ICS Advisory

Rockwell Automation Micro800

Release Date
Alert Code
ICSA-25-226-25

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: Micro800
  • Vulnerabilities: Dependency on Vulnerable Third-Party Component, Improper Input Validation

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could result in remote code execution or may lead to privilege escalation.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Rockwell Automation Micro800 are affected:

  • PLC Micro820 LC20: All versions prior to V14.011 (CVE-2023-48691, CVE-2023-48692, CVE-2023-48693)
  • PLC Micro850 LC50: All versions prior to V12.013 (CVE-2023-48691, CVE-2023-48692, CVE-2023-48693)
  • PLC Micro870 LC70: All versions prior to V12.013 (CVE-2023-48691, CVE-2023-48692, CVE-2023-48693)
  • PLC Micro850 L50E: Versions V20.011 through V22.011 (CVE-2023-48691, CVE-2023-48692, CVE-2023-48693, CVE-2025-7693)
  • PLC Micro870 L70E: Versions V20.011 through V22.011 (CVE-2023-48691, CVE-2023-48692, CVE-2023-48693, CVE-2025-7693)

3.2 VULNERABILITY OVERVIEW

3.2.1 DEPENDENCY ON VULNERABLE THIRD-PARTY COMPONENT CWE-1395

Azure RTOS NetX Duo is a TCP/IP network stack designed specifically for deeply embedded real-time and IoT applications. An attacker can cause an out-of-bounds write in Azure RTOS NETX Duo, that could lead to remote code execution.

CVE-2023-48691 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2023-48691. A base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 DEPENDENCY ON VULNERABLE THIRD-PARTY COMPONENT CWE-1395

Azure RTOS NetX Duo is a TCP/IP network stack designed specifically for deeply embedded real-time and IoT applications. An attacker can cause remote code execution due to memory overflow vulnerabilities in Azure RTOS NETX Duo.

CVE-2023-48692 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2023-48692. A base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.3 DEPENDENCY ON VULNERABLE THIRD-PARTY COMPONENT CWE-1395

Azure RTOS ThreadX is an advanced real-time operating system (RTOS) designed specifically for deeply embedded applications. An attacker can cause arbitrary read and write due to vulnerability in parameter checking mechanism in Azure RTOS ThreadX, which may lead to privilege escalation.

CVE-2023-48693 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2023-48693. A base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.4 IMPROPER INPUT VALIDATION CWE-20

A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.

CVE-2025-7693 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-7693. A base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Transportation Systems, Water and Wastewater
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported these vulnerabilities to CISA.

4. MITIGATIONS

Rockwell Automation recommends the following updates:

Rockwell Automation also recommends users follow their published Security Best Practices.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • August 14, 2025: Initial Republication: Initial Republication of Rockwell Automation’s SD1736