ICS Advisory

Schneider Electric Communication Modules for Modicon M580 and Quantum Controllers (Update B)

Last Revised
Alert Code
ICSA-25-058-01

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Schneider Electric
  • Equipment: Communication modules for Modicon M580 and Quantum controllers
  • Vulnerability: Out-of-bounds Write

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow a stack overflow attack, which could result in loss of confidentiality, integrity, and denial of service of the device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Schneider Electric reports the following communication modules for Modicon M580 and Quantum controllers are affected by a vulnerability in VxWorks operating system:

  • Modicon M580 communication modules BMENOC BMENOC0321: Versions prior to SV1.10
  • Modicon M580 communication modules BMECRA BMECRA31210: Versions prior to SV02.80
  • Modicon M580/Quantum communication modules BMXCRA BMXCRA31200: Versions prior to SV02.80
  • Modicon M580/Quantum communication modules BMXCRA BMXCRA31210: Versions prior to SV02.80
  • 140CRA31200 (Quantum RIO Drop) 140CRA31200: Versions prior to V02.80
  • 140CRA31908 (M580 Quantum S908 RIO Drop Adapter) 140CRA31908: Versions prior to V02.80

3.2 VULNERABILITY OVERVIEW

3.2.1 OUT-OF-BOUNDS WRITE CWE-787

An issue was discovered in Wind River VxWorks through Version 6.8, where a potential stack overflow exists in the DHCP server.

CVE-2021-29999 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2021-29999. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: France

3.4 RESEARCHER

Schneider Electric reported this vulnerability to CISA.

4. MITIGATIONS

Schneider Electric has identified the following specific remediations and mitigations users can apply to reduce risk:

  • Modicon M580 communication modules BMENOC BMENOC0321: Version SV1.10 of BMENOC0321 includes a fix for this vulnerability and is available for download.
  • Modicon M580 communication modules BMECRA BMECRA31210, Modicon M580/Quantum communication modules BMXCRA BMXCRA31200/BMXCRA31210: Version SV02.80 of BMECRA31210, BMXCRA31200, BMXCRA31210 includes a fix for these vulnerabilities and is available for download.
  • 140CRA31200 (Quantum RIO Drop): Version V02.80 of 140CRA31200 includes a fix for these vulnerabilities and is available for download.
  • 140CRA31908 (M580 Quantum S908 RIO Drop Adapter): Version V02.80 of 140CRA31908 includes a fix for these vulnerabilities and is available for download.

Schneider Electric strongly recommends the following industry cybersecurity best practices:

  • Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
  • Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
  • Place all controllers in locked cabinets and never leave them in the "Program" mode.
  • Never connect programming software to any network other than the network intended for that device.
  • Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
  • Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
  • Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
  • When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.

For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.

For more information, see Schneider Electric security notification "SEVD-2025-014-03 Wind River VxWorks DHCP server vulnerability"

Additional information about the vulnerability can be found on the Wind River site.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 27, 2025: Initial Republication of Schneider Electric SEVD-2025-014-03
  • April 17, 2025: Update A - A remediation is now available for BMECRA31210, BMXCRA31200, and BMXCRA31210.
  • September 9, 2025: Update B - Remediations are available for 140CRA31200 (Quantum RIO Drop) and 140CRA31908 (M580
    Quantum S908 RIO Drop Adapter)