Emerson ValveLink Products
1. EXECUTIVE SUMMARY
- CVSS v4 9.3
- ATTENTION: Exploitable remotely/Low attack complexity
- Vendor: Emerson
- Equipment: ValveLink Products
- Vulnerabilities: Cleartext Storage of Sensitive Information in Memory, Protection Mechanism Failure, Uncontrolled Search Path Element, Improper Input Validation
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker with access to the system to read sensitive information stored in cleartext, tamper with parameters, and run un-authorized code.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following ValveLink products are affected:
- ValveLink SOLO: All versions prior to ValveLink 14.0
- ValveLink DTM: All versions prior to ValveLink 14.0
- ValveLink PRM: All versions prior to ValveLink 14.0
- ValveLink SNAP-ON: All versions prior to ValveLink 14.0
3.2 VULNERABILITY OVERVIEW
3.2.1 CLEARTEXT STORAGE OF SENSITIVE INFORMATION IN MEMORY CWE-316
The product stores sensitive information in cleartext in memory. The sensitive memory might be saved to disk, stored in a core dump, or remain uncleared if the product crashes, or if the programmer does not properly clear the memory before freeing it.
CVE-2025-52579 has been assigned to this vulnerability. A CVSS v3 base score of 9.4 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L).
A CVSS v4 score has also been calculated for CVE-2025-52579. A base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:L/SC:N/SI:N/SA:N).
3.2.2 CLEARTEXT STORAGE OF SENSITIVE INFORMATION IN MEMORY CWE-316
The product stores sensitive information in cleartext within a resource that might be accessible to another control sphere.
CVE-2025-50109 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).
A CVSS v4 score has also been calculated for CVE-2025-50109. A base score of 8.5 has been calculated; the CVSS vector string is (AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).
3.2.3 PROTECTION MECHANISM FAILURE CWE-693
The product does not use or incorrectly uses a protection mechanism that provides sufficient defense against directed attacks against the product.
CVE-2025-46358 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).
A CVSS v4 score has also been calculated for CVE-2025-46358. A base score of 8.5 has been calculated; the CVSS vector string is (AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).
3.2.4 UNCONTROLLED SEARCH PATH ELEMENT CWE-427
The product uses a fixed or controlled search path to find resources, but one or more locations in that path can be under the control of unintended actors.
CVE-2025-48496 has been assigned to this vulnerability. A CVSS v3 base score of 5.1 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2025-48496. A base score of 5.9 has been calculated; the CVSS vector string is (AV:L/AC:H/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.5 IMPROPER INPUT VALIDATION CWE-20
The product receives input or data, but it does not validate or incorrectly validates that the input has the properties that are required to process the data safely and correctly.
CVE-2025-53471 has been assigned to this vulnerability. A CVSS v3 base score of 5.1 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N).
A CVSS v4 score has also been calculated for CVE-2025-53471. A base score of 5.9 has been calculated; the CVSS vector string is (AV:L/AC:H/AT:N/PR:N/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: United States
3.4 RESEARCHER
Emerson reported these vulnerabilities to CISA.
4. MITIGATIONS
Emerson recommends users update their Valvelink software to ValveLink 14.0 or later. The upgrade can be downloaded from the Emerson website.
For more information see the associated Emerson security notification.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY
- July 8, 2025: Initial Publication
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Emerson