ICS Advisory

Johnson Controls iSTAR Ultra, iSTAR Ultra SE, iSTAR Ultra G2, iSTAR Ultra G2 SE, iSTAR Edge G2

Release Date
Alert Code
ICSA-25-224-02

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Johnson Controls
  • Equipment: iSTAR Ultra, iSTAR Ultra SE, iSTAR Ultra G2, iSTAR, ULTRA G2 SE, iSTAR Edge G2
  • Vulnerabilities: OS Command Injection, Insufficient Verification of Data Authenticity, Use of Default Credentials, Missing Protection Mechanism for Alternate Hardware Interface, Insecure Storage of Sensitive Information

2. RISK EVALUATION

Successful exploitation of these vulnerabilities may allow an attacker to modify firmware and access the space that is protected by the device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Software House iSTAR Ultra and Edge door controllers are affected:

  • iSTAR Ultra: Versions 6.9.2.CU02 and prior (CVE-2025-53695, CVE-2025-53696, CVE-2025-53697, CVE-2025-53700)
  • iSTAR Ultra SE: Versions 6.9.2.CU02 and prior (CVE-2025-53695, CVE-2025-53696, CVE-2025-53697, CVE-2025-53700)
  • iSTAR Ultra G2: Versions 6.9.2.CU02 and prior (CVE-2025-53695, CVE-2025-53697, CVE-2025-53700)
  • iSTAR Ultra G2 SE: Versions 6.9.2.CU02 and prior (CVE-2025-53695, CVE-2025-53697, CVE-2025-53700)
  • iSTAR Edge G2: Versions 6.9.2.CU02 and prior (CVE-2025-53695, CVE-2025-53697, CVE-2025-53700)
  • iSTAR Ultra: All versions (CVE-2025-53698, CVE-2025-53699)
  • iSTAR Ultra SE: All versions (CVE-2025-53698, CVE-2025-53699)
  • iSTAR Ultra G2: All versions (CVE-2025-53699)
  • iSTAR Ultra G2 SE: All versions (CVE-2025-53699)
  • iSTAR Edge G2: All versions (CVE-2025-53699)

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND ('OS COMMAND INJECTION') CWE-78

OS command injection in iSTAR Ultra, Ultra SE, Ultra G2, Ultra G2 SE, Edge G2 versions 6.9.2 and prior web application allows an authenticated attacker to gain even more privileged access ('root' user) to the device firmware. This is fixed in versions 6.9.3 and newer.

CVE-2025-53695 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-53695. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 INSUFFICIENT VERIFICATION OF DATA AUTHENTICITY CWE-345

iSTAR Ultra and Ultra SE versions 6.9.2 and prior performs a firmware verification on boot, however the verification does not inspect certain portions of the firmware. These firmware parts may contain malicious code. Versions 6.9.3 and newer reduce the risk of this vulnerability.

CVE-2025-53696 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-53696. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.3 USE OF DEFAULT CREDENTIALS CWE-1392

There is a default ‘root' password for iSTAR Ultra, Ultra SE, Ultra G2, Ultra G2 SE, Edge G2 versions 6.9.2 and prior which can be changed through the command shell. iSTAR Ultra and Ultra SE Versions 6.9.3 and newer reduces the risk of this vulnerability. iSTAR Ultra G2, Ultra G2 SE and Edge G2 version 6.9.3 and newer fixes this vulnerability.

CVE-2025-53697 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.7 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-53697. A base score of 8.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.4 MISSING PROTECTION MECHANISM FOR ALTERNATE HARDWARE INTERFACE CWE-1299

There is an undocumented RJ11 serial console on the iSTAR GCM (General Controller Module) which provides access to Uboot. On older firmware versions, an attacker with physical access to this console can get direct access to a shell with ‘root' privileges. In firmware Version 6.8.1 or newer, the console is disabled once the system has fully booted, however the console may be re-enabled due to lack of protection of the Uboot bootloader.

CVE-2025-53698 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-53698. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.5 MISSING PROTECTION MECHANISM FOR ALTERNATE HARDWARE INTERFACE CWE-1299

USB ports on the GCM board are typically used to connect an ACM (Access Control Module) board. The ACM is what reads badge data, ‘push to exit' signals, fire alarm signals, and operates relays to unlock doors. Physical access to GCM USB ports also allows USB devices, such as keyboards, to be connected and the system will treat the input from a connected keyboard as though it were typed on a local console.

CVE-2025-53699 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-53699. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.6 INSECURE STORAGE OF SENSITIVE INFORMATION CWE-922

The software signing key for Tyco NVR products is included in the firmware of iSTAR Ultra, Ultra SE, Ultra G2, Ultra G2 SE, Edge G2 versions 6.9.2 and prior. iSTAR Ultra and Ultra SE Versions 6.9.3 and newer reduces the risk of this vulnerability. iSTAR Ultra G2, Ultra G2 SE and Edge G2 version 6.9.3 and newer fixes this vulnerability.

CVE-2025-53700 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-53700. A base score of 6.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:N/SC:H/SI:H/SA:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Ireland

3.4 RESEARCHER

Reid Wightman of Dragos reported these vulnerabilities to Johnson Controls.

4. MITIGATIONS

Johnson Controls made firmware version 6.9.3 available in 2024 to fix CVE-2025-53695 and lower the risk of exploitation for CVE-2025-53696, CVE-2025-53697, and CVE-2025-53700.

Johnson Controls recommends users consider upgrading to a newer control unit. The hardware installation manual for iSTAR Ultra requires all control units be installed in a restricted access, protected area to lower the risk of physical tampering.

For more detailed mitigation instructions, see Johnson Controls Product Security Advisory.

For assistance and additional information, contact Johnson Controls Trust Center.

Dragos recommends end users place the following network restrictions around iSTAR controllers, regardless of model or firmware version:

  • Pro Mode on iSTAR Ultra and iSTAR Ultra door controllers should be disabled. Use "Ultra Mode."

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • August 12, 2025: Initial Publication

This product is provided subject to this Notification and this Privacy & Use policy.

Vendor

  • Johnson Controls