xmlBuf) and tree.c (xmlBuffer) don't check for integer overflows. This can result in out-of-bounds memory writes. Exploitation requires a victim to open a crafted, multi-gigabyte XML file. Other software using libxml2's buffer functions, for example libxslt through 1.1.35, is affected as well.

CVE-2022-29824 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.304 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319

Using its HSTS support, curl can be instructed to use HTTPS directly instead of using an insecure clear-text HTTP step even when HTTP is provided in the URL. This mechanism could be bypassed if the host name in the given URL used a trailing dot while not using one when it built the HSTS cache. Or the other way around - by having the trailing dot in the HSTS cache and not using the trailing dot in the URL.

CVE-2022-30115 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N).

3.2.305 ALLOCATION OF RESOURCES WITHOUT LIMITS OR THROTTLING CWE-770

A malicious server can serve excessive amounts of "Set-Cookie:" headers in a HTTP response to curl and curl versions prior to 7.84.0 stores all of them. A sufficiently large amount of (big) cookies make subsequent HTTP requests to this, or other servers to which the cookies match, create requests that become larger than the threshold that curl uses internally to avoid sending crazy large requests (1048576 bytes) and instead returns an error. This denial state might remain for as long as the same cookies are kept, match and haven't expired.

CVE-2022-32205 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:L).

3.2.306 ALLOCATION OF RESOURCES WITHOUT LIMITS OR THROTTLING CWE-770

curl versions prior to 7.84.0 supports "chained" HTTP compression algorithms, meaning that a server response can be compressed multiple times and potentially with different algorithms. The number of acceptable "links" in this "decompression chain" was unbounded, allowing a malicious server to insert a virtually unlimited number of compression steps.The use of such a decompression chain could result in a "malloc bomb", making curl end up spending enormous amounts of allocated heap memory, or trying to and returning out of memory errors.

CVE-2022-32206 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.307 INCORRECT DEFAULT PERMISSIONS CWE-276

When curl versions prior to 7.84.0 saves cookies, alt-svc and hsts data to local files, it makes the operation atomic by finalizing the operation with a rename from a temporary name to the final target file name.In that rename operation, it might accidentally widen the permissions for the target file, leaving the updated file accessible to more users than intended.

CVE-2022-32207 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.308 OUT-OF-BOUNDS WRITE CWE-787

When curl versions prior to 7.84.0 does FTP transfers secured by krb5, it handles message verification failures wrongly. This flaw makes it possible for a Man-In-The-Middle attack to go unnoticed and even allows it to inject data to the client.

CVE-2022-32208 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.309 EXPECTED BEHAVIOR VIOLATION CWE-440

When doing HTTP(S) transfers, libcurl might erroneously use the read callback (CURLOPT_READFUNCTION) to ask for data to send, even when the CURLOPT_POSTFIELDS option has been set, if the same handle previously was used to issue a PUT request which used that callback. This flaw may surprise the application and cause it to misbehave and either send off the wrong data or use memory after free or similar in the subsequent POST request. The problem exists in the logic for a reused handle when it is changed from a PUT to a POST.

CVE-2022-32221 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:N).

3.2.310 IMPROPER VALIDATION OF SYNTACTIC CORRECTNESS OF INPUT CWE-1286

When curl is used to retrieve and parse cookies from a HTTP(S) server, it accepts cookies using control codes that when later are sent back to a HTTP server might make the server return 400 responses. Effectively allowing a "sister site" to deny service to all siblings.

CVE-2022-35252 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.311 STACK-BASED BUFFER OVERFLOW CWE-121

curl can be told to parse a .netrc file for credentials. If that file ends in a line with 4095 consecutive non-white space letters and no newline, curl would first read past the end of the stack-based buffer, and if the read works, write a zero byte beyond its boundary.This will in most cases cause a segfault or similar, but circumstances might also cause different outcomes.If a malicious user can provide a custom netrc file to an application or otherwise affect its contents, this flaw could be used as denial-of-service.

CVE-2022-35260 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H).

3.2.312 IMPROPER VALIDATION OF ARRAY INDEX CWE-129

SQLite 1.0.12 through 3.39.x before 3.39.2 sometimes allows an array-bounds overflow if billions of bytes are used in a string argument to a C API.

CVE-2022-35737 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.313 OUT-OF-BOUNDS WRITE CWE-787

zlib through 1.2.12 has a heap-based buffer over-read or buffer overflow in inflate in inflate.c via a large gzip header extra field. NOTE: only applications that call inflateGetHeader are affected. Some common applications bundle the affected zlib source code but may be unable to call inflateGetHeader (e.g., see the nodejs/node reference).

CVE-2022-37434 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.314 INTEGER OVERFLOW OR WRAPAROUND CWE-190

The Keccak XKCP SHA-3 reference implementation before fdc6fef has an integer overflow and resultant buffer overflow that allows attackers to execute arbitrary code or eliminate expected cryptographic properties. This occurs in the sponge function interface.

CVE-2022-37454 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.315 INTEGER OVERFLOW OR WRAPAROUND CWE-190

An issue was discovered in libxml2 before 2.10.3. When parsing a multi-gigabyte XML document with the XML_PARSE_HUGE parser option enabled, several integer counters can overflow. This results in an attempt to access an array at a negative 2GB offset, typically leading to a segmentation fault.

CVE-2022-40303 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.316 DOUBLE FREE CWE-415

An issue was discovered in libxml2 before 2.10.3. Certain invalid XML entity definitions can corrupt a hash table key, potentially leading to subsequent logic errors. In one case, a double-free can be provoked.

CVE-2022-40304 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.317 USE AFTER FREE CWE-416

libexpat before 2.4.9 has a use-after-free in the doContent function in xmlparse.c.

CVE-2022-40674 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.318 INTEGER OVERFLOW OR WRAPAROUND CWE-190

PAC parsing in MIT Kerberos 5 (aka krb5) before 1.19.4 and 1.20.x before 1.20.1 has integer overflows that may lead to remote code execution (in KDC, kadmind, or a GSS or Kerberos application server) on 32-bit platforms (which have a resultant heap-based buffer overflow), and cause a denial of service on other platforms.

CVE-2022-42898 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.319 DOUBLE FREE CWE-415

curl before 7.86.0 has a double free. If curl is told to use an HTTP proxy for a transfer with a non-HTTP(S) URL, it sets up the connection to the remote server by issuing a CONNECT request to the proxy, and then tunnels the rest of the protocol through. An HTTP proxy might refuse this request (HTTP proxies often only allow outgoing connections to specific port numbers, like 443 for HTTPS) and instead return a non-200 status code to the client. Due to flaws in the error/cleanup handling, this could trigger a double free in curl if one of the following schemes were used in the URL for the transfer: dict, gopher, gophers, ldap, ldaps, rtmp, rtmps, or telnet. The earliest affected version is 7.77.0.

CVE-2022-42915 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.320 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319

In curl before 7.86.0, the HSTS check could be bypassed to trick it into staying with HTTP. Using its HSTS support, curl can be instructed to use HTTPS directly (instead of using an insecure cleartext HTTP step) even when HTTP is provided in the URL. This mechanism could be bypassed if the host name in the given URL uses IDN characters that get replaced with ASCII counterparts as part of the IDN conversion, e.g., using the character UTF-8 U+3002 (IDEOGRAPHIC FULL STOP) instead of the common ASCII full stop of U+002E (.). The earliest affected version is 7.77.0 2021-05-26.

CVE-2022-42916 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).

3.2.321 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319

A vulnerability exists in curl versions prior to 7.87.0 HSTS check that could be bypassed to trick it to keep using HTTP. Using its HSTS support, curl can be instructed to use HTTPS instead of using an insecure clear-text HTTP step even when HTTP is provided in the URL. However, the HSTS mechanism could be bypassed if the host name in the given URL first uses IDN characters that get replaced to ASCII counterparts as part of the IDN conversion. Like using the character UTF-8 U+3002 (IDEOGRAPHIC FULL STOP) instead of the common ASCII full stop U+002E (.). Then in a subsequent request, it does not detect the HSTS state and makes a clear text transfer. Because it would store the info IDN encoded but look for it IDN decoded.

CVE-2022-43551 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.322 USE AFTER FREE CWE-416

curl can be asked to tunnel virtually all protocols it supports through an HTTP proxy. HTTP proxies can (and often do) deny such tunnel operations using an appropriate HTTP error response code. When getting denied to tunnel the specific protocols SMB or TELNET, curl would use a heap-allocated struct after it had been freed, in its transfer shutdown code path.

CVE-2022-43552 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.323 USE AFTER FREE CWE-416

In libexpat through 2.4.9, there is a use-after free caused by overeager destruction of a shared DTD in XML_ExternalEntityParserCreate in out-of-memory situations.

CVE-2022-43680 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.324 INEFFICIENT ALGORITHMIC COMPLEXITY CWE-407

An issue was discovered in Python before 3.11.1. An unnecessary quadratic algorithm exists in one path when processing some inputs to the IDNA (RFC 3490) decoder, such that a crafted, unreasonably long name being presented to the decoder could lead to a CPU denial of service. Hostnames are often supplied by remote servers that could be controlled by a malicious actor; in such a scenario, they could trigger excessive CPU consumption on the client attempting to make use of an attacker-supplied supposed hostname. For example, the attack payload could be placed in the Location header of an HTTP response with status code 302.

CVE-2022-45061 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.325 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

systemd 250 and 251 allows local users to achieve a systemd-coredump deadlock by triggering a crash that has a long backtrace. This occurs in parse_elf_object in shared/elf-util.c. The exploitation methodology is to crash a binary calling the same function recursively, and put it in a deeply nested directory to make its backtrace large enough to cause the deadlock. This must be done 16 times when MaxConnections=16 is set for the systemd/units/systemd-coredump.socket file.

CVE-2022-45873 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.326 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

SQLite through 3.40.0, when relying on --safe for execution of an untrusted CLI script, does not properly implement the azProhibitedFunctions protection mechanism, and instead allows UDF functions such as WRITEFILE.

CVE-2022-46908 has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:L).

3.2.327 OUT-OF-BOUNDS READ CWE-125

GNU Tar through 1.34 has a one-byte out-of-bounds read that results in use of uninitialized memory for a conditional jump. Exploitation to change the flow of control has not been demonstrated. The issue occurs in from_header in list.c via a V7 archive in which mtime has approximately 11 whitespace characters.

CVE-2022-48303 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.328 OUT-OF-BOUNDS WRITE CWE-787

In Perl 5.34.0, function S_find_uninit_var in sv.c has a stack-based crash that can lead to remote code execution or local privilege escalation.

CVE-2022-48522 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.329 USE AFTER FREE CWE-416

A use-after-free exists in Python through 3.9 via heappushpop in heapq.

CVE-2022-48560 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.330 USE AFTER FREE CWE-416

The public API function BIO_new_NDEF is a helper function used for streaming ASN.1 data via a BIO. It is primarily used internally to OpenSSL to support the SMIME, CMS and PKCS7 streaming capabilities, but may also be called directly by end user applications. The function receives a BIO from the caller, prepends a new BIO_f_asn1 filter BIO onto the front of it to form a BIO chain, and then returns the new head of the BIO chain to the caller. Under certain conditions, for example if a CMS recipient public key is invalid, the new filter BIO is freed and the function returns a NULL result indicating a failure. However, in this case, the BIO chain is not properly cleaned up and the BIO passed by the caller still retains internal pointers to the previously freed filter BIO. If the caller then goes on to call BIO_pop() on the BIO then a use-after-free will occur. This will most likely result in a crash.

CVE-2023-0215 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.331 IMPROPER INPUT VALIDATION CWE-20

There is a type confusion vulnerability relating to X.400 address processing inside an X.509 GeneralName. X.400 addresses were parsed as an ASN1_STRING but the public structure definition for GENERAL_NAME incorrectly specified the type of the x400Address field as ASN1_TYPE. This field is subsequently interpreted by the OpenSSL function GENERAL_NAME_cmp as an ASN1_TYPE rather than an ASN1_STRING. When CRL checking is enabled (i.e. the application sets the X509_V_FLAG_CRL_CHECK flag), this vulnerability may allow an attacker to pass arbitrary pointers to a memcmp call, enabling them to read memory contents or enact a denial of service. In most cases, the attack requires the attacker to provide both the certificate chain and CRL, neither of which need to have a valid signature. If the attacker only controls one of these inputs, the other input must already contain an X.400 address as a CRL distribution point, which is uncommon. As such, this vulnerability is most likely to only affect applications which have implemented their own functionality for retrieving CRLs over a network.

CVE-2023-0286 has been assigned to this vulnerability. A CVSS v3 base score of 7.4 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.2.332 OBSERVABLE DISCREPANCY CWE-203

A timing side-channel in the handling of RSA ClientKeyExchange messages was discovered in GnuTLS. This side-channel can be sufficient to recover the key encrypted in the RSA ciphertext across a network in a Bleichenbacher style attack. To achieve a successful decryption the attacker would need to send a large amount of specially crafted messages to the vulnerable server. By recovering the secret from the ClientKeyExchange message, the attacker would be able to decrypt the application data exchanged over that connection.

CVE-2023-0361 has been assigned to this vulnerability. A CVSS v3 base score of 7.4 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:N).

3.2.333 IMPROPER CERTIFICATE VALIDATION CWE-295

A security vulnerability has been identified in all supported versions of OpenSSL related to the verification of X.509 certificate chains that include policy constraints. Attackers may be able to exploit this vulnerability by creating a malicious certificate chain that triggers exponential use of computational resources, leading to a denial-of-service (DoS) attack on affected systems. Policy processing is disabled by default but can be enabled by passing the -policy argument to the command line utilities or by calling the X509_VERIFY_PARAM_set1_policies() function.

CVE-2023-0464 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.334 IMPROPER CERTIFICATE VALIDATION CWE-295

Applications that use a non-default option when verifying certificates may be vulnerable to an attack from a malicious CA to circumvent certain checks. Invalid certificate policies in leaf certificates are silently ignored by OpenSSL and other certificate policy checks are skipped for that certificate. A malicious CA could use this to deliberately assert invalid certificate policies in order to circumvent policy checking on the certificate altogether. Policy processing is disabled by default but can be enabled by passing the -policy argument to the command line utilities or by calling the X509_VERIFY_PARAM_set1_policies() function.

CVE-2023-0465 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).

3.2.335 IMPROPER CERTIFICATE VALIDATION CWE-295

The function X509_VERIFY_PARAM_add0_policy() is documented to implicitly enable the certificate policy check when doing certificate verification. However the implementation of the function does not enable the check which allows certificates with invalid or incorrect policies to pass the certificate verification. As suddenly enabling the policy check could break existing deployments it was decided to keep the existing behavior of the X509_VERIFY_PARAM_add0_policy()function. Instead the applications that require OpenSSL to perform certificate policy check need to use X509_VERIFY_PARAM_set1_policies() or explicitly enable the policy check by calling X509_VERIFY_PARAM_set_flags() with the X509_V_FLAG_POLICY_CHECK flag argument. Certificate policy checks are disabled by default in OpenSSL and are not commonly used by applications.

CVE-2023-0466 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).

3.2.336 BUFFER COPY WITHOUT CHECKING SIZE OF INPUT ('CLASSIC BUFFER OVERFLOW') CWE-120

A vulnerability was found in GNU C Library 2.38. This vulnerability affects the function __monstartup of the file gmon.c of the component Call Graph Monitor. The manipulation leads to buffer overflow. It is recommended to apply a patch to fix this issue.

CVE-2023-0687 has been assigned to this vulnerability. A CVSS v3 base score of 4.6 has been assigned; the CVSS vector string is (CVSS:3.1/AV:A/AC:H/PR:L/UI:N/S:U/C:L/I:L/A:L).

3.2.337 ACCESS OF RESOURCE USING INCOMPATIBLE TYPE ('TYPE CONFUSION') CWE-843

In the Linux kernel, pick_next_rt_entity() may return a type confused entry, not detected by the BUG_ON condition, as the confused entry will not be NULL, but list_head.The buggy error condition would lead to a type confused entry with the list head,which would then be used as a type confused sched_rt_entity,causing memory corruption.

CVE-2023-1077 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.338 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

A hash collision flaw was found in the IPv6 connection lookup table in the Linux kernel's IPv6 functionality when a user makes a new kind of SYN flood attack. A user located in the local network or with a high bandwidth connection can increase the CPU usage of the server that accepts IPV6 connections up to 95%.

CVE-2023-1206 has been assigned to this vulnerability. A CVSS v3 base score of 5.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:A/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.339 ALLOCATION OF RESOURCES WITHOUT LIMITS OR THROTTLING CWE-770

Processing some specially crafted ASN.1 object identifiers or data containing them may be very slow. Applications that use OBJ_obj2txt() directly, or use any of the OpenSSL subsystems OCSP, PKCS7/SMIME, CMS, CMP/CRMF or TS with no message size limit may experience notable to very long delays when processing those messages, which may lead to a denial-of-service.

CVE-2023-2650 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.340 NULL POINTER DEREFERENCE CWE-476

A vulnerability was found in openldap. This security flaw causes a null pointer dereference in ber_memalloc_x() function.

CVE-2023-2953 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.341 NULL POINTER DEREFERENCE CWE-476

A NULL pointer dereference issue was found in the gfs2 file system in the Linux kernel. It occurs on corrupt gfs2 file systems when the evict code tries to reference the journal descriptor structure after it has been freed and set to NULL. A privileged local user could use this flaw to cause a kernel panic.

CVE-2023-3212 has been assigned to this vulnerability. A CVSS v3 base score of 4.4 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H).

3.2.342 INEFFICIENT REGULAR EXPRESSION COMPLEXITY CWE-1333

Checking excessively long DH keys or parameters may be very slow. Applications that use the functions DH_check(), DH_check_ex() or EVP_PKEY_param_check() to check a DH key or DH parameters may experience long delays. Where the key or parameters that are being checked have been obtained from an untrusted source this may lead to a denial-of-service. The function DH_check() performs various checks on DH parameters. One of those checks confirms that the modulus ('p' parameter) is not too large. Trying to use a very large modulus is slow and OpenSSL will not normally use a modulus which is over 10,000 bits in length. However the DH_check() function checks numerous aspects of the key or parameters that have been supplied. Some of those checks use the supplied modulus value even if it has already been found to be too large. An application that calls DH_check() and supplies a key or parameters obtained from an untrusted source could be vulnerable to a denial-of-service attack. The function DH_check() is itself called by a number of other OpenSSL functions. An application calling any of those other functions may similarly be affected. The other functions affected by this are DH_check_ex() and EVP_PKEY_param_check(). Also vulnerable are the OpenSSL dhparam and pkeyparam command line applications when using the '-check' option. The OpenSSL SSL/TLS implementation is not affected by this issue. The OpenSSL 3.0 and 3.1 FIPS providers are not affected by this issue.

CVE-2023-3446 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).

3.2.343 USE AFTER FREE CWE-416

A use-after-free vulnerability in the Linux kernel's net/sched: cls_u32 component can be exploited to achieve local privilege escalation. If tcf_change_indev() fails, u32_set_parms() will immediately return an error after incrementing or decrementing the reference counter in tcf_bind_filter(). If an attacker can control the reference counter and set it to zero, they can cause the reference to be freed, leading to a use-after-free vulnerability.

CVE-2023-3609 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.344 OUT-OF-BOUNDS WRITE CWE-787

An out-of-bounds write vulnerability in the Linux kernel's net/sched: sch_qfq component can be exploited to achieve local privilege escalation. The qfq_change_agg() function in net/sched/sch_qfq.c allows an out-of-bounds write because lmax is updated according to packet sizes without bounds checks.

CVE-2023-3611 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.345 NULL POINTER DEREFERENCE CWE-476

A flaw was found in the Linux kernel's IP framework for transforming packets (XFRM subsystem). This issue may allow a malicious user with CAP_NET_ADMIN privileges to directly dereference a NULL pointer in xfrm_update_ae_params(), leading to a possible kernel crash and denial of service.

CVE-2023-3772 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.346 EXCESSIVE ITERATION CWE-834

Checking excessively long DH keys or parameters may be very slow. Applications that use the functions DH_check(), DH_check_ex() or EVP_PKEY_param_check() to check a DH key or DH parameters may experience long delays. Where the key or parameters that are being checked have been obtained from an untrusted source this may lead to a denial-of-service. The function DH_check() performs various checks on DH parameters. After fixing CVE-2023-3446 it was discovered that a large q parameter value can also trigger an overly long computation during some of these checks.

CVE-2023-3817 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).

3.2.347 HEAP-BASED BUFFER OVERFLOW CWE-122

Under some circumstances, this weakness allows a user who has access to run the "ps" utility on a machine, the ability to write almost unlimited amounts of unfiltered data into the process heap.

CVE-2023-4016 has been assigned to this vulnerability. A CVSS v3 base score of 2.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:N/I:N/A:L).

3.2.348 PROTECTION MECHANISM FAILURE CWE-693

A failure in the -fstack-protector feature in GCC-based tool chains that target AArch64 allows an attacker to exploit an existing buffer overflow in dynamically-sized local variables in the application without being detected. This stack-protector failure only applies to C99-style dynamically-sized local variables or those created using alloca(). The stack-protector operates as intended for statically-sized local variables. An attacker who can exploit a buffer overflow without triggering the stack-protector might be able to change program flow control to cause an uncontrolled loss of availability or to go further and affect confidentiality or integrity.

CVE-2023-4039 has been assigned to this vulnerability. A CVSS v3 base score of 4.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:L/A:N).

3.2.349 OUT-OF-BOUNDS READ CWE-125

A flaw was found in glibc. When the getaddrinfo function is called with the AF_UNSPEC address family and the system is configured with no-aaaa mode via /etc/resolv.conf, a DNS response via TCP larger than 2048 bytes can potentially disclose stack contents through the function returned address data, and may cause a crash.

CVE-2023-4527 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:H).

3.2.350 USE AFTER FREE CWE-416

A use-after-free vulnerability in the Linux kernel's net/sched: sch_hfsc (HFSC qdisc traffic control) component can be exploited to achieve local privilege escalation. This leaves a dangling pointer that can cause a use-after-free.

CVE-2023-4623 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.351 USE AFTER FREE CWE-416

A flaw was found in glibc. In an extremely rare situation, the getaddrinfo function may access memory that has been freed, resulting in an application crash.

CVE-2023-4806 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.352 IMPROPER INPUT VALIDATION CWE-20

The POLY1305 MAC (message authentication code) implementation contains a bug that might corrupt the internal state of applications on the Windows 64 platform when running on newer X86_64 processors supporting the AVX512-IFMA instructions. If in an application that uses the OpenSSL library, an attacker can influence whether the POLY1305 MAC algorithm is used, the application state might be corrupted with various application dependent consequences.

CVE-2023-4807 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.353 USE AFTER FREE CWE-416

A flaw was found in glibc. In an uncommon situation, the gaih_inet function may use memory that has been freed, resulting in an application crash. This issue is only exploitable when the getaddrinfo function is called and the hosts database in /etc/nsswitch.conf is configured with SUCCESS=continue or SUCCESS=merge.

CVE-2023-4813 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.354 STACK-BASED BUFFER OVERFLOW CWE-121

A buffer overflow was discovered in the GNU C Library's dynamic loader ld. so while processing the GLIBC_TUNABLES environment variable. This issue could allow a local attacker to use maliciously crafted GLIBC_TUNABLES environment variables when launching binaries with SUID permission to execute code with elevated privileges.

CVE-2023-4911 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.355 USE AFTER FREE CWE-416

A use-after-free vulnerability in the Linux kernel's net/sched: sch_qfq component can be exploited to achieve local privilege escalation.When the plug qdisc is used as a class of the qfq qdisc, sending network packets triggers use-after-free in qfq_dequeue() due to the incorrect .peek handler of sch_plug and lack of error checking in agg_dequeue().

CVE-2023-4921 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.356 MISSING RELEASE OF MEMORY AFTER EFFECTIVE LIFETIME CWE-401

A flaw was found in the GNU C Library. A recent fix for CVE-2023-4806 introduced the potential for a memory leak, which may result in an application crash.

CVE-2023-5156 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).

3.2.357 IMPROPER CHECK FOR UNUSUAL OR EXCEPTIONAL CONDITIONS CWE-754

Generating excessively long X9.42 DH keys or checking excessively long X9.42 DH keys or parameters may be very slow. Applications that use the functions DH_generate_key() to generate an X9.42 DH key may experience long delays. Likewise, applications that use DH_check_pub_key(), DH_check_pub_key_ex() or EVP_PKEY_public_check() to check an X9.42 DH key or X9.42 DH parameters may experience long delays. Where the key or parameters that are being checked have been obtained from an untrusted source this may lead to a denial-of-service. While DH_check() performs all the necessary checks (as of CVE-2023-3817), DH_check_pub_key() doesn't make any of these checks, and is therefore vulnerable for excessively large P and Q parameters. Likewise, while DH_generate_key() performs a check for an excessively large P, it doesn't check for an excessively large Q.

CVE-2023-5678 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).

3.2.358 OUT-OF-BOUNDS WRITE CWE-787

A heap out-of-bounds write vulnerability in the Linux kernel's Linux Kernel Performance Events (perf) component can be exploited to achieve local privilege escalation. If perf_read_group() is called while an event's sibling_list is smaller than its child's sibling_list, it can increment or write to memory locations outside of the allocated buffer.

CVE-2023-5717 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.359 OBSERVABLE DISCREPANCY CWE-203

A vulnerability was found that the response times to malformed cipher texts in RSA-PSK ClientKeyExchange differ from response times of cipher texts with correct PKCS#1 v1.5 padding.

CVE-2023-5981 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.360 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319

A cleartext transmission of sensitive information vulnerability exists in curl versions prior to v7.88.0 that could cause HSTS functionality fail when multiple URLs are requested serially. Using its HSTS support, curl can be instructed to use HTTPS instead of using an insecure clear-text HTTP step even when HTTP is provided in the URL. This HSTS mechanism would however surprisingly be ignored by subsequent transfers when done on the same command line because the state would not be properly carried on.

CVE-2023-23914 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).

3.2.361 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319

A cleartext transmission of sensitive information vulnerability exists in curl versions prior to v7.88.0 that could cause HSTS functionality to behave incorrectly when multiple URLs are requested in parallel. Using its HSTS support, curl can be instructed to use HTTPS instead of using an insecure clear-text HTTP step even when HTTP is provided in the URL. This HSTS mechanism would however surprisingly fail when multiple transfers are done in parallel as the HSTS cache file gets overwritten by the most recently completed transfer. A later HTTP-only transfer to the earlier host name would then not get upgraded properly to HSTS.

CVE-2023-23915 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N).

3.2.362 ALLOCATION OF RESOURCES WITHOUT LIMITS OR THROTTLING CWE-770

An allocation of resources without limits or throttling vulnerability exists in curl versions prior to v7.88.0 based on the "chained" HTTP compression algorithms, meaning that a server response can be compressed multiple times and potentially with different algorithms. The number of acceptable "links" in this "decompression chain" was capped, but the cap was implemented on a per-header basis allowing a malicious server to insert a virtually unlimited number of compression steps simply by using many headers. The use of such a decompression chain could result in a "malloc bomb", making curl end up spending enormous amounts of allocated heap memory, or trying to and returning out of memory errors.

CVE-2023-23916 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.363 IMPROPER INPUT VALIDATION CWE-20

An issue in the urllib.parse component of Python before 3.11.4 allows attackers to bypass blocklisting methods by supplying a URL that starts with blank characters.

CVE-2023-24329 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.364 DOUBLE FREE CWE-415

OpenSSH server (sshd) 9.1 introduced a double-free vulnerability during options.kex_algorithms handling. This is fixed in OpenSSH 9.2. The double free can be leveraged, by an unauthenticated remote attacker in the default configuration, to jump to any location in the sshd address space.

CVE-2023-25136 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:L/A:H).

3.2.365 OUT-OF-BOUNDS WRITE CWE-787

Sprintf in the GNU C Library (glibc) 2.37 has a buffer overflow (out-of-bounds write) in some situations with a correct buffer size. This is unrelated to CWE-676. It may write beyond the bounds of the destination buffer when attempting to write a padded, thousands-separated string representation of a number, if the buffer is allocated the exact size required to represent that number as a string.

CVE-2023-25139 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.366 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Systemd before 247 does not adequately block local privilege escalation for some Sudo configurations, e.g., plausible sudoers files in which the "systemctl status" command may be executed. Specifically, systemd does not set LESSSECURE to 1, and thus other programs may be launched from the less program. This presents a substantial security risk when running systemctl from Sudo, because less executes as root when the terminal size is too small to show the complete systemctl output.

CVE-2023-26604 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.367 IMPROPER INPUT VALIDATION CWE-20

GNU libmicrohttpd before 0.9.76 allows remote DoS (Denial of Service) due to improper parsing of a multipart/form-data boundary in the postprocessor.c MHD_create_post_processor() method. This allows an attacker to remotely send a malicious HTTP POST packet that includes one or more '\0' bytes in a multipart/form-data boundary field, which - assuming a specific heap layout - will result in an out-of-bounds read and a crash in the find_boundary() function.

CVE-2023-27371 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AC:H/AV:N/A:H).

3.2.368 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS IN OUTPUT USED BY A DOWNSTREAM COMPONENT ('INJECTION') CWE-74

A vulnerability in input validation exists in curl versions prior to 8.0 during communication using the TELNET protocol may allow an attacker to pass on maliciously crafted user name and "telnet options" during server negotiation. The lack of proper input scrubbing allows an attacker to send content or perform option negotiation without the application's intent. This vulnerability could be exploited if an application allows user input, thereby enabling attackers to execute arbitrary code on the system.

CVE-2023-27533 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.369 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY ('PATH TRAVERSAL') CWE-22

A path traversal vulnerability exists in curl <8.0.0 SFTP implementation causes the tilde character to be wrongly replaced when used as a prefix in the first path element, in addition to its intended use as the first element to indicate a path relative to the user's home directory. Attackers can exploit this flaw to bypass filtering or execute arbitrary code by crafting a path like /~2/foo while accessing a server with a specific user.

CVE-2023-27534 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.370 IMPROPER AUTHENTICATION CWE-287

An authentication bypass vulnerability exists in libcurl <8.0.0 in the FTP connection reuse feature that can result in wrong credentials being used during subsequent transfers. Previously created connections are kept in a connection pool for reuse if they match the current setup. However, certain FTP settings such as CURLOPT_FTP_ACCOUNT, CURLOPT_FTP_ALTERNATIVE_TO_USER, CURLOPT_FTP_SSL_CCC, and CURLOPT_USE_SSL were not included in the configuration match checks, causing them to match too easily. This could lead to libcurl using the wrong credentials when performing a transfer, potentially allowing unauthorized access to sensitive information.

CVE-2023-27535 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.371 IMPROPER AUTHENTICATION CWE-287

An authentication bypass vulnerability exists libcurl <8.0.0 in the connection reuse feature which can reuse previously established connections with incorrect user permissions due to a failure to check for changes in the CURLOPT_GSSAPI_DELEGATION option. This vulnerability affects krb5/kerberos/negotiate/GSSAPI transfers and could potentially result in unauthorized access to sensitive information. The safest option is to not reuse connections if the CURLOPT_GSSAPI_DELEGATION option has been changed.

CVE-2023-27536 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.372 DOUBLE FREE CWE-415

A double free vulnerability exists in libcurl <8.0.0 when sharing HSTS data between separate "handles". This sharing was introduced without considerations for do this sharing across separate threads but there was no indication of this fact in the documentation. Due to missing mutexes or thread locks, two threads sharing the same HSTS data could end up doing a double-free or use-after-free.

CVE-2023-27537 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.373 IMPROPER INPUT VALIDATION CWE-20

libcurl would reuse a previously created connection even when an SSH related option had been changed that should have prohibited reuse. libcurl keeps previously used connections in a connection pool for subsequent transfers to reuse if one of them matches the setup. However, two SSH settings were left out from the configuration match checks, making them match too easily.

CVE-2023-27538 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.374 NULL POINTER DEREFERENCE CWE-476

In libxml2 before 2.10.4, parsing of certain invalid XSD schemas can lead to a NULL pointer dereference and subsequently a segfault. This occurs in xmlSchemaFixupComplexType in xmlschemas.c.

CVE-2023-28484 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.375 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

ssh-add in OpenSSH before 9.3 adds smartcard keys to ssh-agent without the intended per-hop destination constraints. The earliest affected version is 8.9.

CVE-2023-28531 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.376 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS IN OUTPUT USED BY A DOWNSTREAM COMPONENT ('INJECTION') CWE-74

In Shadow 4.13, it is possible to inject control characters into fields provided to the SUID program chfn (change finger). Although it is not possible to exploit this directly (e.g., adding a new user fails because \n is in the block list), it is possible to misrepresent the /etc/passwd file when viewed. Use of \r manipulations and Unicode characters to work around blocking of the : character make it possible to give the impression that a new user has been added. In other words, an adversary may be able to convince a system administrator to take the system offline (an indirect, social-engineered denial of service) by demonstrating that "cat /etc/passwd" shows a rogue user account.

CVE-2023-29383 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:N).

3.2.377 DOUBLE FREE CWE-415

An issue was discovered in libxml2 before 2.10.4. When hashing empty dict strings in a crafted XML document, xmlDictComputeFastKey in dict.c can produce non-deterministic values, leading to various logic and memory errors, such as a double free. This behavior occurs because there is an attempt to use the first byte of an empty string, and any value is possible (not solely the '\0' value).

CVE-2023-29469 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.378 OUT-OF-BOUNDS WRITE CWE-787

ncurses before 6.4 20230408, when used by a setuid application, allows local users to trigger security-relevant memory corruption via malformed data in a terminfo database file that is found in $HOME/.terminfo or reached via the TERMINFO or TERM environment variable.

CVE-2023-29491 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.379 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

A flaw was found in GLib. GVariant deserialization fails to validate that the input conforms to the expected format, leading to denial of service.

CVE-2023-29499 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.380 DIVIDE BY ZERO CWE-369

An issue was discovered in drivers/mtd/ubi/cdev.c in the Linux kernel 6.2. There is a divide-by-zero error in do_div(sz,mtd->erasesize), used indirectly by ctrl_cdev_ioctl, when mtd->erasesize is 0.

CVE-2023-31085 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.381 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

A flaw was found in GLib. GVariant deserialization is vulnerable to a slowdown issue where a crafted GVariant can cause excessive processing, leading to denial of service.

CVE-2023-32611 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.382 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

A flaw was found in glib, where the gvariant deserialization code is vulnerable to a denial of service introduced by additional input validation added to resolve CVE-2023-29499. The offset table validation may be very slow. This bug does not affect any released version of glib but does affect glib distributors who followed the guidance of glib developers to backport the initial fix for CVE-2023-29499.

CVE-2023-32636 has been assigned to this vulnerability. A CVSS v3 base score of 4.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.383 HEAP-BASED BUFFER OVERFLOW CWE-122

A flaw was found in GLib. The GVariant deserialization code is vulnerable to a heap buffer overflow introduced by the fix for CVE-2023-32665. This bug does not affect any released version of GLib, but does affect GLib distributors who followed the guidance of GLib developers to backport the initial fix for CVE-2023-32665.

CVE-2023-32643 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L).

3.2.384 DESERIALIZATION OF UNTRUSTED DATA CWE-502

A flaw was found in GLib. GVariant deserialization is vulnerable to an exponential blowup issue where a crafted GVariant can cause excessive processing, leading to denial of service.

CVE-2023-32665 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.385 OUT-OF-BOUNDS WRITE CWE-787

The fix for XSA-423 added logic to Linux's net back driver to deal with a front end splitting a packet in a way such that not all of the headers would come in one piece. Unfortunately the logic introduced there didn't account for the extreme case of the entire packet being split into as many pieces as permitted by the protocol, yet still being smaller than the area that's specially dealt with to keep all (possible) headers together. Such an unusual packet would therefore trigger a buffer overrun in the driver.

CVE-2023-34319 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.386 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

D-Bus before 1.15.6 sometimes allows unprivileged users to crash dbus-daemon. If a privileged user with control over the dbus-daemon is using the org.freedesktop.DBus.Monitoring interface to monitor message bus traffic, then an unprivileged user with the ability to connect to the same dbus-daemon can cause a dbus-daemon crash under some circumstances via an unreplyable message. When done on the well-known system bus, this is a denial-of-service vulnerability. The fixed versions are 1.12.28, 1.14.8, and 1.15.6.

CVE-2023-34969 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.387 OUT-OF-BOUNDS WRITE CWE-787

Linux Kernel nftables Out-Of-Bounds Read/Write Vulnerability; nft_byteorder poorly handled vm register contents when CAP_NET_ADMIN is in any user or network namespace

CVE-2023-35001 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.388 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

Envoy is a cloud-native high-performance edge/middle/service proxy. Envoy's HTTP/2 codec may leak a header map and bookkeeping structures upon receiving RST_STREAM immediately followed by the GOAWAY frames from an upstream server. In nghttp2, cleanup of pending requests due to receipt of the GOAWAY frame skips de-allocation of the bookkeeping structure and pending compressed header. The error return [code path] is taken if connection is already marked for not sending more requests due to GOAWAY frame. The clean-up code is right after the return statement, causing memory leak. Denial of service through memory exhaustion.

CVE-2023-35945 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.389 IMPROPER INPUT VALIDATION CWE-20

The PKCS#11 feature in ssh-agent in OpenSSH before 9.3p2 has an insufficiently trustworthy search path, leading to remote code execution if an agent is forwarded to an attacker-controlled system. (Code in /usr/lib is not necessarily safe for loading into ssh-agent.)

NOTE: this issue exists because of an incomplete fix for CVE-2016-10009.

CVE-2023-38408 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:H/UI:R/S:C/C:H/I:H/A:H).

3.2.390 HEAP-BASED BUFFER OVERFLOW CWE-122

This flaw makes curl overflow a heap based buffer in the SOCKS5 proxy handshake. When curl is asked to pass along the hostname to the SOCKS5 proxy to allow that to resolve the address instead of it getting done by curl itself, the maximum length that hostname can be is 255 bytes. If the hostname is detected to be longer than 255 bytes, curl switches to local name resolving and instead passes on the resolved address only to the proxy. Due to a bug, the local variable that means "let the host resolve the name" could get the wrong value during a slow SOCKS5 handshake, and contrary to the intention, copy the too long hostname to the target buffer instead of copying just the resolved address there.

CVE-2023-38545 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.391 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

This flaw allows an attacker to insert cookies at will into a running programusing libcurl, if the specific series of conditions are met.libcurl performs transfers. If a transfer has cookies enabled when the handle is duplicated, the cookie-enable state is also cloned - but without cloning the actual cookies. If the source handle did not read any cookies from a specific file on disk, the cloned version of the handle would instead store the file name as none.

CVE-2023-38546 has been assigned to this vulnerability. A CVSS v3 base score of 3.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:L/A:N).

3.2.392 OUT-OF-BOUNDS WRITE CWE-787

GNU gdb (GDB) 13.0.50.20220805-git was discovered to contain a stack overflow via the function ada_decode at /gdb/ada-lang.c.

CVE-2023-39128 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.393 OUT-OF-BOUNDS READ CWE-125

A flaw was found in the Netfilter subsystem in the Linux kernel. The nfnl_osf_add_callback function did not validate the user mode controlled opt_num field. This flaw allows a local privileged (CAP_NET_ADMIN) attacker to trigger an out-of-bounds read, leading to a crash or information disclosure.

CVE-2023-39189 has been assigned to this vulnerability. A CVSS v3 base score of 5.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:L).

3.2.394 OUT-OF-BOUNDS READ CWE-125

A flaw was found in the Netfilter subsystem in the Linux kernel. The xt_u32 module did not validate the fields in the xt_u32 structure. This flaw allows a local privileged attacker to trigger an out-of-bounds read by setting the size fields with a value beyond the array boundaries, leading to a crash or information disclosure.

CVE-2023-39192 has been assigned to this vulnerability. A CVSS v3 base score of 6.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:C/C:H/I:N/A:L).

3.2.395 OUT-OF-BOUNDS READ CWE-125

A flaw was found in the Netfilter subsystem in the Linux kernel. The sctp_mt_check did not validate the flag_count field. This flaw allows a local privileged (CAP_NET_ADMIN) attacker to trigger an out-of-bounds read, leading to a crash or information disclosure.

CVE-2023-39193 has been assigned to this vulnerability. A CVSS v3 base score of 6.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:L).

3.2.396 OUT-OF-BOUNDS READ CWE-125

A flaw was found in the XFRM subsystem in the Linux kernel. The specific flaw exists within the processing of state filters, which can result in a read past the end of an allocated buffer. This flaw allows a local privileged (CAP_NET_ADMIN) attacker to trigger an out-of-bounds read, potentially leading to an information disclosure.

CVE-2023-39194 has been assigned to this vulnerability. A CVSS v3 base score of 3.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:C/C:L/I:N/A:N).

3.2.397 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

Xmlsoft Libxml2 v2.11.0 was discovered to contain an out-of-bounds read via the xmlSAX2StartElement() function at /libxml2/SAX2.c. This vulnerability allows attackers to cause a Denial of Service (DoS) via supplying a crafted XML file.

CVE-2023-39615 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.398 USE AFTER FREE CWE-416

An issue was discovered in l2cap_sock_release in net/bluetooth/l2cap_sock.c in the Linux kernel before 6.4.10. There is a use-after-free because the children of an sk are mishandled.

CVE-2023-40283 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.399 NULL POINTER DEREFERENCE CWE-476

A NULL pointer dereference flaw was found in the Linux kernel ipv4 stack. The socket buffer (skb) was assumed to be associated with a device before calling __ip_options_compile, which is not always the case if the skb is re-routed by ipvs. This issue may allow a local user with CAP_NET_ADMIN privileges to crash the system.

CVE-2023-42754 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.400 OUT-OF-BOUNDS READ CWE-125

A flaw was found in the IPv4 Resource Reservation Protocol (RSVP) classifier in the Linux kernel. The xprt pointer may go beyond the linear part of the skb, leading to an out-of-bounds read in the rsvp_classify function. This issue may allow a local user to crash the system and cause a denial of service.

CVE-2023-42755 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:C/C:N/I:N/A:H).

3.2.401 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

The HTTP/2 protocol allows a denial of service (server resource consumption) because request cancellation can reset many streams quickly.

CVE-2023-44487 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.402 USE AFTER FREE CWE-416

libxml2 through 2.11.5 has a use-after-free that can only occur after a certain memory allocation fails. This occurs in xmlUnlinkNode in tree.c.

CVE-2023-45322 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.403 INTEGER OVERFLOW OR WRAPAROUND CWE-190

MiniZip in zlib through 1.3 has an integer overflow and resultant heap-based buffer overflow in zipOpenNewFileInZip4_64 via a long filename, comment, or extra field. NOTE: MiniZip is not a supported part of the zlib product.

CVE-2023-45853 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.404 BUFFER COPY WITHOUT CHECKING SIZE OF INPUT ('CLASSIC BUFFER OVERFLOW') CWE-120

An issue was discovered in drivers/net/ethernet/intel/igb/igb_main.c in the IGB driver in the Linux kernel before 6.5.3. A buffer size may not be adequate for frames larger than the MTU.

CVE-2023-45871 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0): Only build and run applications from trusted sources. Currently no fix is available.
  • SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0): Only build and run applications from trusted sources. Currently no fix is available.
  • SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0): Only build and run applications from trusted sources. Currently no fix is available.
  • SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0): Only build and run applications from trusted sources. Currently no fix is available.
  • SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0): Only build and run applications from trusted sources. Currently no fix is available.

Note: This SSA advises vulnerabilities for firmware version V3.1 only; for versions prior to V3.1 refer to Siemens

Security Bulletin SSB-439005.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-398330 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • December 14, 2023: Initial Publication

This product is provided subject to this Notification and this Privacy & Use policy.

Vendor

Siemens