Schneider Electric Zelio Soft 2
1. EXECUTIVE SUMMARY
- CVSS v3 7.8
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Schneider Electric
- Equipment: Zelio Soft 2
- Vulnerabilities: Use After Free, Improper Input Validation
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to achieve arbitrary code execution, cause a denial-of-service condition, or loss of confidentiality and integrity.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of Schneider Electric Zelio Soft 2 are affected:
- Zelio Soft 2: Versions prior to 5.4.2.2
3.2 Vulnerability Overview
3.2.1 USE AFTER FREE CWE-416
A Use After Free vulnerability exists that could cause arbitrary code execution, denial-of-service and loss of confidentiality & integrity if an application user opens a malicious Zelio Soft 2 project file.
CVE-2024-8422 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
3.2.2 IMPROPER INPUT VALIDATION CWE-20
An Improper Input Validation vulnerability exists that could cause a crash of the Zelio Soft 2 application if a specially crafted project file is loaded by an application user.
CVE-2024-8518 has been assigned to this vulnerability. A CVSS v3.1 base score of 3.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Energy, Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: France
3.4 RESEARCHER
rgod working with Trend Micro Zero Day Initiative reported these vulnerabilities to CISA.
4. MITIGATIONS
Schneider Electric recommends that users update to Version 5.4.2.2. It can be updated through the Schneider Electric Software Update (SESU) application and is also available for download here.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY
- October 10, 2024: Initial Publication