ICS Advisory (ICSA-22-167-10)

Siemens SCALANCE XM-400 and XR-500

Click to Tweet.
Click to send to Facebook.
Click to Share.

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

1. EXECUTIVE SUMMARY

  • CVSS v3 5.9
  • ATTENTION: Exploitable remotely
  • Vendor: Siemens
  • Equipment: SCALANCE XM-400 and XR-500
  • Vulnerability: Improper Validation of Integrity Check Value

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to cause interruptions in the network.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of SCALANCE X industrial switches are affected:

  • XM408-4C: All versions prior to v6.5
  • XM408-4C (L3 int.): All versions prior to v6.5
  • XM408-8C: All versions prior to v6.5
  • XM408-8C (L3 int.): All versions prior to v6.5
  • XM416-4C: All versions prior to v6.5
  • XM416-4C (L3 int.): All versions prior to v6.5
  • XR524-8C, 1x230V: All versions prior to v6.5
  • XR524-8C, 1x230V (L3 int.): All versions prior to v6.5
  • XR524-8C, 2x230V: All versions prior to v6.5
  • XR524-8C, 2x230V (L3 int.): All versions prior to v6.5
  • XR524-8C, 24V: All versions prior to v6.5
  • XR524-8C, 24V (L3 int.): All versions prior to v6.5
  • XR526-8C, 1x230V: All versions prior to v6.5
  • XR526-8C, 1x230V (L3 int.): All versions prior to v6.5
  • XR526-8C, 2x230V: All versions prior to v6.5
  • XR526-8C, 2x230V (L3 int.): All versions prior to v6.5
  • XR526-8C, 24V: All versions prior to v6.5
  • XR526-8C, 24V (L3 int.): All versions prior to v6.5
  • XR528-6M: All versions prior to v6.5
  • XR528-6M (2HR2): All versions prior to v6.5
  • XR528-6M (2HR2, L3 int.): All versions prior to v6.5
  • XR528-6M (L3 int.): All versions prior to v6.5
  • XR552-12M: All versions prior to v6.5
  • XR552-12M (2HR2): All versions prior to v6.5
  • XR552-12M (2HR2): All versions prior to v6.5
  • XR552-12M (2HR2, L3 int.): All versions prior to v6.5

3.2 VULNERABILITY OVERVIEW

3.2.1    IMPROPER VALIDATION OF INTEGRITY CHECK VALUE CWE-354

The OSPF protocol implementation in affected devices fails to verify the checksum and length fields in the OSPF LS update messages. Successful exploitation requires OSPF to be enabled on an affected device and could allow an unauthenticated remote attacker to cause network interruptions.

CVE-2021-37182 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Multiple Sectors
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

For all affected products, Siemens recommends updating to v6.5 or later.

Siemens has identified the following specific workarounds and mitigations users can apply to reduce the risk:

  • Disable OSPF in the layer 3 configuration menu (note OSPF is disabled by default). The vulnerability is not exploitable when OSPF is disabled.
  • If OSPF is used, set a password for the OSPF interface, and enable MD5 authentication.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see Siemens Security Advisory SSA-145224

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov/ics in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability. This vulnerability has a high attack complexity.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 
or incident reporting:  https://us-cert.cisa.gov/report