As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
1. EXECUTIVE SUMMARY
- CVSS v4 9.3
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Siemens
- Equipment: User Management Component (UMC)
- Vulnerabilities: Stack-based Buffer Overflow, Out-of-bounds Read
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an unauthenticated remote attacker to execute arbitrary code or to cause a denial-of-service condition.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:
- Siemens SIMATIC PCS neo V4.1: All versions
- Siemens SIMATIC PCS neo V5.0: All versions
- Siemens User Management Component (UMC): Versions prior to 2.15.1.3
3.2 VULNERABILITY OVERVIEW
3.2.1 STACK-BASED BUFFER OVERFLOW CWE-121
Affected products contain a stack-based buffer overflow vulnerability in the integrated UMC component. This vulnerability could allow an unauthenticated remote attacker to execute arbitrary code or to cause a denial-of-service condition.
CVE-2025-40795 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-40795. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.2 OUT-OF-BOUNDS READ CWE-125
Affected products contain an out-of-bounds read vulnerability in the integrated UMC component. This vulnerability could allow an unauthenticated remote attacker to cause a denial-of-service condition.
CVE-2025-40796 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2025-40796. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.3 OUT-OF-BOUNDS READ CWE-125
Affected products contain an out-of-bounds read vulnerability in the integrated UMC component. This vulnerability could allow an unauthenticated remote attacker to cause a denial-of-service condition.
CVE-2025-40797 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2025-40797. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.4 OUT-OF-BOUNDS READ CWE-125
Affected products contain an out-of-bounds read vulnerability in the integrated UMC component. This vulnerability could allow an unauthenticated remote attacker to cause a denial-of-service condition.
CVE-2025-40798 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2025-40798. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
3.4 RESEARCHER
Tenable reported these vulnerabilities to Siemens.
4. MITIGATIONS
Siemens has released a new version for User Management Component (UMC) and recommends updating to the latest version. Siemens recommends specific countermeasures for products where fixes are not available or are not yet available.
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:
- User Management Component (UMC): Update to V2.15.1.3 or later version.
- All affected products: In non-networked scenarios/deployments, block TCP ports 4002 and 4004 on machines with UMC installed. If the deployment is not using the 'RT Server' type of UMC machine, port 4004 can be blocked everywhere without impacting network functionality for all other UMC machine-types (Server, Ring-Server, Agent).
- SIMATIC PCS neo V4.1, SIMATIC PCS neo V5.0: No fix is currently planned.
As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.
For more information, see the associated Siemens security advisory SSA-722410 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as virtual private networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY
- September 11, 2025: Initial Republication of Siemens SSA-722410
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Siemens