Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 7.5
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Mitsubishi Electric Corporation
- Equipment: Energy Saving Data Collecting Server (EcoWebServerIII)
- Vulnerabilities: Improper Neutralization of Input During Web Page Generation, Uncontrolled Resource Consumption, Improperly Controlled Modification of Dynamically-Determined Object Attributes
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow information to be disclosed, tampered with, or result in a denial-of-service condition.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Mitsubishi Electric reports these vulnerabilities affect the following versions of EcoWebServerIII, an energy saving data collecting server:
- MES3-255C-EN: Versions 3.0.0 to 3.3.0
- MES3-255C-DM-EN: Versions 3.0.0 to 3.3.0
- MES3-255C-CN: Versions 3.0.0 to 3.3.0
- MES3-255C-DM-CN: Versions 3.0.0 to 3.3.0
3.2 VULNERABILITY OVERVIEW
3.2.1 CROSS-SITE SCRIPTING CWE-79
Multiple vulnerabilities due to cross-site scripting exist in Energy Saving Data Collecting Server (EcoWebServerIII), which may result in information disclosure or information tampering of the product.
CVE-2016-10735, CVE-2018-14040, CVE-2018-14042, CVE-2018-20676, CVE-2019-8331, CVE-2020-11022, and CVE-2020-11023 have been assigned to these vulnerabilities. A CVSS v3 base score of 6.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N ).
3.2.2 UNCONTROLLED RESOURCE CONSUMPTION CWE-400
A vulnerability due to uncontrolled resource consumption exists in Energy Saving Data Collecting Server (EcoWebServerIII), which may result in a denial-of-service condition.
CVE-2017-18214 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated for; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
3.2.3 IMPROPERLY CONTROLLED MODIFICATION OF DYNAMICALLY-DETERMINED OBJECT ATTRIBUTES CWE-915
A vulnerability due to improperly controlled modification of dynamically determined object attributes exists in Energy Saving Data Collecting Server (EcoWebServerIII), which may result in a denial-of-service condition.
CVE-2020-7746 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated for; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Japan
3.4 RESEARCHER
Mitsubishi Electric reported these vulnerabilities to CISA.
4. MITIGATIONS
Mitsubishi Electric recommends users update to the following versions to mitigate these vulnerabilities:
- MES3-255C-EN: Update to v3.3.1 or later
- MES3-255C-DM-EN: Update to v3.3.1 or later
- MES3-255C-CN: Update to v3.3.1 or later
- MES3-255C-DM-CN: Update to v3.3.1 or later
To update, users of the affected versions should refer to the user manual chapter “4.8.6 Version up of Main Program” (Setting). The manual and Setting Software for EcoWebServerIII are available to download on the MITSUBISHI ELECTRIC FA Global Website.
Mitsubishi Electric recommends users take the following mitigation measures to minimize the risk of exploiting these vulnerabilities:
- Use a firewall, a virtual private network (VPN), etc. to prevent unauthorized access when Internet access is required.
- Use within a LAN and block access from untrusted networks and hosts through firewalls.
For specific update instructions and additional details see the Mitsubishi Electric advisory.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open unsolicited attachments in email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploits specifically target these vulnerabilities.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.