Rockwell Automation 1756-ENT2R, 1756-EN4TR, 1756-EN4TRXT (Update A)
1. EXECUTIVE SUMMARY
- CVSS v4 7.1
- ATTENTION: Low attack complexity
- Vendor: Rockwell Automation
- Equipment: 1756-ENT2R, 1756-EN4TR, 1756-EN4TRXT
- Vulnerabilities: Improper Input Validation, Improper Handling of Exceptional Conditions
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could result in an attacker causing a denial of service condition.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following Rockwell Automation products are affected:
- 1756-ENT2R: Version 6.001 and prior
- 1756-EN4TR: Version 6.001 and prior
- 1756-EN4TRXT: Version 6.001 and prior
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER INPUT VALIDATION CWE-20
A security issue exists in the protected mode of 1756-EN4TR and 1756-ENT2R communication modules, where a Concurrent Forward Close operation can trigger a Major Non-Recoverable (MNFR) fault. This condition may lead to unexpected system crashes and loss of device availability.
CVE-2025-8007 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2025-8007. A base score of 7.1 has been calculated; the CVSS vector string is (AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.2 IMPROPER HANDLING OF EXCEPTIONAL CONDITIONS CWE-755
A security issue exists in the protected mode of EN4TR devices, where sending specifically crafted messages during a Forward Close operation can cause the device to crash.
CVE-2025-8008 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2025-8008. A base score of 7.1 has been calculated; the CVSS vector string is (AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: United States
3.4 RESEARCHER
Rockwell Automation reported this vulnerability to CISA.
4. MITIGATIONS
Rockwell Automation recommends users upgrade their devices to 7.001 or later. The update can be downloaded from Rockwell Automation's website.
Rockwell Automation also recommends users follow their published Security Best Practices.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.
5. UPDATE HISTORY
- August 14, 2025: Initial Republication
- September 9, 2025: Adjusted affected versions
This product is provided subject to this Notification and this Privacy & Use policy.