1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Lantronix
  • Equipment: XPort
  • Vulnerability: Missing Authentication for Critical Function

    2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker unauthorized access to the configuration interface and cause disruption to monitoring and operations.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Lantronix products are affected:

  • XPort: Versions 6.5.0.7 to 7.0.0.3

3.2 VULNERABILITY OVERVIEW

3.2.1 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306

An attacker could modify or disable settings, disrupt fuel monitoring and supply chain operations, leading to disabling of ATG monitoring. This would result in potential safety hazards in fuel storage and transportation.

CVE-2025-2567 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-2567. A base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Energy, Transportation Systems, Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Souvik Kandar from Microsec(microsec.io) reported this vulnerability to CISA.

4. MITIGATIONS

Lantronix has released firmware update v8.0.0.0 for XPort to enhance security and prevent unauthorized access.

For even greater protection, Lantronix recommends users upgrade to their XPort Edge product, which implements a cutting-edge security suite. XPort Edge is immune to these vulnerabilities. Users should contact Lantronix directly for assistance.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • April 15, 2025: Initial Publication
  • April 29, 2025: Update A: Revised mitigation section and added firmware fix link for Xport v8.0.0.0.