ICS Advisory

Siemens APOGEE PXC and TALON TC Series

Release Date
Alert Code
ICSA-25-135-14

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 5.3
  • ATTENTION: Exploitable from adjacent network/low attack complexity
  • Vendor: Siemens
  • Equipment: APOGEE PXC and TALON TC Series
  • Vulnerability: Expected Behavior Violation

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to cause a partial denial of service and reduce network availability.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports the following products are affected:

  • Siemens APOGEE PXC+TALON TC Series: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 EXPECTED BEHAVIOR VIOLATION CWE-440

The affected devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device's normal operation.

CVE-2025-40555 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.7 has been calculated; the CVSS vector string is (CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:L).

A CVSS v4 score has also been calculated for CVE-2025-40555. A base score of 5.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Energy, Government Facilities, Healthcare and Public Health, Information Technology, Transportation Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens ProductCERT reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • APOGEE PXC+TALON TC Series (BACnet): Currently no fix is planned

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-718393 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

May 15, 2025: Initial Republication of Siemens ProductCERT SSA-718393