Siemens RUGGEDCOM, SINEC NMS, and SINEMA
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
1. EXECUTIVE SUMMARY
- CVSS v3 9.8
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Siemens
- Equipment: RUGGEDCOM, SINEC NMS, and SINEMA
- Vulnerabilities: NULL Pointer Dereference, Out-of-bounds Write, Server-Side Request Forgery (SSRF)
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to cause a denial-of-service, crash the product, or perform remote code execution.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:
- Siemens RUGGEDCOM NMS: All versions when using the device firmware upgrade mechanism (CVE-2021-34798)
- Siemens SINEC NMS: < V1.0.3
- Siemens SINEMA Remote Connect Server: < V3.1 (CVE-2021-34798)
- Siemens SINEMA Server V14: All versions
3.2 VULNERABILITY OVERVIEW
3.2.1 NULL POINTER DEREFERENCE CWE-476
Malformed requests may cause the server to dereference a NULL pointer. This issue affects Apache HTTP Server 2.4.48 and earlier.
CVE-2021-34798 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
3.2.2 OUT-OF-BOUNDS WRITE CWE-787
ap_escape_quotes() may write beyond the end of a buffer when given malicious input. No included modules pass untrusted data to these functions, but third-party / external modules may. This issue affects Apache HTTP Server 2.4.48 and earlier.
CVE-2021-39275 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
3.2.3 SERVER-SIDE REQUEST FORGERY (SSRF) CWE-918
A crafted request uri-path can cause mod_proxy to forward the request to an origin server chosen by the remote user. This issue affects Apache HTTP Server 2.4.48 and earlier.
CVE-2021-40438 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.0 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
3.4 RESEARCHER
Siemens ProductCERT reported these vulnerabilities to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:
- SINEC NMS: Update to V1.0.3 or later version
- (CVE-2021-34798) All affected products: Restrict access to the affected systems, especially to port 443/tcp, to trusted IP addresses only
- (CVE-2021-34798) RUGGEDCOM NMS, SINEMA Server V14: Currently no fix is planned
- (CVE-2021-34798) SINEMA Remote Connect Server: Update to V3.1 or later version
- (CVE-2021-39275, CVE-2021-40438) SINEC NMS, SINEMA Server V14: Restrict access to the affected systems, especially to port 443/tcp, to trusted IP addresses only
- (CVE-2021-39275, CVE-2021-40438) SINEMA Server V14: Currently no fix is planned
As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.
For more information see the associated Siemens security advisory SSA-685781 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open attachments in unsolicited email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY
- September 16, 2025: Initial Republication of Siemens ProductCERT SSA-685781
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Siemens