ICS Advisory (ICSA-22-286-07)

Siemens Nucleus RTOS FTP Server (Update A)

Click to Tweet.
Click to send to Facebook.
Click to Share.

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

1. EXECUTIVE SUMMARY

  • CVSS v3 7.5
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: Nucleus Real-Time Operating System (RTOS) FTP Server
  • Vulnerability: Uncontrolled Resource Consumption

2. UPDATE INFORMATION

This updated advisory is a follow-up to the original advisory titled ICSA-22-286-07 Siemens Nucleus RTOS FTP Server that was published October 13, 2022, on the ICS webpage on cisa.gov/ICS.

3. RISK EVALUATION

Successful exploitation of this vulnerability could allow a remote attacker to generate a denial-of-service condition on devices running the affected software.

4. TECHNICAL DETAILS

4.1 AFFECTED PRODUCTS

The following Nucleus RTOS components contain the affected File Transport Protocol (FTP) server:

  • Nucleus NET: All versions

--------- Begin Update A Part 1 of 4 --------- 

  • Nucleus ReadyStart V3: All versions

--------- End Update A Part 1 of 4 --------- 

  • Nucleus Source Code: Versions including affected FTP server

4.2 VULNERABILITY OVERVIEW

4.2.1    UNCONTROLLED RESOURCE CONSUMPTION CWE-400

--------- Begin Update A Part 2 of 4 --------- 

The FTP server does not properly release memory resources reserved for incomplete connection attempts by FTP clients. This could allow a remote attacker to generate a denial-of-service condition on devices incorporating a vulnerable version of the FTP server.

--------- End Update A Part 2 of 4 --------- 

CVE-2022-38371 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

4.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

4.4 RESEARCHER

Siemens reported this vulnerability to CISA.

5. MITIGATIONS

Siemens recommends updating to the latest version of its software where available:

  • Nucleus NET: No fix available – users should follow general security measures for mitigation.

--------- Begin Update A Part 3 of 4 --------- 

--------- End Update A Part 3 of 4 --------- 

--------- Begin Update A Part 4 of 4 ---------

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • Configure TCP_MAX_KEEPALIVES to a lower value such as 3.
  • Configure TCP_KEEPALIVE_INTERVAL and TCP_KEEPALIVE_DELAY be set to 3 seconds.
  • Rebuild the application.

--------- End Update A Part 4 of 4 --------- 

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens Security Advisory in HTML or CSAF formats.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 