Rockwell Automation Stratix IOS
1. EXECUTIVE SUMMARY
- CVSS v4 8.6
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Rockwell Automation
- Equipment: Stratix IOS
- Vulnerability: Injection
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to run malicious configurations without authentication.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of Stratix IOS are affected:
- Stratix IOS: Versions 15.2(8)E5 and prior
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS IN OUTPUT USED BY A DOWNSTREAM COMPONENT ('INJECTION') CWE-74
A security issue affecting multiple Cisco devices also directly impacts Stratix® 5410, 5700, and 8000 devices. This can lead to remote code execution by uploading and running malicious configurations without authentication.
CVE-2025-7350 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-7350. A base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: United States
3.4 RESEARCHER
Rockwell Automation reported this vulnerability to CISA.
4. MITIGATIONS
Rockwell Automation has provided an update that mitigates this vulnerability. Users are recommended to update to version 15.2(8)E6 or later.
If users are not able to upgrade to the corrected version, Rockwell Automation recommends referring to their security best practices.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.
5. UPDATE HISTORY
- September 09, 2025: Initial Republication of Rockwell Automation advisory
This product is provided subject to this Notification and this Privacy & Use policy.