ICS Advisory

Siemens SIPROTEC 4 and SIPROTEC 4 Compact

Release Date
Alert Code
ICSA-25-226-12

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SIPROTEC 4 and SIPROTEC 4 Compact
  • Vulnerability: Improper Check for Unusual or Exceptional Conditions

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to cause a denial-of-service condition.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • SIPROTEC 4 6MD61: All versions
  • SIPROTEC 4 7SJ62: All versions
  • SIPROTEC 4 7SJ63: All versions
  • SIPROTEC 4 7SJ64: All versions
  • SIPROTEC 4 7SJ66: All versions
  • SIPROTEC 4 7SS52: All versions
  • SIPROTEC 4 7ST6: All versions
  • SIPROTEC 4 7UM61: All versions
  • SIPROTEC 4 7UM62: All versions
  • SIPROTEC 4 7UT63: All versions
  • SIPROTEC 4 7UT612: All versions
  • SIPROTEC 4 6MD63: All versions
  • SIPROTEC 4 7UT613: All versions
  • SIPROTEC 4 7VE6: All versions
  • SIPROTEC 4 7VK61: All versions
  • SIPROTEC 4 7VU683: All versions
  • SIPROTEC 4 Compact 7RW80: All versions
  • SIPROTEC 4 Compact 7SD80: All versions
  • SIPROTEC 4 Compact 7SJ80: All versions
  • SIPROTEC 4 Compact 7SJ81: All versions
  • SIPROTEC 4 Compact 7SK80: All versions
  • SIPROTEC 4 Compact 7SK81: All versions
  • SIPROTEC 4 6MD66: All versions
  • SIPROTEC 4 6MD665: All versions
  • SIPROTEC 4 7SA6: Versions prior to V4.78
  • SIPROTEC 4 7SA522: All versions
  • SIPROTEC 4 7SD5: Versions prior to V4.78
  • SIPROTEC 4 7SD610: Versions prior to V4.78
  • SIPROTEC 4 7SJ61: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER CHECK FOR UNUSUAL OR EXCEPTIONAL CONDITIONS CWE-754

Affected devices do not properly handle interrupted operations of file transfer. This could allow an unauthenticated remote attacker to cause a denial-of-service-condition. To restore normal operations, the devices need to be restarted.

CVE-2024-52504 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2024-52504. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • SIPROTEC 4 6MD61, SIPROTEC 4 6MD63, SIPROTEC 4 6MD66, SIPROTEC 4 6MD665, SIPROTEC 4 7SA522, SIPROTEC 4 7SJ61, SIPROTEC 4 7SJ62, SIPROTEC 4 7SJ63, SIPROTEC 4 7SJ64, SIPROTEC 4 7SS52, SIPROTEC 4 7ST6, SIPROTEC 4 7UM61, SIPROTEC 4 7UM62, SIPROTEC 4 7UT63, SIPROTEC 4 7UT612, SIPROTEC 4 7UT613, SIPROTEC 4 7VE6, SIPROTEC 4 7VK61, SIPROTEC 4 7VU683, SIPROTEC 4 Compact 7RW80, SIPROTEC 4 Compact 7SD80, SIPROTEC 4 Compact 7SJ80, SIPROTEC 4 Compact 7SJ81, SIPROTEC 4 Compact 7SK80, SIPROTEC 4 Compact 7SK81: Currently no fix is planned
  • SIPROTEC 4 7SJ66: Currently no fix is available
  • SIPROTEC 4 7SA6: Update to V4.78 or later version
  • SIPROTEC 4 7SD5: Update to V4.78 or later version
  • SIPROTEC 4 7SD610: Update to V4.78 or later version

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-400089 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • August 14, 2025: Initial Republication of Siemens ProductCERT SSA-400089

This product is provided subject to this Notification and this Privacy & Use policy.