Schneider Electric Saitel DR & Saitel DP Remote Terminal Unit
1. EXECUTIVE SUMMARY
- CVSS v4 5.8
- ATTENTION: Low Attack Complexity
- Vendor: Schneider Electric
- Equipment: Saitel DR RTU
- Vulnerabilities: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection')
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could enable an attacker to execute arbitrary shell commands on the affected devices.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Schneider Electric reports that the following products are affected:
- Schneider Electric Saitel DR RTU: Versions 11.06.29 and prior
- Schneider Electric Saitel DP RTU: Versions 11.06.33 and prior
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND ('OS COMMAND INJECTION') CWE-78
An OS command injection vulnerability exists that could cause the execution of any shell command when executing a netstat command using BLMon Console in an SSH session.
CVE-2025-9996 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.6 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:L/A:L).
A CVSS v4 score has also been calculated for CVE-2025-9996. A base score of 5.8 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:P/PR:L/UI:N/VC:H/VI:L/VA:L/SC:N/SI:N/SA:N).
3.2.2 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND ('OS COMMAND INJECTION') CWE-78
CWE-78: Improper Neutralization of Special Elements used in an OS Command vulnerability exists that could cause command injection in BLMon that is executed in the operating system console when in an SSH session.
CVE-2025-9997 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.6 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:L/A:L).
A CVSS v4 score has also been calculated for CVE-2025-9997. A base score of 5.8 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:P/PR:L/UI:N/VC:H/VI:L/VA:L/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Energy
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: France
3.4 RESEARCHER
Robin Senn of GAI NetConsult GmbH reported CVE-2025-9996 to Schneider Electric. Sebastian Krause of GAI NetConsult GmbH reported CVE-2025-9997 to Schneider Electric. Schneider Electric reported these vulnerabilities to CISA.
4. MITIGATIONS
Schneider Electric has identified the following specific workarounds and mitigations users can apply to reduce risk:
- Schneider Electric Saitel DR RTU Versions 11.06.29 and prior: HUe Firmware version 11.06.30 of Saitel DR includes a fix for this vulnerability and is available for download. A reboot is necessary to complete the firmware upgrade.
- Schneider Electric Saitel DP RTU Versions 11.06.33 and prior: Firmware SM_CPU866e version 11.06.34 of Saitel DP includes a fix for this vulnerability and is available for download. A reboot is necessary to complete the firmware upgrade.
Schneider Electric recommends that users follow appropriate patching methodologies when applying these patches to their systems. They strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric's Customer Care Center for assistance removing a patch.
If users are unable to apply these patches, Schneider Electric recommends immediately applying the following mitigations to reduce the risk of exploitation:
- Restrict access to BLMon by assigning permissions only to a limited set of user roles.
- Ensure users are assigned the least privileged role that still allows them to perform their designated tasks.
- Implement firewall rules to restrict SSH connections to the device.
Schneider Electric strongly recommends the following industry cybersecurity best practices.
- Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
- Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
- Place all controllers in locked cabinets and never leave them in the "Program" mode.
- Never connect programming software to any network other than the network intended for that device.
- Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
- Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
- Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For more information see the associated Schneider Electric CPCERT security advisory SEVD-2025-252-02 Saitel DR & Saitel DP Remote Terminal Unit - SEVD-2025-252-02 PDF Version, Saitel DR & Saitel DP Remote Terminal Unit - SEVD-2025-252-02 CSAF Version.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.
5. UPDATE HISTORY
- September 18, 2025: Initial Republication of Schneider Electric SEVD-2025-252-02
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Schneider Electric