ICS Advisory

Schneider Electric Modicon M340 Controller and Communication Modules

Release Date
Alert Code
ICSA-25-238-03

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Schneider Electric
  • Equipment: Modicon M340 and Communication Modules
  • Vulnerability: Improper Input Validation

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Schneider Electric reports that the following products are affected:

  • Modicon M340: All versions
  • BMXNOR0200H Ethernet/Serial RTU Module: All versions
  • BMXNGD0100 M580 Global Data module: All versions
  • BMXNOC0401 Modicon M340 X80 Ethernet Communication modules: All versions
  • BMXNOE0100 Modbus/TCP Ethernet Modicon M340 module: Versions prior to 3.60
  • BMXNOE0110 Modbus/TCP Ethernet Modicon M340 FactoryCast module: Versions prior to 6.80

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER INPUT VALIDATION CWE-20

Improper Input Validation vulnerability exists that could cause a Denial-of-Service when specially crafted FTP command is sent to the device.

CVE-2025-6625 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-6625. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: France

3.4 RESEARCHER

CyManII reported this vulnerability to Schneider Electric.

4. MITIGATIONS

Schneider Electric has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • BMXNOE0100 Modbus/TCP Ethernet Modicon M340 module: Version 3.60 of BMXNOE0100 includes a fix for this vulnerability and is available for download here. Reboot is needed to complete the firmware upgrade.
  • BMXNOE0110 Modbus/TCP Ethernet Modicon M340 FactoryCast module: Version 6.80 of BMXNOE0110 includes a fix for this vulnerability and is available for download here. Reboot is needed to complete the firmware upgrade.

Schneider Electric is establishing a remediation plan for all future versions of Modicon M340, BMXNOR0200H, BMXNGD0100, and BMXNOC401. Until then, users should immediately apply the following mitigations to reduce the risk of exploit:

  • FTP service is disabled by default
  • Ensure to disable FTP service when not in use
  • Setup network segmentation and implement a firewall to block all unauthorized access to ports 21/FTP
  • Use VPN (Virtual Private Networks) tunnels if remote access is required

For more information see the associated Schneider Electric CPCERT security advisory SEVD-2025-224-05.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • August 26, 2025: Initial Republication of Schneider Electric SEVD-2025-224-05

This product is provided subject to this Notification and this Privacy & Use policy.

Vendor

  • Schneider Electric