ICS Advisory

Siemens Mendix SAML Module

Release Date
Alert Code
ICSA-25-231-02

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 8.7
  • ATTENTION: Exploitable remotely
  • Vendor: Siemens
  • Equipment: Mendix SAML Module
  • Vulnerability: Improper Verification of Cryptographic Signature

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow unauthenticated remote attackers to hijack an account in specific SSO configurations.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Siemens Mendix SAML (Mendix 9.24 compatible): Versions prior to V3.6.21
  • Siemens Mendix SAML (Mendix 10.12 compatible): Versions prior to V4.0.3
  • Siemens Mendix SAML (Mendix 10.21 compatible): Versions prior to V4.1.2

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER VERIFICATION OF CRYPTOGRAPHIC SIGNATURE CWE-347

Affected versions of the module insufficiently enforce signature validation and binding checks. This could allow unauthenticated remote attackers to hijack an account in specific SSO configurations.

CVE-2025-40758 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.7 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • All affected products: Make sure to use configurations where UseEncryption is enabled
  • Mendix SAML (Mendix 9.24 compatible): Update to V3.6.21 or later version
  • Mendix SAML (Mendix 10.12 compatible): Update to V4.0.3 or later version
  • Mendix SAML (Mendix 10.21 compatible): Update to V4.1.2 or later version

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-395458 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability has a high attack complexity.

5. UPDATE HISTORY

  • August 19, 2025: Initial Republication of Siemens ProductCERT SSA-395458