Siemens Third Party Component in SICAM and SITIPE Products
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
1. EXECUTIVE SUMMARY
- CVSS v4 8.8
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Siemens
- Equipment: IEC 61850 Client libraries from Triangle MicroWorks affecting SICAM and SITIPE products
- Vulnerability: Classic Buffer Overflow
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to create a denial-of-service condition by sending specially crafted MMS messages.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following Siemens products are affected:
- SICAM A8000 Device Firmware ETI5 Ethernet Int. 1x100TX IEC61850: All versions prior to V05.30
- SICAM EGS Device Firmware ETI5: All versions prior to V05.30
- SICAM 8 Software Solution: ETI5 All versions prior to V05.30
- SICAM SCC: All versions prior to V10.0
- SITIPE AT: All versions
3.2 Vulnerability Overview
3.2.1 BUFFER COPY WITHOUT CHECKING SIZE OF INPUT ('CLASSIC BUFFER OVERFLOW') CWE-120
The IEC 61850 Client libraries as integrated in affected products improperly check buffer sizes when processing received MMS messages. This could allow an unauthenticated remote attacker to create a denial of service condition by sending specially crafted MMS messages.
CVE-2024-34057 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H).
A CVSS v4 score has also been calculated for CVE-2024-34057. A base score of 8.8 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
3.4 RESEARCHER
Siemens reported this vulnerability to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:
- SICAM SCC: Update to V10.0 or later version
- ETI5 Ethernet Int. 1x100TX IEC61850: Update to V05.30 or later version . The firmware ETI5 V5.30 is present within "CP-8031/CP-8050 Package" V5.30
Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-673996 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.
5. UPDATE HISTORY
- September 12, 2024: Initial Publication