Lantronix Provisioning Manager
1. EXECUTIVE SUMMARY
- CVSS v4 8.6
- ATTENTION: Low attack complexity
- Vendor: Lantronix
- Equipment: Provisioning Manager
- Vulnerability: Improper Restriction of XML External Entity Reference
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to perform a cross-site scripting attack, which could result in remote code execution.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following Lantronix products are affected:
- Provisioning Manager: Versions 7.10.2 and prior
3.2 Vulnerability Overview
3.2.1 IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE CWE-611
Provisioning Manager is vulnerable to XML External Entity (XXE) attacks in configuration files supplied by network devices, leading to unauthenticated remote code execution on hosts with Provisioning Manager installed.
CVE-2025-7766 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.0 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-7766. A base score of 8.6 has been calculated; the CVSS vector string is (AV:A/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:L/SI:L/SA:L).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Information Technology
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: United States
3.4 RESEARCHER
Robert McLellan reported this vulnerability to CISA.
4. MITIGATIONS
Lantronix has provided a fix and recommends users update to v7.10.4 or later.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open attachments in unsolicited email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.
5. UPDATE HISTORY
- July 22, 2025: Initial Publication
This product is provided subject to this Notification and this Privacy & Use policy.