ICS Advisory

Siemens SIMOTION Tools

Release Date
Alert Code
ICSA-25-254-01

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 8.1
  • ATTENTION: Exploitable locally
  • Vendor: Siemens
  • Equipment: SIMOTION Tools
  • Vulnerability: Improper Check for Unusual or Exceptional Conditions

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to execute arbitrary code with SYSTEM privileges when a legitimate user installs an application that uses the affected setup component.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • SIMATIC Technology Package TPCamGen (6ES7823-0FE30-1AA0): All versions
  • SIMOTION OA MIIF (6AU1820-3DA20-0AB0): All versions
  • SIMOTION OACAMGEN (6AU1820-3EA20-0AB0): All versions
  • SIMOTION OALECO (6AU1820-3HA20-0AB0): All versions
  • SIMOTION OAVIBX (6AU1820-3CA20-0AB0): All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER CHECK FOR UNUSUAL OR EXCEPTIONAL CONDITIONS CWE-754

Nullsoft Scriptable Install System (NSIS) before 3.11 on Windows allows local users to escalate privileges to SYSTEM during an installation, because the temporary plugins directory is created under %WINDIR%\temp and unprivileged users can place a crafted executable file by winning a race condition. This occurs because EW_CREATEDIR does not always set the CreateRestrictedDirectory error flag.

CVE-2025-43715 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.1 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens reports that no fix currently is available. Siemens has also identified the following workarounds and mitigations users can apply to reduce risk:

  • Ensure that no other users are logged in and that no unknown programs are running before starting the installation of the affected products

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-563922 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely. This vulnerability has a high attack complexity.

5. UPDATE HISTORY

  • September 11, 2025: Initial Republication of Siemens SSA-563922

This product is provided subject to this Notification and this Privacy & Use policy.

Vendor

  • Siemens